A B B M E A S U R E M E N T & A N A L Y T I C S | O P E R A T I N G I N S T R U C T I O N | O I / E B N 8 5 3 / E B N 8 6 1 / E X - E N R E V . C
EBN853 / EBN861
Electronic unit for field installation (Contrac)
Introduction
EBN853
EBN861
The electronic unit builds the interface between
the actuator and the control system.
During continuous positioning, the electronic unit
varies the motor torque continuously until the
actuator force and the control valve force are
balanced.
High response sensitivity and high positioning
accuracy with short positioning time ensure an
excellent control quality and a long actuator life.
For the control of Contrac control
actuators in potentially explosive
atmospheres
Additional Information
Additional documentation on EBN853 / EBN861 is
available for download free of charge at
www.abb.com/actuators.
Alternatively simply scan this code:

Advertisement

Table of Contents
loading

Summary of Contents for ABB EBN861

  • Page 1 Introduction Additional Information EBN853 EBN861 The electronic unit builds the interface between Additional documentation on EBN853 / EBN861 is the actuator and the control system. available for download free of charge at During continuous positioning, the electronic unit www.abb.com/actuators. varies the motor torque continuously until the...
  • Page 2: Table Of Contents

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Table of contents Change from one to two columns Safety ................3 Electronic Unit EBN853 (Contrac) ........21 General information and instructions ........3 Analog / Digital ..............21 Warnings ..................3 PROFIBUS DP®...
  • Page 3: Safety

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Change from one to two columns 1 Safety General information and instructions Warnings The warnings in these instructions are structured as follows: These instructions are an important part of the product and must be retained for future reference.
  • Page 4: Intended Use

    Warranty provisions Using the device in a manner that does not fall within the scope The electronic units of type EBN853 / EBN861 interconnected as of its intended use, disregarding this manual, using illustrated in this operating instruction are used exclusively to underqualified personnel, or making unauthorized alterations control the RHDE...
  • Page 5: Use In Potentially Explosive Atmospheres

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 2 Use in potentially explosive atmospheres Cable harness for the connection of the DANGER actuator to the electronic unit Explosion hazard due to improper installation! An explosion hazard is present when installing the electronic Installation information on the cable harness for actuators in unit in potentially explosive atmospheres.
  • Page 6: Specification

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 2 Use in potentially explosive atmospheres … Cable harness for the connection of the actuator to the electronic unit Specification Motor connection Motor temperature monitoring Signal terminal (option) Wire conductor 8 ×...
  • Page 7 EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Option Motor connection Motor temperature monitoring Signal terminal (option) Manufacturer Pflitsch Pflitsch Type blue globe ATEX blue globe ATEX Diameter M25 × 1.5 KAD20-16/16-11 M20 × 1.5 KAD14-9/9-5 Article no. bg225 msex...
  • Page 8: Overview

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 2 Use in potentially explosive atmospheres Overview Figure 1: Allocation of the Contrac components when using in potentially explosive atmospheres (example) Change from one to two columns...
  • Page 9: Design And Function

    3 Design and function Design EBN861 The electronic units EBN853 and EBN861 consist of two housing halves, one holding the connection components and the transformer, the other holding the electronics and the commissioning and service field (ISF) for ‘local operation’ of the actuator.
  • Page 10: Principle Of Operation

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 3 Design and function Principle of operation The electronic unit builds the interface between the actuator and the control system. During continuous positioning, the electronic unit varies the motor torque continuously until the actuator force and the control valve force are balanced.
  • Page 11: Device Designs

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Device designs EBN853 IP rating IP 66 in accordance with IEC 60529 / EN 60529 NEMA 4X in accordance with CAN / CSA22.2 No. 94 Humidity ≤ 95% annual average; condensation not permitted Ambient temperature −25 to 55 °C (−13 to 131 °F)
  • Page 12: Product Identification

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 4 Product identification Note In electronic units which can be separated for assembly, the name plate for the hardware is located on the lower part of the electronic unit (Figure 1). The name plate for the software (Figure 2) and an additional name plate for the hardware (Figure 3) are located on the electronic unit cover.
  • Page 13: Delivery Status

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Delivery status The individual actuator configuration may vary from the PROFIBUS DP® communication standard setup above. This information can be displayed via the Parameter Setting user interface. Function selection Positioner, parameter: set point...
  • Page 14: Transport And Storage

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 5 Transport and storage Inspection Storing the device Check the devices immediately after unpacking for possible Note damage that may have occurred from improper transport. The storage data provided below assumes that the devices are...
  • Page 15: Installation

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 6 Installation Mounting EBN853 NOTICE 1. Fasten the electronic unit to a vertical mounting plate using Damage to components! grade 8.8 screws. Tensile strength 800 N/mm Damage to components caused by ingress of foreign bodies (116032 pounds/square in.), yield strength 640 N/mm...
  • Page 16: Dimensions

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 6 Installation Dimensions Electronic unit EBN853 (Contrac) 1 Back view 3 Side view 2 Leave at least 100 mm (3.94 in) distance for the cable gland and cable 4 Front view...
  • Page 17: Electronic Unit Ebn861 (Contrac)

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Electronic unit EBN861 (Contrac) 1 Front section open, rotated 90° 2 Rotational radius 3 Tap holes Figure 8: Dimensions in mm (in) Change from one to two columns...
  • Page 18: Electrical Connections

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 7 Electrical connections Safety instructions General Each actuator requires a suited Contrac electronic unit with WARNING installed actuator-specific software. Observe the information in Risk of injury due to live parts! the operating instruction. The specifications on the name plates...
  • Page 19: Conductor Cross-Section On Control Actuator

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Conductor cross-section on control actuator Cable glands Screw terminals Motor/brake max. 2.5 mm (14 AWG) DANGER Signals max. 2.5 mm (14 AWG) Risk of explosion! Risk of explosion due to the use of unsuitable cable glands.
  • Page 20: Selection Of Suited Connection Cables

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 7 Electrical connections … Conductor cross-section on electronic unit Selection of suited connection cables Please observe the following information when installing the Please observe the following information when selecting cables: cable set: •...
  • Page 21: Electronic Unit Ebn853 (Contrac)

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Electronic Unit EBN853 (Contrac) Analog / Digital Note The electrical connection is established via screw terminals on the control actuator and on the electronic unit. DI = digital input DO = digital output...
  • Page 22: Profibus Dp

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 7 Electrical connections … Electronic Unit EBN853 (Contrac) PROFIBUS DP® Note The electrical connection is established via screw terminals on the control actuator and on the electronic unit. DO = digital output...
  • Page 23: Analog / Digital

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Electronic Unit EBN861 (Contrac) Analog / Digital Note • The electrical connection is established via screw terminals on the control actuator and on the electronic unit. • If you are using a separate heat supply, the heater must be protected with a 2 to 6 A medium time-lag fuse (e.g. NEOZED D01 E14).
  • Page 24: Profibus Dp

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 7 Electrical connections … Electronic Unit EBN853 (Contrac) PROFIBUS DP® Note • The electrical connection is established via screw terminals on the control actuator and on the electronic unit. •...
  • Page 25: Connection Examples

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Connection examples Operation following a continuous set point (standard) In the standard configuration, the binary inputs are configured as ‘MANUAL OPERATION’. To switch the actuator to automatic mode (AUT), the following conditions must be met: •...
  • Page 26 EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 7 Electrical connections … Connection examples Operation downstream from step controller Contrac actuators can be driven using step controller pulses instead of an analog setpoint. The following conditions must be fulfilled in order to implement the step controller pulses: •...
  • Page 27: Electrical Data For Inputs And Outputs

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Electrical data for inputs and outputs Power supply EBN853 Supply voltage (standard actuators) 115 V AC (94 to 130 V) or 230 V AC (190 to 260 V); 47.5 to 63 Hz; single-phase Supply voltage (Ex actuators) 115 V AC (94 to 127 V) or 230 V AC (190 to 253 V);...
  • Page 28 EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 7 Electrical connections … Electrical data for inputs and outputs Binary inputs and outputs - communication Conventional communication Analog input 0 / 4 to 20 mA, internal load: 300 Ω...
  • Page 29 EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C PROFIBUS DP® Communication PNO ID no. 0×9655 Actuators with DP/V0 communication (cyclic data traffic) 0×09EC Actuators with DP/V1 communication (cyclic and acyclic data traffic) Communication protocol PROFIBUS PA® Profile V3.0 Class B in accordance with IEC 50170 / EN 50170 (DIN 19245) Bus cable Twisted, shielded copper wire acc.
  • Page 30: Connection On The Device

    The conductor cross-section between the fuses and the electronic unit must be at least 2.5 mm (AWG 14). In addition to the internal fuses, the EBN861 electronic unit requires two additional external fuses which are supplied separately with the assembly.
  • Page 31: Commissioning And Operation

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 8 Commissioning and operation Engineering Software ECOM688 and ECOM700 Note It is imperative that you observe the operating instruction of the Using the ECOM688 / ECOM700 engineering software, the user corresponding actuator for the commissioning of the electronic...
  • Page 32: Commissioning And Service Field

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 8 Commissioning and operation Commissioning and service field Operating element Description Write protection switch Activates the hardware write protection. Factory setting: OFF – write protection deactivated. Refer to Hardware write protection on page 34.
  • Page 33: Meaning Of The Led Indicators

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Meaning of the LED indicators The LEDs 100 % / 0 % on the commissioning and service field (Figure 17 on page 32, Pos. ) flash at different rates, depending on the function that has been initiated.
  • Page 34: Hardware Settings

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 8 Commissioning and operation Hardware settings Hardware write protection Defining the initial position (0 % or 100 %) If write protection is active, the device parameterization cannot 2. Use one of the travel buttons to move to the desired be changed.
  • Page 35: Manual (Man)- And Automatic Operation (Aut)

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Manual (MAN)- and Automatic Operation (AUT) Signaling on the commissioning and service field Software version 2.00 and higher In the manual operating mode (MAN), the actuator solely reacts upon actuation of either of the two travel buttons on the...
  • Page 36: Diagnosis / Error Messages

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 9 Diagnosis / error messages Definition – Alarms and Errors Alarms The actuator / electronic unit is in a critical state (e.g., high temperature), which currently does not affect the actuator, electronic unit, process or persons.
  • Page 37: Error Diagram

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Error Diagram Positioning loop monitoring Hardware monitoring Software monitoring Standstill Frequency converter end Error position transmitter memory Min. speed positions Flash Error Movement in incorrect direction RAM error Watchdog monitoring activated Monitoring ON &...
  • Page 38: Hardware Errors

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 9 Diagnosis / error messages Hardware Errors This chapter only covers hardware-related errors. For additional troubleshooting information, refer to the online help for the operator interface. Error Possible cause Troubleshooting the Instrument Valve cannot be moved by actuator.
  • Page 39: Maintenance

    All devices delivered to ABB must be free from any hazardous Contrac actuators feature a robust construction. As a result, materials (acids, alkalis, solvents, etc.).
  • Page 40: Fuses

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 11 Repair Fuses Type Fuse Installation location Design Rated current of fuse at 115 V AC at 230 V AC EBN853 External fuse External – 16 A, time-lag 16 A, time-lag...
  • Page 41: Recycling And Disposal

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 12 Recycling and disposal 13 Approvals and certifications Note CE mark The version of the device as provided by us meets the Products that are marked with the adjacent symbol requirements of the following EU directives: may not be disposed of as unsorted municipal waste •...
  • Page 42: Appendix

    EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 15 Appendix Return form Statement on the contamination of devices and components Repair and/or maintenance work will only be performed on devices and components if a statement form has been completed and submitted.
  • Page 43 EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Trademarks HART is a registered trademark of FieldComm Group, Austin, Texas, USA PROFIBUS and PROFIBUS DP are registered trademarks of PROFIBUS & PROFINET International (PI)
  • Page 44 We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.