Introduction Additional Information EBN853 EBN861 The electronic unit builds the interface between Additional documentation on EBN853 / EBN861 is the actuator and the control system. available for download free of charge at During continuous positioning, the electronic unit www.abb.com/actuators. varies the motor torque continuously until the...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Table of contents Change from one to two columns Safety ................3 Electronic Unit EBN853 (Contrac) ........21 General information and instructions ........3 Analog / Digital ..............21 Warnings ..................3 PROFIBUS DP®...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Change from one to two columns 1 Safety General information and instructions Warnings The warnings in these instructions are structured as follows: These instructions are an important part of the product and must be retained for future reference.
Warranty provisions Using the device in a manner that does not fall within the scope The electronic units of type EBN853 / EBN861 interconnected as of its intended use, disregarding this manual, using illustrated in this operating instruction are used exclusively to underqualified personnel, or making unauthorized alterations control the RHDE...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 2 Use in potentially explosive atmospheres Cable harness for the connection of the DANGER actuator to the electronic unit Explosion hazard due to improper installation! An explosion hazard is present when installing the electronic Installation information on the cable harness for actuators in unit in potentially explosive atmospheres.
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 2 Use in potentially explosive atmospheres … Cable harness for the connection of the actuator to the electronic unit Specification Motor connection Motor temperature monitoring Signal terminal (option) Wire conductor 8 ×...
Page 7
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Option Motor connection Motor temperature monitoring Signal terminal (option) Manufacturer Pflitsch Pflitsch Type blue globe ATEX blue globe ATEX Diameter M25 × 1.5 KAD20-16/16-11 M20 × 1.5 KAD14-9/9-5 Article no. bg225 msex...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 2 Use in potentially explosive atmospheres Overview Figure 1: Allocation of the Contrac components when using in potentially explosive atmospheres (example) Change from one to two columns...
3 Design and function Design EBN861 The electronic units EBN853 and EBN861 consist of two housing halves, one holding the connection components and the transformer, the other holding the electronics and the commissioning and service field (ISF) for ‘local operation’ of the actuator.
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 3 Design and function Principle of operation The electronic unit builds the interface between the actuator and the control system. During continuous positioning, the electronic unit varies the motor torque continuously until the actuator force and the control valve force are balanced.
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Device designs EBN853 IP rating IP 66 in accordance with IEC 60529 / EN 60529 NEMA 4X in accordance with CAN / CSA22.2 No. 94 Humidity ≤ 95% annual average; condensation not permitted Ambient temperature −25 to 55 °C (−13 to 131 °F)
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 4 Product identification Note In electronic units which can be separated for assembly, the name plate for the hardware is located on the lower part of the electronic unit (Figure 1). The name plate for the software (Figure 2) and an additional name plate for the hardware (Figure 3) are located on the electronic unit cover.
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Delivery status The individual actuator configuration may vary from the PROFIBUS DP® communication standard setup above. This information can be displayed via the Parameter Setting user interface. Function selection Positioner, parameter: set point...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 5 Transport and storage Inspection Storing the device Check the devices immediately after unpacking for possible Note damage that may have occurred from improper transport. The storage data provided below assumes that the devices are...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 6 Installation Mounting EBN853 NOTICE 1. Fasten the electronic unit to a vertical mounting plate using Damage to components! grade 8.8 screws. Tensile strength 800 N/mm Damage to components caused by ingress of foreign bodies (116032 pounds/square in.), yield strength 640 N/mm...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 6 Installation Dimensions Electronic unit EBN853 (Contrac) 1 Back view 3 Side view 2 Leave at least 100 mm (3.94 in) distance for the cable gland and cable 4 Front view...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Electronic unit EBN861 (Contrac) 1 Front section open, rotated 90° 2 Rotational radius 3 Tap holes Figure 8: Dimensions in mm (in) Change from one to two columns...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 7 Electrical connections Safety instructions General Each actuator requires a suited Contrac electronic unit with WARNING installed actuator-specific software. Observe the information in Risk of injury due to live parts! the operating instruction. The specifications on the name plates...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Conductor cross-section on control actuator Cable glands Screw terminals Motor/brake max. 2.5 mm (14 AWG) DANGER Signals max. 2.5 mm (14 AWG) Risk of explosion! Risk of explosion due to the use of unsuitable cable glands.
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 7 Electrical connections … Conductor cross-section on electronic unit Selection of suited connection cables Please observe the following information when installing the Please observe the following information when selecting cables: cable set: •...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Electronic Unit EBN853 (Contrac) Analog / Digital Note The electrical connection is established via screw terminals on the control actuator and on the electronic unit. DI = digital input DO = digital output...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 7 Electrical connections … Electronic Unit EBN853 (Contrac) PROFIBUS DP® Note The electrical connection is established via screw terminals on the control actuator and on the electronic unit. DO = digital output...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Electronic Unit EBN861 (Contrac) Analog / Digital Note • The electrical connection is established via screw terminals on the control actuator and on the electronic unit. • If you are using a separate heat supply, the heater must be protected with a 2 to 6 A medium time-lag fuse (e.g. NEOZED D01 E14).
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 7 Electrical connections … Electronic Unit EBN853 (Contrac) PROFIBUS DP® Note • The electrical connection is established via screw terminals on the control actuator and on the electronic unit. •...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Connection examples Operation following a continuous set point (standard) In the standard configuration, the binary inputs are configured as ‘MANUAL OPERATION’. To switch the actuator to automatic mode (AUT), the following conditions must be met: •...
Page 26
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 7 Electrical connections … Connection examples Operation downstream from step controller Contrac actuators can be driven using step controller pulses instead of an analog setpoint. The following conditions must be fulfilled in order to implement the step controller pulses: •...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Electrical data for inputs and outputs Power supply EBN853 Supply voltage (standard actuators) 115 V AC (94 to 130 V) or 230 V AC (190 to 260 V); 47.5 to 63 Hz; single-phase Supply voltage (Ex actuators) 115 V AC (94 to 127 V) or 230 V AC (190 to 253 V);...
Page 28
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 7 Electrical connections … Electrical data for inputs and outputs Binary inputs and outputs - communication Conventional communication Analog input 0 / 4 to 20 mA, internal load: 300 Ω...
Page 29
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C PROFIBUS DP® Communication PNO ID no. 0×9655 Actuators with DP/V0 communication (cyclic data traffic) 0×09EC Actuators with DP/V1 communication (cyclic and acyclic data traffic) Communication protocol PROFIBUS PA® Profile V3.0 Class B in accordance with IEC 50170 / EN 50170 (DIN 19245) Bus cable Twisted, shielded copper wire acc.
The conductor cross-section between the fuses and the electronic unit must be at least 2.5 mm (AWG 14). In addition to the internal fuses, the EBN861 electronic unit requires two additional external fuses which are supplied separately with the assembly.
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 8 Commissioning and operation Engineering Software ECOM688 and ECOM700 Note It is imperative that you observe the operating instruction of the Using the ECOM688 / ECOM700 engineering software, the user corresponding actuator for the commissioning of the electronic...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 8 Commissioning and operation Commissioning and service field Operating element Description Write protection switch Activates the hardware write protection. Factory setting: OFF – write protection deactivated. Refer to Hardware write protection on page 34.
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Meaning of the LED indicators The LEDs 100 % / 0 % on the commissioning and service field (Figure 17 on page 32, Pos. ) flash at different rates, depending on the function that has been initiated.
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 8 Commissioning and operation Hardware settings Hardware write protection Defining the initial position (0 % or 100 %) If write protection is active, the device parameterization cannot 2. Use one of the travel buttons to move to the desired be changed.
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Manual (MAN)- and Automatic Operation (AUT) Signaling on the commissioning and service field Software version 2.00 and higher In the manual operating mode (MAN), the actuator solely reacts upon actuation of either of the two travel buttons on the...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 9 Diagnosis / error messages Definition – Alarms and Errors Alarms The actuator / electronic unit is in a critical state (e.g., high temperature), which currently does not affect the actuator, electronic unit, process or persons.
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Error Diagram Positioning loop monitoring Hardware monitoring Software monitoring Standstill Frequency converter end Error position transmitter memory Min. speed positions Flash Error Movement in incorrect direction RAM error Watchdog monitoring activated Monitoring ON &...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 9 Diagnosis / error messages Hardware Errors This chapter only covers hardware-related errors. For additional troubleshooting information, refer to the online help for the operator interface. Error Possible cause Troubleshooting the Instrument Valve cannot be moved by actuator.
All devices delivered to ABB must be free from any hazardous Contrac actuators feature a robust construction. As a result, materials (acids, alkalis, solvents, etc.).
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C … 11 Repair Fuses Type Fuse Installation location Design Rated current of fuse at 115 V AC at 230 V AC EBN853 External fuse External – 16 A, time-lag 16 A, time-lag...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 12 Recycling and disposal 13 Approvals and certifications Note CE mark The version of the device as provided by us meets the Products that are marked with the adjacent symbol requirements of the following EU directives: may not be disposed of as unsorted municipal waste •...
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C 15 Appendix Return form Statement on the contamination of devices and components Repair and/or maintenance work will only be performed on devices and components if a statement form has been completed and submitted.
Page 43
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C Trademarks HART is a registered trademark of FieldComm Group, Austin, Texas, USA PROFIBUS and PROFIBUS DP are registered trademarks of PROFIBUS & PROFINET International (PI)
Page 44
We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.