Siemens RUGGEDCOM RS8000 Installation Manual
Siemens RUGGEDCOM RS8000 Installation Manual

Siemens RUGGEDCOM RS8000 Installation Manual

Hide thumbs Also See for RUGGEDCOM RS8000:

Advertisement

Quick Links

RUGGEDCOM RS8000
Installation Guide
07/2018
RC1020-EN-04
Preface
Introduction
Installing the Device
Device Management
Communication Ports
Technical Specifications
Certification
1
2
3
4
5
6

Advertisement

Table of Contents
loading

Summary of Contents for Siemens RUGGEDCOM RS8000

  • Page 1 Preface Introduction Installing the Device RUGGEDCOM RS8000 Device Management Communication Ports Technical Specifications Installation Guide Certification 07/2018 RC1020-EN-04...
  • Page 2 Warranty Siemens warrants this product for a period of five (5) years from the date of purchase, conditional upon the return to factory for maintenance during the warranty term. This product contains no user-serviceable parts. Attempted service by unauthorized personnel shall render all warranties null and void.
  • Page 3 RUGGEDCOM RS8000 Installation Guide Contacting Siemens Address Telephone E-mail Siemens Canada Ltd Toll-free: 1 888 264 0006 ruggedcom.info.i-ia@siemens.com Industry Sector Tel: +1 905 856 5288 300 Applewood Crescent Fax: +1 905 856 1995 Concord, Ontario https://www.siemens.com/ruggedcom Canada, L4K 5C7...
  • Page 4 RUGGEDCOM RS8000 Installation Guide...
  • Page 5: Table Of Contents

    RUGGEDCOM RS8000   Installation Guide Table of Contents Table of Contents Preface ......................Alerts ..............................vii Related Documents ..........................viii Accessing Documentation ........................viii Training ............................viii Customer Support ..........................viii Chapter 1 Introduction ..................... 1.1  Feature Highlights ........................1 1.2    Description ........................... 2 1.3  Required Tools and Materials ......................
  • Page 6   RUGGEDCOM RS8000 Table of Contents Installation Guide Chapter 4 Communication Ports ..................Chapter 5 Technical Specifications .................. 5.1  Power Supply Specifications ......................19 5.2  Failsafe Relay Specifications ......................19 5.3  Fiber Optic Ethernet Port Specifications ..................20 5.4  Operating Environment ....................... 20 5.5  Mechanical Specifications ......................20 5.6  Dimension Drawings ........................
  • Page 7: Preface

    Installation Guide Preface Preface This guide describes the RUGGEDCOM RUGGEDCOM RS8000. It describes the major features of the device, installation, commissioning and important technical specifications. It is intended for use by network technical support personnel who are responsible for the installation, commissioning and maintenance of the device.
  • Page 8: Related Documents

    Siemens Sales representative. Customer Support Customer support is available 24 hours, 7 days a week for all Siemens customers. For technical support or general information, contact Siemens Customer Support through any of the following methods: Online Visit http://www.siemens.com/automation/support-request...
  • Page 9: Customer Support

    RUGGEDCOM RS8000   Installation Guide Preface • Contact a local Siemens representative from Sales, Technical Support, Training, etc. • Ask questions or share knowledge with fellow Siemens customers and the support community Customer Support...
  • Page 10   RUGGEDCOM RS8000 Preface Installation Guide Customer Support...
  • Page 11: Introduction

    (EMI) and heavy electrical surges typical of environments found in electric utility substations, industrial plant floors or in curb side traffic control cabinets. The RUGGEDCOM RS8000 model provides IEEE 1613 Class 2 error-free communications performance under EMI stress. An operating temperature range of -40 to 85 °C (-40 to 185 °F) allows the RUGGEDCOM RS8000 to be placed in almost any location.
  • Page 12: Description

    • Terminal blocks for reliable maintenance free connections • CSA/UL 60950 safety approved to 85 °C (185 °F) Section 1.2 Description The RUGGEDCOM RS8000 features various ports, controls and indicator LEDs on the front and rear panels for configuring and troubleshooting the device. Description...
  • Page 13 RUGGEDCOM RS8000 Chapter 1 Installation Guide Introduction Figure 1: Front and Rear Panels 1. POWER LED    2. RESET Button    3. Communication Ports    4. Port Status Indicator LEDS    5. RS232 Serial Console Port (DB9) POWER LED Illuminates when power is being supplied to the device. Color Description Green...
  • Page 14: Required Tools And Materials

    RUGGEDCOM RS8000, refer to Chapter 4, Communication Ports. Section 1.3 Required Tools and Materials The following tools and materials are required to install the RUGGEDCOM RS8000: Tools/Materials Purpose AC or DC power cord (16 AWG) For connecting power to the device. CAT-5 Ethernet cables For connecting the device to the network.
  • Page 15: Supported Fiber Optic Cables

    Siemens also does not recommend using copper Ethernet ports to interface with devices in the field across distances that could produce high levels of ground potential rise (i.e. greater than 2500 V), during line-to-ground fault conditions.
  • Page 16 Chapter 1 RUGGEDCOM RS8000 Introduction Installation Guide Supported Fiber Optic Cables...
  • Page 17: Installing The Device

    This product contains no user-serviceable parts. Attempted service by unauthorized personnel shall render all warranties null and void. Changes or modifications not expressly approved by Siemens Canada Ltd could invalidate specifications, test results, and agency approvals, and void the user's authority to operate the equipment.
  • Page 18: Mounting The Device

    Mounting the Device The RUGGEDCOM RS8000 is designed for maximum mounting and display flexibility. It can be equipped with connectors that allow it to be installed in a 48 cm (19 in) rack, 35 mm (1.4 in) DIN rail, or directly on a panel.
  • Page 19: Mounting The Device To A Rack

    RUGGEDCOM RS8000 Chapter 2 Installation Guide Installing the Device Figure 2: DIN Rail Mounting 1. Panel/DIN Rail Adaptor    2. DIN Rail    3. Screw Install one of the supplied screws on either side of the device to secure the adapters to the DIN rails. Section 2.2.2 Mounting the Device to a Rack To secure the device to a standard 48 cm (19 in) rack, do the following: Remove the four screws from the side of the device.
  • Page 20: Mounting The Device To A Panel

    Chapter 2 RUGGEDCOM RS8000 Installing the Device Installation Guide Figure 3: Rack Mounting 1. Rack Mount Adapter    2. Screw Insert the rack mount adapter and device assembly into the rack. NOTE Since heat within the device is channelled to the enclosure, it is recommended that 1 rack-unit of space, or 44 mm (1.75 in), be kept empty above the device.
  • Page 21: Connecting The Failsafe Alarm Relay

    Control of the failsafe relay output is configurable through ROS. One common application for this relay is to signal an alarm if a power failure occurs. For more information, refer to the ROS User Guide for the RUGGEDCOM RS8000. The following shows the proper relay connections.
  • Page 22: Connecting Power

    1. Normally Closed    2. Common    3. Normally Open Section 2.4 Connecting Power The RUGGEDCOM RS8000 supports a single integrated high AC/DC or low DC power supply IMPORTANT! • For 88-300 VDC rated equipment, an appropriately rated circuit breaker must be installed. • For 100-240 VAC rated equipment, an appropriately rated circuit breaker must be installed.
  • Page 23: Connecting Dc Power

    RUGGEDCOM RS8000 Chapter 2 Installation Guide Installing the Device Figure 6: Terminal Block Wiring 1. Positive/Hot (+/H) Terminal    2. Negative/Neutral (-/N) Terminal    3. Surge Ground Terminal    4. Braided Ground Cable Connect the negative wire from the power source to the negative/neutral (-/N) terminal on the terminal block.
  • Page 24 Chapter 2 RUGGEDCOM RS8000 Installing the Device Installation Guide CAUTION! Electrical hazard – risk of damage to equipment. Before testing the dielectric strength (HIPOT) in the field, remove the braided ground cable connected to the surge ground terminal and chassis ground.
  • Page 25: Device Management

    Connecting to the Device The following describes the various methods for accessing the ROS console and Web interfaces on the device. For more detailed instructions, refer to the ROS User Guide for the RUGGEDCOM RS8000. Serial Console Port Connect a PC or terminal directly to the serial console port to access the boot-time control and ROS console interface.
  • Page 26: Configuring The Device

    Section 3.3 Resetting the Device The RUGGEDCOM RS8000 can be reset (rebooted) using the RESET button. The RESET button is recessed and can only be reached using a pin or small screwdriver. To reset the device, quickly press and release the RESET button with a pin.
  • Page 27: Communication Ports

    RUGGEDCOM RS8000 Chapter 4 Installation Guide Communication Ports Communication Ports Fiber optic Ethernet ports are available with either MTRJ (Mechanical Transfer Registered Jack) or LC (Lucent Connector) connectors. Make sure the Transmit (Tx) and Receive (Rx) connections of each port are properly connected and matched to establish a proper link.
  • Page 28 Chapter 4 RUGGEDCOM RS8000 Communication Ports Installation Guide...
  • Page 29: Technical Specifications

    RUGGEDCOM RS8000 Chapter 5 Installation Guide Technical Specifications Technical Specifications This chapter provides important technical specifications related to the device. CONTENTS • Section 5.1, “Power Supply Specifications” • Section 5.2, “Failsafe Relay Specifications” • Section 5.3, “Fiber Optic Ethernet Port Specifications” • Section 5.4, “Operating Environment”...
  • Page 30: Fiber Optic Ethernet Port Specifications

    16.5 MM = Multi-Mode, SM = Single-Mode Section 5.4 Operating Environment The RUGGEDCOM RS8000 is rated to operate under the following environmental conditions. Ambient Operating Temperature -40 to 85°C (-40 to 185 °F) Ambient Storage Temperature -40 to 85°C (-40 to 185 °F)
  • Page 31: Dimension Drawings

    RUGGEDCOM RS8000 Chapter 5 Installation Guide Technical Specifications Section 5.6 Dimension Drawings NOTE All dimensions are in millimeters, unless otherwise stated. 248.9 Figure 13: Overall Dimensions Dimension Drawings...
  • Page 32 Chapter 5 RUGGEDCOM RS8000 Technical Specifications Installation Guide 479.4 464.5 Figure 14: Rack Mount Dimensions Dimension Drawings...
  • Page 33 RUGGEDCOM RS8000 Chapter 5 Installation Guide Technical Specifications 274.3 264.2 Figure 15: Panel and Din Rail Mount Dimensions Dimension Drawings...
  • Page 34 Chapter 5 RUGGEDCOM RS8000 Technical Specifications Installation Guide Dimension Drawings...
  • Page 35: Certification

    RUGGEDCOM RS8000 Chapter 6 Installation Guide Certification Certification The RUGGEDCOM RS8000 device has been thoroughly tested to guarantee its conformance with recognized standards and has received approval from recognized regulatory agencies. CONTENTS • Section 6.1, “Approvals” • Section 6.2, “EMC and Environmental Type Tests”...
  • Page 36: European Union (Eu)

    The device is marked with CE and European Explosive Atmosphere symbols and can be used throughout the European community. A copy of the CE Declaration of Conformity is available from Siemens Canada Ltd. For contact information, refer to “Contacting Siemens”.
  • Page 37: Acma

    Section 6.1.5 RoHS This device is declared by Siemens Canada Ltd to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: • China RoHS 2...
  • Page 38 Chapter 6 RUGGEDCOM RS8000 Certification Installation Guide Test Description Test Levels Severity Levels IEC 61000-4-3 Radiated RFI Enclosure ports 20 V/m IEC 61000-4-4 Burst (Fast Transient) Signal ports ±4 kV @ 2.5 kHz DC Power ports ±4 kV AC Power ports ±4 kV...
  • Page 39 RUGGEDCOM RS8000 Chapter 6 Installation Guide Certification IEEE 1613 (C37.90.x) EMC Immunity Type Tests NOTE The RUGGEDCOM RS8000 meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for copper ports. IEEE Test IEEE 1613 Clause Description Test Levels C37.90.3...
  • Page 40 Chapter 6 RUGGEDCOM RS8000 Certification Installation Guide EMC and Environmental Type Tests...