Page 2
Please read the information carefully, since it is provided for your personal safety and will also help prolong the service life of your MICROMASTER 440 Inverter and the equipment you connect to it.
Frame Size D, E Frame Size F Frame Size FX, GX Mounting dimensions Fig. 1-1 Mounting dimensions MICROMASTER 440 Operating Instructions (Compact) above and below 100 mm above and below 300 mm above and below 350 mm above 250 mm...
Page 7
= 2 % referred to the rated drive converter power and a rated line supply voltage of 240 V without line commutating reactor. UL listed fuses such as Class NON from Bussmann are required for use in America MICROMASTER 440 Operating Instructions (Compact) 2AC23-...
Page 9
= 2 % referred to the rated drive converter power and a rated line supply voltage of 400 V without line commutating reactor. UL listed fuses such as Class NON from Bussmann are required for use in America MICROMASTER 440 Operating Instructions (Compact) 2AD22-...
Page 11
≥ 2.33 % referred to the rated drive converter power and a rated line supply supply V voltage of 400 V without line commutating reactor. MICROMASTER 440 Operating Instructions (Compact) 3 AC 380 V – 480 V, ± 10 %...
Connection terminals for Frame Sizes A - F (Fig. 2-6) Connection overview for Frame Size FX (Fig. 2-7) Connection overview for Frame Size GX (Fig. 2-8) Frame Size A Fig. 2-1 Removing front covers (Frame Size A) MICROMASTER 440 Operating Instructions (Compact) 2 Electrical Installation...
Page 14
2 Electrical Installation Issue 10/06 Frame Sizes B and C " Fig. 2-2 Removing front covers (Frame Sizes B and C) MICROMASTER 440 Operating Instructions (Compact)
Page 15
Issue 10/06 2 Electrical Installation Frame Sizes D and E Fig. 2-3 Removing front covers (Frame Sizes D and E) MICROMASTER 440 Operating Instructions (Compact)
Page 16
2 Electrical Installation Issue 10/06 Frame Size F 19 mm AF Fig. 2-4 Removing front covers (Frame Size F) MICROMASTER 440 Operating Instructions (Compact)
Page 17
Issue 10/06 2 Electrical Installation Frame Sizes FX and GX Fig. 2-5 Removing front covers (Frame Sizes FX and GX) MICROMASTER 440 Operating Instructions (Compact)
Page 18
2 Electrical Installation Access to the power supply and motor terminals is possible by removing the front covers. Fig. 2-6 Connection terminals for Frame Sizes A - F Issue 10/06 MICROMASTER 440 Operating Instructions (Compact)
Page 19
Bottom retaining screw Fan screws Shield connection control leads Fan fuses Transformer adaption Motor cable Phase U2, V2, W2 Motor cable PE Shield connection Fig. 2-7 Connection overview for Frame Size FX MICROMASTER 440 Operating Instructions (Compact) 2 Electrical Installation...
Page 20
Bottom adjustment rail Bottom retaining screw Fan screws Shield connection control leads Fan fuses Transformer adaption Motor cable Phase U2, V2, W2 Motor cable PE Shield connection Fig. 2-8 Connection overview for Frame Size GX Issue 10/06 MICROMASTER 440 Operating Instructions (Compact)
Digital output 3 / Changeover contact DAC2+ Analog output 2 (+) DAC2– Analog output 2 (–) – Isolated output 0 V / max. 100 mA RS485 port N– RS485 port Fig. 2-9 Control terminals of MICROMASTER 440 MICROMASTER 440 Operating Instructions (Compact) 2 Electrical Installation...
Issue 10/06 Factory setting The MICROMASTER 440 frequency inverter is set in the factory so that it can be operated without any additional parameterization. To do this, the motor parameters set in the factory (P0304, P0305, P0307, P0310), that correspond to a 4-pole 1LA7 Siemens motor, must match the rated data of the connected motor (refer to the rating plate).
STARTER and MICROMASTER 440: PC <-> frequency inverter connecting set BOP if the USS standard values (refer to Section 6.4.1 "Serial Interface (USS)") are changed in the MICROMASTER 440 frequency inverter PC <-> frequency inverter connecting set Establishing communications MICROMASTER 440 ⇔...
Baud rate 0: 125 kbaud 1: 250 kbaud 2: 500 kbaud P2041[3] Diagnostics P2041[4] MICROMASTER 440 Operating Instructions (Compact) AOP on BOP link 2032.13 (2032.D) 2032.14 (2032.E) Output frequency of the MOP higher Output frequency of the MOP lower 2032.7...
Activate the button: see button "Start converter" Pressing the button twice (or once long) causes the motor to coast to a standstill. BOP: This function is always enabled (independent of P0700 or P0719). Issue 10/06 on BOP link on COM link MICROMASTER 440 Operating Instructions (Compact)
Press in order to obtain the required value Press to acknowledge the value and to save the value The user can only see the command parameters. MICROMASTER 440 Operating Instructions (Compact) 5 BOP / AOP (Option) Result on the display...
The quick commissioning shouldn't be carried-out if the rated motor data saved in the frequency inverter (4-pole 1LA Siemens motor, star circuit configuration specific) match the rating plate data. Parameters, designated with a * offer more setting possibilities than are actually listed here.
Page 29
(enters the command source) Factory default setting BOP (keypad) Terminal USS on BOP link USS on COM link (control terminals 29 and 30) CB on COM link (CB = communications module) MICROMASTER 440 Operating Instructions (Compact) 6 Commissioning FU-spec. P0304 P0310 FU-spec.
Page 30
F0001 (overcurrent) or F0002 (overvoltage). Terminals P0700 = 2 Sequence control BOP link COM link Setpoint channel COM link + MOP setpoint Operating Instructions (Compact) Issue 10/06 Motor control 0.00 Hz 50.00 Hz 10.00 s 10.00 s 5.00 s MICROMASTER 440...
Page 31
End of the quick commissioning/drive setting If additional functions must be implemented at the drive inverter, please use the Section "Commissioning the application" (refer to Section 6.4). We recommend this procedure for drives with a high dynamic response. MICROMASTER 440 Operating Instructions (Compact) 6 Commissioning...
The value of the magnetizing current r0331/P0320 has a significant influence on the closed-loop control. This cannot be measured at standstill. This means that the value is estimated for standard 4-pole 1LA7 Siemens standard using the automatic parameterization P0340=1 (P0320=0; result in r0331).
Page 33
The values of the motor equivalent circuit diagram data are calculated from the entered rating plate data. In addition, the parameters of the controls are pre-set (subsequently optimized) (P0340 = 3). MICROMASTER 440 Operating Instructions (Compact) entered, the better the flux setpoint (r1598=100%) matches the flux actual value (r0084=96..104%) of the observer model.
P0700 = 2 BOP link COM link Setpoint channel COM link Operating Instructions (Compact) Issue 10/06 Possible Settings: 2400 Baud 4800 Baud 9600 Baud 19200 Baud 38400 Baud 57600 Baud 76800 Baud 93750 Baud 115200 Baud Sequence control Motor control MICROMASTER 440...
DC 30 V / 5 A AC 250 V / 2 A max. opening / closing time 5 / 10 ms Issue 10/06 Closed int. 24 V max. 100 mA Kl.9 Kl.20 Kl.19 Kl.18 Kl.28 MICROMASTER 440 Operating Instructions (Compact)
1.7 V P0707 3.9 V Issue 10/06 10 V 100% P0757 P0759 20 mA 10 ms r0754 P1000 P0761 Setpoint dead r0755 Pxxxx zone r0752 P0762 P0761 F0080 r0751 r0722 r0722.6 Pxxxx Function MICROMASTER 440 Operating Instructions (Compact)
Value y2 of DAC scaling P0780 = ... This parameter represents the value for x2 in mA. Width of DAC deadband P0781 = ... Sets width of deadband in [mA] for analog output. MICROMASTER 440 Operating Instructions (Compact) 0.0 % P0780 P0781 P0778 100.0 %...
CB control word r2090 Bit13 P0719 = 61 Issue 10/06 5.00 Hz MOP down P0703 = 14 (DIN3) DOWN button USS control word r2032 Bit14 USS control word r2036 Bit14 CB control word r2090 Bit14 MICROMASTER 440 Operating Instructions (Compact)
P1019 = ... Fixed frequency code - Bit 4 P1025 = ... Fixed frequency code - Bit 5 P1027 = ... MICROMASTER 440 Operating Instructions (Compact) 0.00 Hz 5.00 Hz 10.00 Hz When defining the function of the digital inputs 15.00 Hz...
Rounding type P1134 = ... Continuous smoothing Discontinuous smoothing OFF3 ramp-down time P1135 = ... Defines ramp-down time from maximum frequency to standstill for OFF3 command. MICROMASTER 440 Operating Instructions (Compact) 0.00 Hz 0.00 Hz 0.00 Hz p1101 Skip frequency 0.00 Hz...
This setting should only be changed if it is necessary to output the torque with a different scaling. Issue 10/06 0.00 Hz 50.00 Hz 50.00 Hz 100 % p2000) refer to this value. 1000 V 0.10 A 0.12 Mn MICROMASTER 440 Operating Instructions (Compact)
If the frequency inverter is permanently supplied with an external 24V voltage, then the motor temperature is also tracked/corrected using the motor temperature time constant – even when the line supply voltage is switched-out. MICROMASTER 440 Operating Instructions (Compact) Inverter overload reaction...
Page 46
A high thermal motor load and when the line supply is frequently switched- out/switched-in requires, for closed-loop vector control − that a KTY84 sensor is used, or − an external 24V power supply voltage is connected Motor cooling (Selects motor cooling system used) P0335 = ...
(loss of the encoder signal at high frequency remains active as long as parameter p0492 > 0). MICROMASTER 440 Operating Instructions (Compact) The table shows the values of P0400 as a function of the...
V ist Boost AccBoost,100 AccBoost,50 Boost,end (P1316) Linear V/f Boost voltage ⏐f⏐ Boost P1310 active f max (P0310) (P1082) Boost-Spannung P1311 aktiv fmax (P0310) (P1082) Issue 10/06 50.00 % Validity range 0.0 % Gültigkeitsbereich ⏐f⏐ MICROMASTER 440 Operating Instructions (Compact)
Page 49
Dynamically adjusts output frequency of inverter so that motor speed is kept constant independent of motor load. P1338 =... Resonance damping gain V/f Defines resonance damping gain for V/f. MICROMASTER 440 Operating Instructions (Compact) 0.0 Hz = f(V r0071 P0304 0.0 Hz...
Value is entered in [%] relative to rated motor torque r0333. p1611 is only effective in the open-loop mode between 0 Hz and approx. ± p1755. In opposite to p1610 the acceleration torque boost p1611 is only in operation during acceleration/deceleration. MICROMASTER 440 Operating Instructions (Compact) 150 ms Droop...
Page 52
Act. frequency Slip Observer model closed loop Issue 10/06 1 YES 1 YES Zero crossing Closed loop Open loop p1755 5.0 Hz Act. output voltage Current controller Current measurement Act. angle Act. output frequency MICROMASTER 440 Operating Instructions (Compact)
Enters integral time of speed controller. r1490 p1492 r1084 r1170 – Freq. setpoint r0063 Act. frequency from encoder MICROMASTER 440 Operating Instructions (Compact) 150 ms Droop r1518 Precontrol r1438 – r0064 *) only active, if pre-control is enabled (p1496 > 0)
Page 54
SLVC: P1452 P1442 Operating Instructions (Compact) Issue 10/06 Fixed setpoint 1 as a % Fixed setpoint 2 as a % Analog input 1 Analog input 2 r1518 r1538 Torque setpoint r1539 r1508 r0079 r1515 P1470 P1472 P1460 P1462 MICROMASTER 440...
Trip reset after power on Restart after mains blackout Restart after mains brownout or fault Restart after mains brownout Restart after mains blackout and fault Restart after mains brown/blackout or fault MICROMASTER 440 Operating Instructions (Compact) 6 Commissioning 100 % 100 %...
Page 57
Holding time after ramp-down (entered in s) P1217 = ... Defines time for which inverter runs at minimum frequency (p1080) after ramping down. P1217 ≥ brake closing time + relay closing time MICROMASTER 440 Operating Instructions (Compact) 52.3 Frequent settings: 52.0 Ready to power-up...
Defines duration for which DC injection braking is to be active following an OFF1 or OFF3 command. OFF1/OFF3 OFF2 ⏐f⏐ P1234 DC braking active r0053 Bit00 DC braking P0347 P0347 OFF2 DC braking P1233 Issue 10/06 f_set f_act 100 % MICROMASTER 440 Operating Instructions (Compact)
Time delay for belt failure P2192 = ... P2192 defines a delay before warning/trip becomes active. It is used to eliminate events caused by transient conditions. It is used for both methods of fault detection. MICROMASTER 440 Operating Instructions (Compact) 6 Commissioning 5.00 30.00...
Page 62
Lower torque threshold 1 |Torque| [Nm] P1080 Min. frequency P2183 P2182 Threshold frequency 2 Threshold frequency 1 Boundary zones De-activated monitoring Issue 10/06 P1082 Max. frequency |Frequency| [Hz] P2184 Threshold frequency 3 Envelope curve Active monitoring MICROMASTER 440 Operating Instructions (Compact)
PID output upper limit P2291 =... Sets upper limit for PID controller output in [%]. PID output lower limit P2292 =... Sets lower limit for the PID controller output in [%]. MICROMASTER 440 Operating Instructions (Compact) 6 Commissioning 1.00 s 1.00 s 755.0 100.00 %...
Page 64
OFF1/3: active active OFF1/3: active Motor control Output & P2251 PID controller active Adapt to the application Adapt to the application Determined by optimizing Determined by optimizing Adapt to the application Adapt to the application MICROMASTER 440 Operating Instructions (Compact)
Adapt CDS2 parameters (P0700[1] = 1 and P1000[1] = 1) P0810 = 722.3 DIN4 P0700[0] = 2 Terminals P0700[1] = 1 P1000[0] = 2 P1000[1] = 1 MICROMASTER 440 Operating Instructions (Compact) Changeover time Changeover time approx. 4 ms approx. 4 ms Sequence control Setpoint...
Page 70
Selects command source from which Bit 1 for selecting a drive data set is to be read in (see parameter P0820). Changeover time Changeover time approx. 50 ms approx. 50 ms Operating Instructions (Compact) Issue 10/06 CO/BO: Act CtrlWd2 r0055 r0055 CO/BO: Act CtrlWd2 r0055 r0055 CO: Active DDS r0051 [2] MICROMASTER 440...
Page 71
− Connect P0820 (P0821 if required) to the DDS changeover source (e.g. via DIN 4: P0704[0] = 99, P0820 = 722.3). − Changeover to DDS2 (check using r0051). − Commission motor 2; adapt the remaining DDS2 parameters. MICROMASTER 440 Operating Instructions (Compact) Sequence control Motor...
ω , M ⋅ ⋅ r0032 [kW] π 1000 r0032 [hp] 0.75 ⋅ r0032 [kW] t model. ⋅ ⋅ ⋅ ⋅ ϕ Issue 10/06 r0022 ⋅ ⋅ [1/min] r0031 [Nm] t value provides the level of MICROMASTER 440 Operating Instructions (Compact)
Page 73
Displays valid maximum output current of inverter. P0640 Motor Motor protection r0209 Inverter Inverter protection r0072 CO: Act. output voltage Displays output voltage. MICROMASTER 440 Operating Instructions (Compact) 160 ms P1300 <20 20,22 21,23 P0400 P1300 = 21,23 and P0400 = 0 --> F0090 P0305...
Page 74
Displays the total frequency setpoint (reference value) in Hz after the ramp-function generator. P1110 P1091 P1080 P1082 P1120 P1135 Inhibit Skip neg. freq. frequency setpoint r1114 Operating Instructions (Compact) Issue 10/06 . . . Motor control r0020 r1170 r1119 MICROMASTER 440...
Issue 10/06 Series commissioning An existing parameter set can be transferred to a MICROMASTER 440 frequency inverter using STARTER or DriveMonitor (refer to Section 4.1 "Establishing communications MICROMASTER 440 ⇔ STARTER"). Typical applications for series commissioning include: 1. If several drives are to be commissioned that have the same configuration and same functions.
LEDs twinkling same time Other warnings both LEDs twinkling alternatively Undervoltage trip / undervoltage warning Drive is not in ready state ROM failure both LEDs flashing same time RAM failure both LEDs flashing alternatively MICROMASTER 440 Operating Instructions (Compact) Issue 10/06...
Stack Overflow F0221 PID Feedback below min. value F0222 PID Feedback above max. value BIST Tests Failure F0450 (Service mode only) F0452 Belt Failure Detected MICROMASTER 440 Operating Instructions (Compact) Alarm Significance A0501 Current Limit A0502 Overvoltage limit A0503 Undervoltage Limit...
Page 78
Information about MICROMASTER 440 is also available from: Regional Contacts Please get in touch with your contact for Technical Support in your Region for questions about services, prices and conditions of Technical Support. Central Technical Support The competent consulting service for technical issues with a broad range of requirements-based services around our products and systems.