MICROMASTER 440 Documentation Getting Started Guide Is for quick commissioning with SDP and BOP. Operating Instructions Gives information about features of the MICROMASTER 440, Installation, Commissioning, Control modes, System Parameter structure, Troubleshooting, Specifications and available options of the MICROMASTER 440. Parameter List...
Page 3
Overview Installation Commissioning MICROMASTER 440 Using the MICROMASTER 440 System Parameters Operating Instructions Troubleshooting User Documentation MICROMASTER 440 Specifications Available options Electro-Magnetic Compatibility Appendices Valid for Issue 10/01 Converter Type Control Version MICROMASTER 440 Index Issue B1...
Page 4
Further information can be obtained from Internet website: http://www.siemens.de/micromaster Approved Siemens Quality for Software and Training Other functions not described in this document may be is to DIN ISO 9001, Reg. No. 2160-01 available. However, this fact shall not constitute an...
Customers can access technical and general information at: http://www.siemens.de/micromaster Contact address Should any questions or problems arise while reading this manual, please contact the Siemens office concerned using the form provided at the back this manual. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Earth voltage. This connection is normally used to ground the motor. Use for intended purpose only The equipment may be used only for the application stated in the manual and only in conjunction with devices and components recommended and authorized by Siemens. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Please read the information carefully, since it is provided for your personal safety and will also help prolong the service life of your MICROMASTER 440 Inverter and the equipment you connect to it. General WARNING ♦...
Page 8
The connection of power, motor and control cables to the inverter must be carried out as shown in Figure 2-7 on page 31, to prevent inductive and capacitive interference from affecting the correct functioning of the inverter. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 9
EN 60204, 9.2.5.4) Repair WARNING ♦ Repairs on equipment may only be carried out by Siemens Service, by repair centers authorized by Siemens or by qualified personnel who are thoroughly acquainted with all the warnings and operating procedures contained in this manual.
Issue B1 Table of Contents Table of Contents Overview ........................ 15 The MICROMASTER 440 ..................16 Features ........................16 Installation ......................19 General........................21 Ambient operating conditions.................. 21 Mechanical installation .................... 23 Electrical installation....................26 Commissioning ..................... 33 Block diagram......................35 Commission modes....................
Page 12
Removing ‘Y’ Cap Link Frame Sizes B and C........... 108 Removing ‘Y’ Cap Link Frame Sizes D and E........... 109 Removing ‘Y’ Cap Link Frame Sizes F .............. 110 Applicable Standards..................111 List of Abbreviations................... 112 Index ..........................113 MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 13
Motor and Power Connections....................29 Figure 2-7 Wiring Guidelines to Minimize the Effects of EMI ..............31 Figure 3-1 Inverter block diagram ......................35 Figure 3-2 Panels available for the MICROMASTER 440 Inverter............36 Figure 3-3 DIP switch..........................36 Figure 3-4 Basic operation with SDP .....................38 Figure 3-5 Buttons on the BOP ......................41...
Issue B1 1 Overview Overview This Chapter contains: A summary of the major features of the MICROMASTER 440 range. The MICROMASTER 440 ..................16 Features ........................16 MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Comprehensive protective functions provide excellent inverter and motor protection. The MICROMASTER 440 with its default factory settings is ideal for a large range of simple motor control applications. The MICROMASTER 440 can also be used for more advanced motor control applications via its comprehensive functionality.
Page 17
Ø parameter sets which can be switched, allowing one inverter to control several alternative processes Protection characteristics Ø Overvoltage/undervoltage protection Ø Overtemperature protection for the inverter Ø Ground fault protection Ø Short-circuit protection Ø i t thermal motor protection Ø PTC/KTY for motor protection MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Ø General data relating to installation Ø Dimensions of Inverter Ø Wiring guidelines to minimize the effects of EMI Ø Details concerning electrical installation General........................21 Ambient operating conditions.................. 21 Mechanical installation .................... 23 Electrical installation....................26 MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 20
The connection of power, motor and control cables to the inverter must be carried out as shown in Figure 2-7 on page 31, to prevent inductive and capacitive interference from affecting the correct functioning of the inverter. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Storage period 3 and more years Prior to energizing, form according to the curve Time t [h] Figure 2-1 Forming Ambient operating conditions Temperature Permissible output current Constant Torque Variable Torque [°C] Operating temperature Figure 2-2 Ambient operating temperature MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
The inverters can be mounted without any clearance at either side. Allow 100 mm clearance above and below the inverter. Make sure that the cooling vents in the inverter are positioned correctly to allow free movement of air. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
The inverters can be mounted adjacent to each other. If they are mounted on top of each other, however, a clearance of 100 mm has to be observed. Table 2-1 Dimensions and Torques of MICROMASTER 440 Tightening Frame-Size Overall Dimensions...
Ø 15 mm 0.68" 0.68" 0.59" 486 mm 19.13" 616.4 mm 24.27" 810 mm 31.89" with filter 1110 mm 43.70" 235 mm 9.25" 235 mm 9.25" 300 mm 11.81" Figure 2-4 Drill pattern for MICROMASTER 440 MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 25
1. To disengaged the release mechanism of the inverter, insert a screwdriver into the release mechanism. 2. Apply a downward pressure and the lower rail latch will disengage. 3. Pull the inverter from the rail. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
þ The output cables are less than 50m (screened) or 100m (unscreened). Operation with long cables All inverters will operate at full specification with cable lengths up to 50 m screened or 100 m unscreened. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 27
Access to the power and motor terminals You can gain access to the mains and motor terminals by removing the covers (see also Appendices 0 to E. The mains and motor connections must be made as shown in Figure 2-6. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
2 Installation CABLE SCREENING OPTIONAL FILTER (Class B only) CONTACTOR MICROMASTER MOTOR FUSE L/L1 N/L2 SINGLE PHASE TYPICAL INSTALLATION CABLE SCREENING OPTIONAL FILTER CONTACTOR MICROMASTER MOTOR FUSE THREE PHASE Figure 2-6 Motor and Power Connections MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 30
Ø Use screened or armored cables for the motor connections and ground the screen at both ends using the cable clamps WARNING Safety regulations must not be compromised when installing inverters! MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Screening cables Figure 2-7 Wiring Guidelines to Minimize the Effects of EMI NOTES To enhance the screening of the motor and control cables, the optional Gland Plate can be used (not shown in Figure 2-7). MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
This Chapter contains: Ø A schematic diagram of the MICROMASTER 440 Ø An overview of the commissioning options and the display and operator panels Ø An overview of quick commissioing of the MICROMASTER 440 Block diagram......................35 Commission modes....................36 General operation....................
Page 34
This equipment must not be used as an ‘emergency stop mechanism’ (see EN 60204, 9.2.5.4) CAUTION Only qualified personnel may enter settings in the control panels. Particular attention must be paid to safety precautions and warnings at all times. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Terminal 9 (24 V) can also be used to drive the analog inputs when used as digital inputs. Terminals RS485 2 and 28 (0 V) must be linked together. U,V,W Figure 3-1 Inverter block diagram MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Issue A2 Commission modes In the standard version, the MICROMASTER 440 is fitted with the Status Display Panel (SDP) (see Figure 3-2) with which it is possible to use the inverter with the pre-assigned factory settings for a large range of applications. If these factory...
Ø Motor voltage Ø Rated motor current Ø Rated motor frequency (A conventional Siemens motor is recommended) In addition, the following conditions must be met: Ø Linear V/f motor speed controlled by an analog potentiometer. Ø Maximum speed 3000 rpm at 50 Hz (3600 rpm at 60 Hz); can be controlled by a potentiometer via the analog inputs of the inverter.
OFF = Voltage 0 - 10 V = 0 - 20 mA AIN1 OFF = Voltage 0 - 10 V = 0 - 20 mA Analogue Output 0 - 20 mA Ω (500 Figure 3-4 Basic operation with SDP MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 39
Further Commissioning via P0004 and P0003 An overview of the parameter structure is given in Section 5.3 For a detailed description of the parameter, see the Parameter List. NOTES We recommend the commissioning according this scheme. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Dimension (kW (Hp)) depending on setting of P0100. [Value depending on variant.] P0310 Motor frequency rating 50 Hz (60 Hz) P0311 Motor speed rating 1395 (1680) rpm [depending on variant] P1082 Maximum Motor Frequency 50 Hz (60 Hz) MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Access Pressing this button allows access to the parameters. parameters Increase Pressing this button increases the displayed value. value Decrease Pressing this button decreases the displayed value. value Figure 3-5 Buttons on the BOP MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Press to confirm and store the value Press until r0000 is displayed Press to return the display to the standard drive display (as defined by the customer) Figure 3-6 Changing parameters via the BOP MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 43
Ø Upload/download of multiple parameter sets Ø Programmable via PC Ø Multidrop capability to drive up to 30 inverters Please refer to the AOP Manual for details or contact your local Siemens sales office for assistance. 3.2.3 Commissioning functions with BOP / AOP 3.2.3.1...
Page 44
End Quick Commissioning with motor calculation but without I/O reset. 1) Motor-specific parameters – see motor rating plate. 2) The parameters offer more setting options than listed here. See Parameter List for further setting options. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
To reset all parameters to the factory default settings; the following parameters should be set as follows (BOP, AOP or Communication Option needed): 1. Set P0010=30. 2. Set P0970=1. NOTE The reset process can take up to 3 minutes to complete. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
1.0 seconds while the inverter is stopped. 3. The inverter is programmed at the factory for standard applications on Siemens four-pole standard motors that have the same power rating as the inverters. When using other motors it is necessary to enter the specifications from the motor's rating plate.
P0601 must also be set to 1. Figure 3-8 Motor Overload PTC Connection NOTE To enable the trip function, set parameter P0701, P0702 or P0703 = 29. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Issue B1 4 Using the MICROMASTER 440 Using the MICROMASTER 440 This Chapter contains: Ø An explanation of the various methods of controlling the inverter Ø A summary of the types of control of the inverter Frequency setpoint (P1000)..................50 Command sources (P0700) ..................
4 Using the MICROMASTER 440 Issue A2 WARNING ♦ When operating electrical devices, it is impossible to avoid applying hazardous voltages to certain parts of the equipment. ♦ Emergency Stop facilities according to EN 60204 IEC 204 (VDE 0113) must remain operative in all operating modes of the control equipment.
Issue B1 4 Using the MICROMASTER 440 Command sources (P0700) NOTICE The ramp times and ramp-smoothing functions also affect how the motor starts and stops. For details of these functions, please refer to parameters P1120, P1121, P1130 – P1134 in the Parameter List.
4 Using the MICROMASTER 440 Issue A2 4.3.2 OFF2 This command causes the motor to coast to a standstill (pulses disabled). NOTICE The OFF2 command can have one or more sources. By default the OFF2 command is set to BOP/AOP. This source still exists even if other sources are defined by one of the following parameters, P0700 to P0708 inclusive.
4 Using the MICROMASTER 440 Control modes (P1300) The various modes of operation of the MICROMASTER 440 control the relation- ship between the speed of the motor and the voltage supplied by the inverter. A summary of the control modes available are listed below: Ø...
4 Using the MICROMASTER 440 Issue A2 Faults and warnings If an SDP is fitted, the fault states and warnings are indicated by the two LEDs on the panel, see section 6.1 on page 72 for further information. Fault-free operation of the inverter is indicated by the following sequence of LED displays: Ø...
Issue B1 5 System parameters System parameters This Chapter contains: Ø An overview of the parameter structure of the MICROMASTER 440 Ø A parameter list in short form Introduction to MICROMASTER system parameters..........56 Parameter overview ....................57 Parameter list (short form) ..................58...
Standard (P0003 = 1) or Extended parameters (P0003 = 2) are sufficient. The number of parameters that appear within each functional group depends on the access level set in parameter P0003. For further details regarding parameters, see the Parameter List on the Documentation CD-ROM. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Act. power stack code number P0201 Power stack code number r0203 Act. inverter type r0204 Power stack features P0205 Inverter application r0206 Rated inverter power [kW] / [hp] r0207 Rated inverter current r0208 Rated inverter voltage MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 59
P0347[3] Demagnetization time 1.000 P0350[3] Stator resistance (line-to-line) P0352[3] Cable resistance r0384[3] Rotor time constant r0395 CO: Total stator resistance [%] r0396 CO: Act. rotor resistance P0601[3] Motor temperature sensor P0604[3] Threshold motor temperature 130.0 MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 60
BI: Function of digital output 2 52:7 P0733[3] BI: Function of digital output 3 r0747 CO/BO: State of digital outputs P0748 Invert digital outputs P0800[3] BI: Download parameter set 0 P0801[3] BI: Download parameter set 1 MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 62
50.00 P1012[3] Fixed frequency 12 55.00 P1013[3] Fixed frequency 13 60.00 P1014[3] Fixed frequency 14 65.00 P1015[3] Fixed frequency 15 65.00 P1016 Fixed frequency mode - Bit 0 P1017 Fixed frequency mode - Bit 1 MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 63
Ramp-up initial rounding time 0.00 P1131[3] Ramp-up final rounding time 0.00 P1132[3] Ramp-down initial rounding time 0.00 P1133[3] Ramp-down final rounding time 0.00 P1134[3] Rounding type P1135[3] OFF3 ramp-down time 5.00 r1170 CO: Frequency setpoint after RFG MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 64
CO: Act. output voltage r0027 CO: Act. output current r0029 CO: Flux gen. current r0030 CO: Torque gen. current r0031 CO: Act. torque r0032 CO: Act. power r0038 CO: Act. power factor r0056 CO/BO: Status of motor control MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 65
CO: Imax controller volt. output P1345[3] Imax controller prop. gain 0.250 P1346[3] Imax controller integral time 0.300 P1350[3] Voltage soft start P1400[3] Configuration of speed control r1407 CO/BO: Status 2 of motor control r1438 CO: Freq. setpoint to controller MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 66
Control word of motor model r1751 Status word of motor model r1770 CO: Prop. output of n-adaption r1771 CO: Int. output of n-adaption P1780[3] Control word of Rs/Rr-adaption r1782 Output of Rs-adaptation r1787 Output of Xm-adaption MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 67
CB telegram off time P2041[5] CB parameter r2050[8] CO: PZD from CB P2051[8] CI: PZD to CB 52:0 r2053[5] CB identification r2054[7] CB diagnosis r2090 BO: Control word 1 from CB r2091 BO: Control word 2 from CB MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 68
2000 P2181[3] Belt failure detection mode P2182[3] Belt threshold frequency 1 5.00 P2183[3] Belt threshold frequency 2 30.00 P2184[3] Belt threshold frequency 3 50.00 P2185[3] Upper torque threshold 1 99999.0 P2186[3] Lower torque threshold 1 MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 69
CI: PID trim source P2255 PID setpoint gain factor 100.00 P2256 PID trim gain factor 100.00 P2257 Ramp-up time for PID setpoint 1.00 P2258 Ramp-down time for PID setpoint 1.00 r2260 CO: Act. PID setpoint MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Issue B1 7 MICROMASTER 440 specifications Troubleshooting This Chapter contains: Ø An overview of the operating statuses of the inverter with the SDP Ø Notes on troubleshooting with the BOP Ø A list of the alarms and fault messages Troubleshooting with the SDP................. 72 Troubleshooting with the BOP ................
Issue A2 WARNING ♦ Repairs on equipment may only be carried out by Siemens Service, by repair centers authorized by Siemens or by qualified personnel who are thoroughly acquainted with all the warnings and operating procedures contained in this manual.
Issue B1 7 MICROMASTER 440 specifications Troubleshooting with the BOP Warnings and faults are displayed on the BOP with Axxx and Fxxx respectively. The individual messages are shown in Section 6.3. If the motor fails to start when the ON command has been given: Ø...
7 MICROMASTER 440 specifications Issue A2 Fault messages In the event of a failure, the inverter switches off and a fault code appears on the display. NOTE To reset the fault code, one of three methods listed below can be used: 1.
Page 75
Issue B1 7 MICROMASTER 440 specifications Fault Possible Causes Diagnose & Remedy Reac- tion Wire breakage of inverter OFF1 F0012 temperature (heatsink) sensor Inverter temp. signal lost Open or short circuit of motor OFF2 F0015 temperature sensor. If signal loss is...
Page 76
7 MICROMASTER 440 specifications Issue A2 Fault Possible Causes Diagnose & Remedy Reac- tion Ø Motor data identification failed. Check that the motor is connected to the OFF2 F0041 Ø Alarm value =0: Load missing inverter. Motor Data Ø Alarm value =1: Current limit level...
Page 77
Issue B1 7 MICROMASTER 440 specifications Fault Possible Causes Diagnose & Remedy Reac- tion Ø Broken wire Check connection to analogue input OFF2 F0080 Ø Signal out of limits ADC lost input signal External fault triggered Disable input for fault trigger...
7 MICROMASTER 440 specifications Issue A2 Alarm messages Fault Possible Causes Diagnose & Remedy Reac- tion Ø Motor power does not correspond Check the following: A0501 to the inverter power 1. Motor power (P0307) must correspond to Current Limit Ø Motor leads are too short inverter power (P0206).
Page 79
Issue B1 7 MICROMASTER 440 specifications Fault Possible Causes Diagnose & Remedy Reac- tion CB (communication board) specific See CB user manual A0702 CB warning 3 CB (communication board) specific See CB user manual A0703 CB warning 4 CB (communication board) specific...
Page 80
7 MICROMASTER 440 specifications Issue A2 Fault Possible Causes Diagnose & Remedy Reac- tion DAC parameters should not be set to Analogue Output parameters should not be set to A0921 identical values, since this would the same value as each other produce illogical results.
Issue B1 7 MICROMASTER 440 specifications MICROMASTER 440 specifications This Chapter contains: Ø Table 7.1 contains the general technical specifications for the MICROMASTER 440 inverter Ø Table 7-2 contains terminal tightening torques Ø Table 7-3 includes various tables of specific technical data for individual...
Issue B1 7 MICROMASTER 440 specifications Table 7-2 Tightening torques for power terminals Frame Size [Nm] 2.25 10 (max) 10 (max) Tightening Torque [lbf.in] 13.3 87 (max) 87 (max) Table 7-3 MICROMASTER 440 Specifications In order to have a UL compliant installation fuses from the SITOR range with the appropriate current rating must be used.
Page 84
7 MICROMASTER 440 specifications Issue A2 Input voltage range 3 AC 200 V – 240 V, ± 10 % (with built in Class A Filter) Order No. 6SE6440- 2AC23- 2AC24- 2AC25- 0CA0 0CA0 5CA0 [kW] Motor Output Rating [hp] Output Power [kVA] 13.6...
Page 85
Issue B1 7 MICROMASTER 440 specifications Input voltage range 1 AC 3 AC 200 V – 240 V, ± 10 % (Unfiltered) Order No. 6SE6440- 2UC11 2UC12 2UC13 2UC15 2UC17 2UC21 2UC21 2UC22 2UC23 -2AA0 -5AA0 -7AA0 -5AA0 -5AA0 -1BA0...
Page 86
7 MICROMASTER 440 specifications Issue A2 Input voltage range 3 AC 200 V – 240 V, ± 10 % (Unfiltered) Order No. 6SE6440- 2UC24- 2UC25- 2UC27- 2UC31- 2UC31- 2UC31- 2UC32- 2UC33- 2UC33- 2UC34- 0CA0 5CA0 5DA0 1DA0 5DA0 8EA0 2EA0...
Page 87
Issue B1 7 MICROMASTER 440 specifications Input voltage range 3 AC 380 V – 480 V, ± 10 % (with built in Class A Filter), Part 1 Order No. 6SE6440- 2AD22- 2AD23- 2AD24- 2AD25- 2AD27- 2AD31- 2AD31- 2AD31- 2BA0 0BA0...
Page 88
7 MICROMASTER 440 specifications Issue A2 Input voltage range 3 AC 380 V – 480 V, ± 10 % (with built in Class A Filter), Part 2 Order No. 6SE6440- 2AD32- 2AD33- 2AD33- 2AD34- 2AD35- 2AD37- 2DA0 0EA0 7EA0 5FA0...
Page 89
Issue B1 7 MICROMASTER 440 specifications Input voltage range 3 AC 380 V – 480 V, ± 10 % (Unfiltered), Part 1 Order No. 6SE6440- 2UD13- 2UD15- 2UD17- 2UD21- 2UD21- 2UD22- 2UD23- 2UD24- 2UD25- 2UD27- 7AA0 5AA0 5AA0 1AA0 5AA0...
Page 90
7 MICROMASTER 440 specifications Issue A2 Input voltage range 3 AC 380 V – 480 V, ± 10 % (Unfiltered), Part 2 Order No. 6SE6440- 2UD31- 2UD31- 2UD31- 2UD32- 2UD33- 2UD33- 2UD34- 2UD35- 2UD37- 1CA0 5DA0 8DA0 2DA0 0EA0 7EA0...
Page 91
Issue B1 7 MICROMASTER 440 specifications Input voltage range 3 AC 500 V – 600 V, ± 10 % (Unfiltered), Part 1 Order No. 6SE6440 2UE17- 2UE21- 2UE22- 2UE24- 2UE25- 2UE27- 2UE31- 2UE31- 2UE31- 5CA0 5CA0 2CA0 0CA0 5CA0 5CA0...
Page 92
7 MICROMASTER 440 specifications Issue A2 Input voltage range 3 AC 500 V – 600 V, ± 10 % (Unfiltered), Part 2 Order No. 6SE6440- 2UE32- 2UE33- 2UE33- 2UE34- 2UE35- 2UE37- 2DA0 0EA0 7EA0 5FA0 5FA0 5FA0 22.0 30.0 37.0 45.0...
Ø “DriveMonitor” and "Starter" commissioning tool Device-dependent options Ø EMC filter, Class A Ø EMC filter, Class B Ø Additional EMC filter, Class B Ø Low leakage Class B filter Ø Line commutating choke Ø Output choke Ø Gland plate MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
EC type examination certificate This approach is only applicable to radio communication transmitting apparatus. All MICROMASTER units are certified for compliance with the EMC directive, when installed in accordance with the recommendations in Section 2. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
EN 61000-3-2 "Limits for harmonic current emissions (equipment input ≤ 16 A per phase)". All Siemens variable speed drives of the MICROMASTER, MIDIMASTER, MICROMASTER Eco and COMBIMASTER ranges, which are classified as "Professional Equipment" within the terms of the standard, fulfill the requirements of the standard.
Ø The MICROMASTER inverters are intended exclusively for professional applications. Therefore, they do not fall within the scope of the harmonics emissions specification EN 61000-3-2. Ø Maximum mains supply voltage when filters are fitted is 460 V. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Frame size A units 400-480 V with external Class A footprint filters 6SE6440-2FA00-6AD0 Class 3 – Filtered for residential, commercial and light industry 6SE6440-2U***-**A0 with Unfiltered units fitted with external Class B footprint filters. 6SE6400-2FB0*-***0 * denotes any value is allowed. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Removing the I/O Board NOTICE 1. Only a small amount of pressure is required to release the I/O Board catch. 2. Currently, the I/O Board is removed using the same technique regardless of frame size. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Issue A2 Removing ‘Y’ Cap Frame Sizes D and E Removing ‘Y’ Cap Frame Sizes D and E Torque Driver Screw 13 mm AF MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
EMC Product Standard for Power Drive Systems EN61800-3. Underwriters Laboratories UL and CUL LISTED POWER CONVERSION EQUIPMENT 5B33 for use in a pollution degree 2 ISO 9001 Siemens plc operates a quality management system, which complies with the requirements of ISO 9001. MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 114
Removing ‘Y’ Cap Frame Sizes B and C · Main characteristics · 16 Removing ‘Y’ Cap Frame Sizes D and E · Mechanical Installation · 23 MICROMASTER 440 Removing ‘Y’ Cap Frame Sizes F · 110 general · 16 Removing Covers Frame Size F · 105 main characteristics ·...
Page 116
Index Issue A2 MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...
Page 117
Suggestions and/or Corrections Suggestions Siemens AG Automation & Drives Group Corrections SD VM 4 For Publication/Manual: P.O. Box 3269 MICROMASTER 440 D-91050 Erlangen Federal Republic of Germany Email: Technical.documentation@con.siemens.co.uk User Documentation Operating Instructions From Order Number: Name: 6SE6400-5AC00-0BP0 Date of Issue: 10/01...
Page 119
View of Unit Frame Size A Frame Size B & C fitted Analog Analog Setting Setting DIP Switch DIP Switch I/O Board Frequency Frequency Setting Setting DIP Switch DIP Switch Control Board Power Terminal Connections MICROMASTER 440 Operating Instructions 6SE6400-5AC00-0BP0...