1 | Overview
This keypad is an SDI2 bus compatible
1
3
6
2
1
10
4
5
7
7
R Y G B
6
1
2
3
6
5
Callout ― Description
1 ― Wall mount holes
2 ― Single gang box holes
3 ― Double gang box holes
4 ― Wire opening
5 ― Surface mount wire openings
6 ― Gang box holes (3-4 in)
7 ― Surface mount wire channel
8 ― Bubble level
9 ― SDI2 wiring terminal block
10 ― Wire tie posts
2 | SDI2 address switches
Two switches set the address for the keypad. The control panel
uses the address for communication.
2.1 | Access the address switches
1.
Use a slotted screwdriver. Turn the lock counter-
clockwise.
2.
Push down on the keypad to remove it from the base.
3.
Find the switches on the back of the keypad.
Refer to the following illustrations.
10
5
9
10
8
1
1
Callout ― Description
1 ― Address switches
2.2 | Setting the address switches
Set the address switches per the control panel configuration.
Each SDI2 keypad must have a unique address. For single-
digit addresses 1 through 9, set the tens switch to 0. The
following illustration shows the address switch setting for
address 1.
3 | Installation
Caution!
Remove all power (AC and battery) before making any
connections. Failure to do so might result in personal
injury and/or equipment damage.
3.1 | Install the keypad
You can surface install the keypad, or install it to standard
electrical boxes, including single gang boxes.
1.
Use the base as a template to mark surface.
2.
Pull the wiring through the opening in the base.
3.
Use the mounting hardware to attach.
3.2 | Attaching to the control panel
Use the control panel terminals labeled R, Y, G, B (PWR, A, B,
COM). Connect them to the keypad terminals labeled R, Y, G, B.
Keypads can be wired directly to the control panel or from
keypad to keypad.
PWR+/R
PWR+/R
30
29
29
28
A/Y
A/Y
2
B/G
B/G
28
27
27
26
COM/B
COM/B
e
e
Callout ― Description
1 ― Control panel
2 ― Terminal wiring
3 ― Keypad's wiring terminal block
PWR+/R
PWR+/R
30
29
29
28
A/Y
A/Y
27
28
B/G
B/G
COM/B
COM/B
27
26
e
e
Reconnect the keypad to the base by sliding the keypad onto
the base (reverse of Step 2). Apply power to the system.
4 | Display
Adjusting the brightness:
1.
Press [MENU] or press [CMD][8] to open the Main menu.
2.
Use [NEXT] to go to the Press 5 for Settings Menu option,
or simply press [5].
3.
Use [NEXT] to go to the Press 4 for Keypad Config option,
or simply press [4].
4.
Press [1] to adjust the brightness.
1
5.
Use [PREV] or [NEXT] to adjust the brightness level. The
2
changes apply immediately.
6.
Press [ESC] to exit the menu.
R
Adjusting nightlight (for control panels with version 2.01 or
Y
higher):
3
G
1.
Press [MENU] or press [CMD][8] to open the Main menu.
2.
Use [NEXT] to go to the Press 5 for Settings Menu option,
B
or simply press [5].
3.
Use [NEXT] to go to the Press 4 for Keypad Config option,
or simply press [4].
4.
Use [NEXT] to go to the Press 4 for Nightlight option, or
simply press [4].
5.
Use [PREV] or [NEXT] to toggle between the Yes and No
options.
6.
Press [ENTER] while viewing the desired option to save the
programming.
7.
Press [ESC] to exit the menu.
5 | Status indicators
Status
indicator
GAS
Fire keypad
indicator
R
Y
G
B
Function
Ready to turn on (arm)
Turned on (armed)
Gas alarm
AC (Mains) power present
Function
Fire alarm
Silenced
Supervisory condition
System trouble