Advertisement

E3M080 Line module "Collective"

9
E3M080 Line module "Collective"
9.1
Overview
9.2
Key data
32
Siemens Building Technologies
Fire & Security Products
Line module for collective detectors (digital comparator)
I-Bus module with common line processor for all 8 lines
2 line types available (programmable via SWE700A)
Line termination depending on programmable line type
Short circuit can be evaluated as fault or alarm per module (Programming switch
'S4')
Line inputs protected against over voltage
Card format 100mm x 200mm
I-Bus address is set at programming switch 'S3'
Terminal block X20 (20 terminals)
- mounted on module chassis
- for the connection of the prefabricated cable to
connection level, or
- for direct connection of the periphery
Card chassis
- mounted on module chassis
Line type
Connectable detector series
Number of detectors per line
Number of wires
Twisted cable
Line resistance
Line capacitance
Line termination element
Line voltage
Alarm current limit
Line voltage limit
Quiescent line current
Reset time
Turn-on alarm delay
Fault delay
Module quiescent current at 24V
Type 1
Type 11
See chapter 0 'Compatibility'
max. 25
2
recommended
max. 250Ω
max. 150Ω
max. 4µF
EOL22 (Ex)
Transzorb 20V
See chapter 9.3 "Line voltage"
45 - 60mA during AI pulse
max. 4,5mA during AI "dark" phase
26,5 ... 27,7V
max. 4,5mA
3 sec.
4.6 sec.
15 sec.
85mA
E3M080
007831_a_en_--.doc
03.2004