In no event shall ABB Oy be liable for direct, indirect, special, incidental, or consequential damages of any nature or kind arising from the use of this document, nor shall ABB Oy be liable for incidental or consequential damages arising from use of any software or hardware described in this document.
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual • Lowercase letters are used for the name of a keyboard key that is not labeled on the keyboard. For example, the space bar, comma key, and so on. • Press CTRL+C indicates that you must hold down the CTRL key while pressing the C key (to copy a selected object in this case).
Terminology The following is a list of terms associated with COM600 that you should be familiar with. The list contains terms that are unique to ABB or have a usage or definition that is different from standard industry usage. Term...
COM600S IEC is a substation automation, analyzer and data management unit that integrates devices, facilitates operations, manages communication and runs analysis applications pertinent to equipment or operations in utility or industrial distribution substations. • COM600F ANSI – COM600 as distribution automation controller (for ANSI markets)
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual • COM600F is a dedicated distribution automation controller unit that runs dis- tributed grid and feeder applications for ANSI power networks and inherits all core features of the COM600 series. 2.3. Overview of GOOSE Analyzer The GOOSE Analyzer functionality in COM600 can be used throughout the whole life cycle of the IEC 61850 substation automation system.
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual Getting started with COM600 GOOSE Analyzer 3.1. Starting COM600 GOOSE Analyzer GOOSE Connection Viewer is available in the WebHMI page, user can navigate to dif- ferent views here in the GOOSE Analyzer diagnostics page. gathmi.png Figure 3.1-1 GOOSE Analyzer tab on COM600 WebHMI menu bar 3.2.
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual gatclickonce.png Figure 3.2-1 Logging in to GOOSE Analyzer 3.3. Logging out from GOOSE Analyzer To log out from GOOSE Analyzer: 1. Move the cursor to the top of the screen to show the title bar. The title bar is displayed (see Figure 3.3-1).
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual 3.4.2. Title bar By default, the title bar is hidden in the main screen. To show the title bar, move the cursor to the top of the screen (see Figure 3.3-1 and Figure 3.3-1). •...
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual GOOSE Connection Viewer 4.1. Using GOOSE Connection Viewer GOOSE Connection Viewer presents graphical views of GOOSE signal flow from publishers to subscribers on the content page. The real-time diagnosis of the GOOSE signal flow dynamically controls the display of the graphical views.
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual 4.2. Viewing subnetworks 4.2.1. Viewing subnetwork level connections To see GOOSE connections for a chosen subnetwork, select the name of the subnetwork in the navigation tree. In Figure 4.1-1, each GOOSE publisher connects to a horizontal bar (later referred to as GOOSE bus) with an outward arrow exclusively, representing the publishing of all signals despite its internal GOOSE configuration.
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual colors (see Figure 4.2.2-1). The publishing IED is differentiated from the subscribing IEDs by coloring. HighlightConnection.png Figure 4.2.2-1 Highlighting GOOSE connection 4.2.3. Exploring GOOSE configuration To explore the sets of GOOSE signals associated with GOOSE control blocks, double- click the selected GOOSE bus (see Figure 4.2.3-1).
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual ExploringGOOSEconfiguration.png Figure 4.2.3-1 Exploring GOOSE configuration 4.2.4. Monitoring GOOSE bus status You can analyze the GOOSE bus status and mark it with different colors using GOOSE Analyzer (see Figure 4.2.4-1). GOOSE bus has four possible statuses: •...
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual GOOSE_Bus_Diagnosis.png Figure 4.2.4-1 Monitoring GOOSE bus status 4.2.5. Monitoring subnetwork status GOOSE Analyzer monitors intruding GOOSE conflicts (see Figure 4.2.4-1). For a more detailed explanation of the statuses, see 9.2.1, Subnetwork analyzer group. 4.3. Viewing GOOSE connections 4.3.1.
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual GOOSEDetail.png Figure 4.3.1-1 IED level GOOSE connection view As shown in Figure 4.3.1-1, the selected IED is positioned in the middle. The arrows on the left side of the selected IED indicate the subscribed GOOSE signals from other publishers, and the arrows on the right side indicate its published GOOSE signals to be subscribed by other IEDs.
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual 4.5. Exporting views To export the GOOSE connection views and GOOSE configurations into external html files, click Export. Exported information contains a subnetwork level view (see Figure 4.5-1), an IED level view (see Figure 4.5-2), and a detailed view of GOOSE configuration (see Figure 4.5- To navigate to different views, click the IED name in the first column.
Page 21
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual GOOSEConfigurationDetailedView.png Figure 4.5-3 Detailed view of GOOSE configuration...
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual Monitoring of events 5.1. Monitoring events GOOSE provides fast and reliable system-wide distribution of substation events over the switched networks. GOOSE Analyzer enables you to monitor these substation events transmitted over the subnetwork. GOOSE Analyzer monitors the transmission reliability of GOOSE messages and provides you with diagnostic events to verify the health of GOOSE with comparison to its config- uration.
Page 23
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual RealtimeEvents.png Figure 5.2-2 Real-time event list – GOOSE Events Each GOOSE diagnosis event record has the following properties: • Detected Time: date and time of a diagnostic event • Subnetwork: subnetwork name •...
Page 24
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual RealtimeGATEvents.png Figure 5.2-3 Real-time event list – GOOSE Diagnosis Events To configure the filter of the displayed list: 1. Click Filter. The Filter configuration dialog (see Figure 5.2-4) appears. 2. Select the specific branch to view. 3.
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual RealtimeEventListFilter.png Figure 5.2-4 Real-time event list filter To freeze/unfreeze the display of the event list, click respectively (see Figure 5.2-2). 5.3. Using Historical Events To view historical events, click on Historical Events on the menu bar. A new dialog box opens displaying all historical events (see Figure 5.3-1).
Page 26
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual GOOSEEvents.png Figure 5.3-1 Historical event list The historical event list is similar to the real-time event list but its data source is the historical database. To query specific events from the database, use conditional settings. You can reset the query conditions for new queries and export the queried events to text in csv format.
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual GOOSE Tester Manager 6.1. Using GOOSE Tester Manager GOOSE Tester Manager enables capturing raw GOOSE packets and associated events into a single record, and presenting graphical and system-oriented views of the recorded information.
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual To see the configuration details of a test case, double-click the test case. The details are shown on the right. To start or stop a test case, click Start or Stop. Test records created in the test case are listed at the lower part of the page.
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual The newly created tester script is added to the Test Overview list (see Figure 6.1- AddNewTriggerOptions.png Figure 6.2-2 Configuring trigger options for auto tester scripts Handling tester scripts: • To view existing scripts in COM600, click (refresh).
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual TestReportOverview.png Figure 6.3.1-1 Test report overview The record tab shows: • Statistics information about received packets • Detected GOOSE control blocks You can export the packets by clicking Export Packets..Details of GOOSE control blocks are listed in the navigation tree under subnetwork > IED >...
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual ExploringGOOSEPackets.png Figure 6.3.2-1 Exploring GOOSE packets GOOSE Packets Diagnosis explore the time based view of specific GOOSE packets that are captured from the network. 6.3.3. Exploring GOOSE events To open a new dialog box for the graphical representation of GOOSE events, click the context menu for Explore GOOSE Events (see Figure 6.3.3-1).
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual ExploringGOOSEEvents.png Figure 6.3.3-1 Exploring GOOSE events GOOSE Event Diagnosis discover and plot the trend of GOOSE message values of certain GOOSE Signal within the Tester’s triggering time frame. 6.3.4. Exploring GOOSE diagnosis To open a new dialog box for the graphical representation of GOOSE diagnosis events, click the context menu for Explore GOOSE Diagnosis (see Figure 6.3.4-1).
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual Network statistics 7.1. Viewing network statistics information GOOSE Analyzer can calculate the amount of GOOSE load periodically and store the calculations in the historical database. The configuration of the statistic interval is set in SAB600.
Page 34
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual DiagnosticStatisticTab.png Figure 7.1-2 Diagnostic Events Statistic To view a statistic trend, click an entry in the Network Statistic tab to plot the correspond- ing trend. GraphPanel.png Figure 7.1-3 Network statistic trend You can compare different trends on the plotting area by clicking a similar trend. To remove the plotting, click the entry again.
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual Interaction with COM600 WebHMI 8.1. Viewing GOOSE Analyzer diagnostic events in COM600 WebHMI The diagnostic events generated in GOOSE Analyzer can be viewed in the Events List in COM600 WebHMI. This functionality is used in cases where the GOOSE Analyzer diagnostics WebHMI is not started.
Page 36
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual GATFigure 1.1-2.png Figure 8.1-2 Corresponding GOOSE Analyzer diagnostic events in COM600 WebHMI Note that only diagnostic events can be viewed in COM600 WebHMI. These can be used to verify the health of GOOSE.
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual GOOSE Analyzer Engine 9.1. Using GOOSE Analyzer Engine GOOSE Analyzer Engine provides means to verify and validate GOOSE signals against GOOSE configurations in the substation configuration description (SCD). The engine continuously analyzes the decoded GOOSE packets and monitors the availability, reliab- ility, and status transitions of GOOSE.
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual For each interval, the analyzer sums up: • Received network packets • Received network bytes • Received GOOSE packets • Received GOOSE bytes • Received GOOSE events for users 9.3. IED analyzers 9.3.1.
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual 9.4. GOOSE control block analyzers 9.4.1. GOOSE control block analyzer group This group is designed to analyze GoCB wide GOOSE with comparison to the corres- ponding configurations in the SCD. The following analyzers belong to this group: •...
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual The reserved value range for GOOSE type 1 is 0x0000 to 0x3FFF. For GOOSE type 1A (Trip), the reserved value range is 0x8000 to 0xBFFF. If no APPID is configured, the default value is 0x0000. This default value indicates the lack of configuration. It is recommended to use a unique, source-orientated GOOSE APPID within a system.
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual 9.4.6. VLAN tag analyzer VLAN tag analyzer allows users to check the existence of a VLAN tag in the GOOSE frames, in case a VLAN tag is not supported and removed by ethernet switches. When a VLAN tag is missing from the GOOSE frames, the analyzer issues a specific event to warn users of the status transition.
COM600 series 5.0 1MRS757546 GOOSE Analyzer Operator's Manual The counter is incremented when the configuration changes. At configuration time, the configuration tool is responsible for incrementing/maintaining the ConfRev value. When configuration changes occur due to SetGoCBValues, the IED is responsible for incre- menting the value of ConfRev.
1MRS757546 COM600 series 5.0 GOOSE Analyzer Operator's Manual StNum and SqNum are integers ranging from 1 to 4 294 967 295. If counter SqNum overruns, it has to be set to 1. The disorder analyzer verifies StNum and SqNum contained in the received GOOSE message (packet) for each GOOSE control block.