5 SETTINGS
When changes are made to the oscillography settings, all existing oscillography records are cleared.
NOTE
b) DIGITAL CHANNELS
PATH: SETTINGS
PRODUCT SETUP
DIGITAL CHANNELS
MESSAGE
MESSAGE
A
setting selects the FlexLogic™ operand state recorded in an oscillography trace. The length of
DIGITAL 1(63) CHANNEL
each oscillography trace depends in part on the number of parameters selected here. Parameters set to "Off" are ignored.
Upon startup, the relay will automatically prepare the parameter list.
c) ANALOG CHANNELS
PATH: SETTINGS
PRODUCT SETUP
ANALOG CHANNELS
MESSAGE
MESSAGE
These settings select the metering actual value recorded in an oscillography trace. The length of each oscillography trace
depends in part on the number of parameters selected here. Parameters set to "Off" are ignored. The parameters available
in a given relay are dependent on:
•
The type of relay,
•
The type and number of CT/VT hardware modules installed, and
•
The type and number of analog input hardware modules installed.
Upon startup, the relay will automatically prepare the parameter list. A list of all possible analog metering actual value
parameters is presented in Appendix A: FlexAnalog parameters. The parameter index number shown in any of the tables is
used to expedite the selection of the parameter on the relay display. It can be quite time-consuming to scan through the list
of parameters via the relay keypad and display - entering this number via the relay keypad will cause the corresponding
parameter to be displayed.
All eight CT/VT module channels are stored in the oscillography file. The CT/VT module channels are named as follows:
<slot_letter><terminal_number>—<I or V><phase A, B, or C, or 4th input>
The fourth current input in a bank is called IG, and the fourth voltage input in a bank is called VX. For example, F2-IB desig-
nates the IB signal on terminal 2 of the CT/VT module in slot F.
If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will
appear.
GE Multilin
OSCILLOGRAPHY
DIGITAL CHANNELS
DIGITAL CHANNEL
Off
DIGITAL CHANNEL
Off
↓
DIGITAL CHANNEL 63:
Off
OSCILLOGRAPHY
ANALOG CHANNELS
ANALOG CHANNEL
1:
Off
ANALOG CHANNEL
2:
Off
↓
ANALOG CHANNEL 16:
Off
C30 Controller System
Range: FlexLogic™ operand
1:
Range: FlexLogic™ operand
2:
Range: FlexLogic™ operand
Range: Off, any FlexAnalog parameter
See Appendix A for complete list.
Range: Off, any FlexAnalog parameter
See Appendix A for complete list.
Range: Off, any FlexAnalog parameter
See Appendix A for complete list.
5.2 PRODUCT SETUP
5
5-37