Page 3
___________________ Terminal Board 30 (TB30) Safety information ___________________ General ___________________ Mechanical installation SINAMICS ___________________ Electrical installation SINAMICS G130 ___________________ Terminal Board 30 (TB30) Technical specifications Operating Instructions Control version V4.5 03/2012 A5E01221269A...
Page 4
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Safety information Warnings WARNING Hazardous voltages are present when electrical equipment is in operation. Severe personal injury or substantial material damage may result if these warnings are not observed. Only qualified personnel are permitted to work on or around the equipment. This personnel must be thoroughly familiar with all the warnings and maintenance procedures described in these operating instructions.
The operating manual and machine documentation are written in different languages as specified in the delivery contracts. Note We recommend engaging the support and services of your local Siemens service center for all planning, installation, commissioning and maintenance work. Terminal Board 30 (TB30)
Safety information 1.3 Components that can be destroyed by electrostatic discharge (ESD) Components that can be destroyed by electrostatic discharge (ESD) CAUTION The board contains components that can be destroyed by electrostatic discharge. These components can be easily destroyed if not handled properly. If you do have to use electronic boards, however, please observe the following: •...
Page 10
Safety information 1.3 Components that can be destroyed by electrostatic discharge (ESD) Terminal Board 30 (TB30) Operating Instructions, 03/2012, A5E01221269A...
General Description The TB30 Terminal Board supports the addition of digital inputs/digital outputs and analog inputs/analog outputs to the Control Unit. The following are located on the TB30 Terminal Board: ● Power supply for digital inputs/digital outputs ● 4 digital inputs ●...
Mechanical installation CAUTION The option board may only be inserted and removed when the control unit and option board are disconnected from the power supply. Figure 3-1 Installing an Option Board on a CU320-2 DP Terminal Board 30 (TB30) Operating Instructions, 03/2012, A5E01221269A...
Page 14
Mechanical installation Figure 3-2 Installing an Option Board on a CU320-2 PN Terminal Board 30 (TB30) Operating Instructions, 03/2012, A5E01221269A...
Page 17
Electrical installation X424 power supply, digital outputs Table 4- 1 Terminal block X424 Terminal Function Technical data Power supply Voltage: 24 V DC (20.4 V - 28.8 V) Current consumption: Max. 4 A (per digital output max. Power supply 0.5 A) Ground Ground Max.
Page 18
Electrical installation Digital inputs/outputs X481 Table 4- 2 Terminal strip X481 Terminal Designation Technical data DI 0 Voltage: - 3 V to 30 V Current consumption: 10 mA at 24 V DC DI 1 Ground reference: X424.M DI 2 Input delay: DI 3 - for "0"...
Page 19
Electrical installation Analog inputs/outputs X482 Table 4- 3 Terminal strip X482 Terminal Designation Technical data AI 0+ Analog inputs (AI) Voltage: -10 V to +10 V AI 0- Inner flow resistance: 65 kΩ AI 1+ Resolution: 13 bit + sign AI 1- AO 0+ Analog outputs (AO)
Page 20
Electrical installation Shield connection of the TB30 on the Control Unit CU320 Figure 4-3 TB30 shield connection The permissible bending radii for the cables must not be exceeded when the cables are being installed. Terminal Board 30 (TB30) Operating Instructions, 03/2012, A5E01221269A...
Technical specifications General technical data Table 5- 1 General technical data Product standard EN 61800-5-1 Technical data Table 5- 2 Technical data Unit Value Electronic power supply Voltage 24 DC (20.4 – 28.8) Current via the option slot of the CU 0.05 (without digital outputs) Power loss...