Page 3
GE Industrial Systems ADDENDUM This Addendum contains information that relates to the C60 relay, version 2.9X. This addendum lists a number of information items that appear in the instruction manual GEK-106376 (1601-0100-B8) but are not included in the cur- rent C60 operations.
1.3 URPC SOFTWARE 1.3.1 PC REQUIREMENTS ..................1-5 1.3.2 SOFTWARE INSTALLATION ................1-5 ® 1.3.3 CONNECTING URPC WITH THE C60............1-6 1.4 UR HARDWARE 1.4.1 MOUNTING AND WIRING................. 1-8 1.4.2 COMMUNICATIONS..................1-8 1.4.3 FACEPLATE DISPLAY ..................1-8 1.5 USING THE RELAY 1.5.1...
Page 6
FLEXLOGIC™ TIMERS ...................5-43 5.4.7 FLEXELEMENTS™ ..................5-44 5.5 GROUPED ELEMENTS 5.5.1 OVERVIEW ......................5-48 5.5.2 SETTING GROUP ....................5-48 5.5.3 BREAKER FAILURE ..................5-48 5.5.4 VOLTAGE ELEMENTS ..................5-58 5.6 CONTROL ELEMENTS 5.6.1 OVERVIEW ......................5-62 5.6.2 SETTING GROUPS..................5-62 5.6.3 SYNCHROCHECK ...................5-63 C60 Breaker Management Relay GE Multilin...
Page 7
DATA LOGGER ....................6-16 6.4.6 MAINTENANCE ....................6-17 6.5 PRODUCT INFORMATION 6.5.1 MODEL INFORMATION .................. 6-18 6.5.2 FIRMWARE REVISIONS ................. 6-18 7. COMMANDS AND 7.1 COMMANDS TARGETS 7.1.1 COMMANDS MENU ..................7-1 7.1.2 VIRTUAL INPUTS....................7-1 GE Multilin C60 Breaker Management Relay...
Page 8
FUNCTION CODE 10H: STORE MULTIPLE SETTINGS ......... B-6 B.1.10 EXCEPTION RESPONSES................B-6 B.2 FILE TRANSFERS ® B.2.1 OBTAINING UR FILES USING MODBUS PROTOCOL ......... B-7 ® B.2.2 MODBUS PASSWORD OPERATION............. B-8 B.3 MEMORY MAPPING ® B.3.1 MODBUS MEMORY MAP ................B-9 C60 Breaker Management Relay GE Multilin...
Page 9
COUNTERS .....................E-14 E.3.4 ANALOG INPUTS ....................E-15 F. MISCELLANEOUS F.1 CHANGE NOTES F.1.1 REVISION HISTORY ..................F-1 F.1.2 CHANGES TO C60 MANUAL................F-1 F.2 TABLES AND FIGURES F.2.1 LIST OF TABLES....................F-3 F.2.2 LIST OF FIGURES..................... F-4 F.3 ABBREVIATIONS F.3.1 STANDARD ABBREVIATIONS ................. F-6 F.4 WARRANTY...
Page 10
TABLE OF CONTENTS C60 Breaker Management Relay GE Multilin...
• registration card (attached as the last page of the manual) • Fill out the registration form and mail it back to GE Multilin (include the serial number located on the rear nameplate). • For product information, instruction manual updates, and the latest software updates, please visit the GE Multilin Home Page at http://www.GEindustrial.com/multilin.
This new generation of equipment must also be easily incorporated into automation systems, at both the station and enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals. C60 Breaker Management Relay...
The remote outputs interface to the remote inputs of other UR devices. Remote outputs are FlexLogic™ operands inserted into UCA2 GOOSE messages and are of two assignment types: DNA standard functions and USER defined functions. GE Multilin C60 Breaker Management Relay...
MENU section. An explanation of the use of inputs from CTs and VTs is in the INTRODUCTION TO AC SOURCES section. A description of how digital signals are used and routed within the relay is contained in the INTRODUCTION TO FLEX- LOGIC™ section. C60 Breaker Management Relay GE Multilin...
10. Subsequently, double click on the URPC software icon to activate the application. Refer to the HUMAN INTERFACES chapter in this manual and the URPC Software Help program for more information about the URPC software interface. NOTE GE Multilin C60 Breaker Management Relay...
Click the "OK" button then click "Finish". The new Site List tree will be added to the Site List window (or Online window) located in the top left corner of the main URPC window. The Site Device has now been configured for RS232 communications. Proceed to Section c) CONNECTING TO THE RELAY below to begin communications. C60 Breaker Management Relay GE Multilin...
Page 17
In a few moments, the flashing light should turn green, indicating that URPC is communicating with the relay. Refer to the HUMAN INTERFACES chapter in this manual and the URPC Software Help program for more information about the URPC software interface. NOTE GE Multilin C60 Breaker Management Relay...
This device (catalog number F485) connects to the computer using a "straight-through" serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the C60 rear communications port. The con- verter terminals (+, –, GND) are connected to the C60 communication module (+, –, COM) terminals. Refer to the CPU COMMUNICATION PORTS section in the HARDWARE chapter for option details.
MESSAGE key from a setting value or actual value display returns to the header display. HIGHEST LEVEL LOWEST LEVEL (SETTING VALUE) ## SETTINGS # PASSWORD ACCESS LEVEL: ## PRODUCT SETUP # SECURITY Restricted ## SETTINGS ## SYSTEM SETUP GE Multilin C60 Breaker Management Relay...
1.5.5 BATTERY TAB The battery tab is installed in the power supply module before the C60 shipped from the factory. The battery tab prolongs battery life in the event the relay is powered down for long periods of time before installation. The battery is responsible for backing up event records, oscillography, data logger, and real-time clock information when the relay is powered off.
2 PRODUCT DESCRIPTION 2.1 INTRODUCTION 2.1.1 OVERVIEW The C60 Breaker Management Relay is a microprocessor based relay designed for breaker monitoring, control and protec- tion. Voltage and current metering is built into the relay as a standard feature. Current parameters are available as total wave- form RMS magnitude, or as fundamental frequency only RMS magnitude and angle (phasor).
Page 22
Digital Elements (16) Oscillography Disturbance Detection Setting Groups (8) Event Recorder Transducer I/O Fault Detector and Fault Report User Definable Displays FlexElements™ (16) User Programmable LEDs FlexLogic™ Equations Virtual Inputs (32) Virtual Outputs (64) C60 Breaker Management Relay GE Multilin...
±0.5% of reading from 10 to 208 V Curve Shapes: GE IAV Inverse Definite Time Curve Multiplier: Time Dial = 0 to 600.00 in steps of 0.01 Timing Accuracy: ±3% of operate time or ±4 ms (whichever is greater) GE Multilin C60 Breaker Management Relay...
1 sec.; 1, 5, 10, 15, 20, 30, 60 min. Storage Capacity: (NN is dependent on memory) 1-second rate: 01 channel for NN days 16 channels for NN days ↓ ↓ 60-minute rate: 01 channel for NN days 16 channels for NN days C60 Breaker Management Relay GE Multilin...
±0.2% of full scale Relay Burden: < 0.25 VA at 120 V Type: Passive Conversion Range: 1 to 275 V Voltage Withstand: cont. at 260 V to neutral 1 min./hr at 420 V to neutral GE Multilin C60 Breaker Management Relay...
2.2.9 ENVIRONMENTAL Operating Temperatures: Humidity (noncondensing): IEC 60068-2-30, 95%, Variant 1, 6 Cold: IEC 60028-2-1, 16 h at –40°C days Dry Heat: IEC 60028-2-2, 16 h at 85°C Altitude: Up to 2000 m Installation Category: GE Multilin C60 Breaker Management Relay...
IEC 1010-1 EMC 81/336/EEC: EN 50081-2 EN 50082-2 2.2.13 MAINTENANCE Cleaning: Normally, cleaning is not required; but for situations where dust has accumulated on the faceplate display, a dry cloth can be used. 2-10 C60 Breaker Management Relay GE Multilin...
RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay. UR SERIES UR SERIES Figure 3–1: C60 VERTICAL MOUNTING AND DIMENSIONS GE Multilin C60 Breaker Management Relay...
Page 32
3.1 DESCRIPTION 3 HARDWARE Figure 3–2: C60 VERTICAL SIDE MOUNTING INSTALLATION C60 Breaker Management Relay GE Multilin...
Type 9C and 9D CPU modules are equipped with 10BaseT and 10BaseF Ethernet connectors for communications. These connectors must be individually disconnected from the module before the it can be removed from the chas- sis. NOTE C60 Breaker Management Relay GE Multilin...
(nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following figure for an example of rear terminal assignments. Figure 3–7: EXAMPLE OF MODULES IN F & H SLOTS GE Multilin C60 Breaker Management Relay...
PROVIDED Supply (Rear View) This diagram is based on the following order code: C60-A00-HCL-F8A-H6B-M6K-P5F. The purpose of this diagram is to provide an example of how the relay is typically wired, not specifi- CAUTION cally how to wire your own relay. Please refer to the following pages for examples to help you wire your relay correctly based on your own relay configuration and order code.
Table 3–2: CONTROL POWER VOLTAGE RANGE RANGE NOMINAL VOLTAGE 24 to 48 V (DC only) 125 to 250 V The power supply module provides power to the relay and supplies power for dry contact input connections. GE Multilin C60 Breaker Management Relay...
CT connections for both ABC and ACB phase rotations are identical as shown in the TYPICAL WIRING DIAGRAM. The exact placement of a zero sequence CT so that ground fault current will be detected is shown below. Twisted pair cabling on the zero sequence CT is recommended. C60 Breaker Management Relay GE Multilin...
Page 39
Figure 3–11: CT/VT MODULE WIRING CURRENT INPUTS 8C / 8D / 8Z CTMDL8CD.cdr (P/O 827831A1.CDR) Figure 3–12: CT MODULE WIRING Wherever a tilde “~” symbol appears, substitute with the Slot Position of the module. NOTE GE Multilin C60 Breaker Management Relay...
Cont Op x Ioff Load b) Current with optional voltage monitoring Current monitoring only Both voltage and current monitoring (external jumper a-b is required) Load c) No monitoring 827821A4.CDR Figure 3–13: FORM-A CONTACT FUNCTIONS 3-10 C60 Breaker Management Relay GE Multilin...
Page 41
2 Inputs Fast Form-C ~6a, ~6c 2 Inputs ~6a, ~6c 2 Inputs Fast Form-C ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs Fast Form-C ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs Fast Form-C GE Multilin C60 Breaker Management Relay 3-11...
Page 43
CONTACT IN CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON COMMON SURGE CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON SURGE Figure 3–14: DIGITAL I/O MODULE WIRING (SHEET 1 OF 2) GE Multilin C60 Breaker Management Relay 3-13...
Page 44
SURGE 827719AR.CDR Sheet 2 of 2 Figure 3–15: DIGITAL I/O MODULE WIRING (SHEET 2 OF 2) CORRECT POLARITY MUST BE OBSERVED FOR ALL CONTACT INPUT CONNECTIONS OR EQUIP- MENT DAMAGE MAY RESULT. CAUTION 3-14 C60 Breaker Management Relay GE Multilin...
Page 45
DC current flowing through the contacts when the Form-A contact closes. If enabled, the cur- rent monitoring can be used as a seal-in signal to ensure that the Form-A contact does not attempt to break the energized inductive coil circuit and weld the output contacts. GE Multilin C60 Breaker Management Relay 3-15...
COM 1 10BaseT TEST ONLY 10BaseT TEST ONLY RS485 RS485 RS485 COM 2 COM 2 COM 2 IRIG-B IRIG-B IRIG-B SURGE GROUND SURGE SURGE COMMOD.CDR P/O 827719C2.CDR Figure 3–19: CPU MODULE COMMUNICATIONS WIRING GE Multilin C60 Breaker Management Relay 3-17...
Page 48
EACH END (TYPICALLY 120 Ohms and 1 nF) 485 - SURGE COMP 485COM UP TO 32 DEVICES, RELAY MAXIMUM 4000 FEET 485 + 485 - SURGE COMP 485COM LAST DEVICE 827757A5.DWG Figure 3–20: RS485 SERIAL CONNECTION 3-18 C60 Breaker Management Relay GE Multilin...
(AM). Third party equipment is available for generating the IRIG-B signal; this equipment may use a GPS satellite system to obtain the time reference so that devices at different geographic locations can also be synchronized. GE Multilin C60 Breaker Management Relay 3-19...
® The URPC software, provided with every C60 relay, can be run from any computer supporting Microsoft Windows 95, 98, or NT. This chapter provides a summary of the basic URPC software interface features. The URPC Help file provides details for getting started and using the URPC software interface.
Page 52
“EEPROM DATA ERROR” message displayed after upgrading/downgrading the firmware is a resettable, self-test message intended to inform users that the Modbus addresses have changed with the upgraded firmware. This message does not signal any problems when appearing after firmware upgrades. C60 Breaker Management Relay GE Multilin...
Settings List control bar window Device data view window(s), with common tool bar Settings File data view window(s), with common tool bar Workspace area with data view tabs Status bar Figure 4–1: URPC SOFTWARE MAIN WINDOW GE Multilin C60 Breaker Management Relay...
IN SERVICE VOLTAGE TROUBLE CURRENT RESET TEST MODE FREQUENCY LED PANEL 1 TRIP OTHER USER 1 ALARM PHASE A PICKUP PHASE B USER 2 PHASE C NEUTRAL/GROUND USER 3 Figure 4–3: UR VERTICAL FACEPLATE PANELS C60 Breaker Management Relay GE Multilin...
OTHER: Indicates a composite function was involved. • PHASE A: Indicates Phase A was involved. • PHASE B: Indicates Phase B was involved. • PHASE C: Indicates Phase C was involved. • NEUTRAL/GROUND: Indicates neutral or ground was involved. GE Multilin C60 Breaker Management Relay...
Page 56
LED settings must be entered as shown in the USER-PROGRAMMABLE LEDs section of the SET- TINGS chapter. The LEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both LED panels 2 and 3 as explained in the next section. C60 Breaker Management Relay GE Multilin...
For Position and Size enable the "Center image" and "Maintain aspect ratio" check boxes and press "OK", then "OK" once more to print. From the printout, cut-out the BACKGROUND TEMPLATE from the three windows (use the cropmarks as a guide). GE Multilin C60 Breaker Management Relay...
The key may be pressed at any time for context sensitive help messages. The key stores altered setting values. MENU HELP MESSAGE ESCAPE VALUE ENTER Figure 4–8: KEYPAD C60 Breaker Management Relay GE Multilin...
4.2.7 BREAKER CONTROL The C60 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, which can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually initiated from faceplate keypad or automatically initiated from a FlexLogic™...
MESSAGE key from a setting value or actual value display returns to the header display. HIGHEST LEVEL LOWEST LEVEL (SETTING VALUE) ## SETTINGS # PASSWORD ACCESS LEVEL: ## PRODUCT SETUP # SECURITY Restricted ## SETTINGS ## SYSTEM SETUP 4-10 C60 Breaker Management Relay GE Multilin...
While at the maximum value, pressing the VALUE key again will allow the setting selection to continue upward from the minimum value. The VALUE key decrements the displayed value by the step value, down to the GE Multilin C60 Breaker Management Relay 4-11...
Page 62
Flash messages will sequentially appear for several seconds each. For the case of a text setting message, the key displays how to edit and store a new value. 4-12 C60 Breaker Management Relay GE Multilin...
Page 63
Press the key until the 'SETTINGS' header flashes momentarily and the ‘SETTINGS PRODUCT SETUP’ mes- sage appears on the display. Press the MESSAGE key until the ‘ACCESS LEVEL:’ message appears on the display. GE Multilin C60 Breaker Management Relay 4-13...
Page 64
(for each security level) before a new password can be entered. In the event that a password has been lost (forgotten), submit the corresponding Encrypted Password from the PASS- WORD SECURITY menu to the Factory for decoding. 4-14 C60 Breaker Management Relay GE Multilin...
This setting programs the element to be operational when selected as "Enabled". The factory default is "Disabled". Once programmed to "Enabled", any element associated with the Function becomes active and all options become available. NAME Setting This setting is used to uniquely identify the element. GE Multilin C60 Breaker Management Relay...
BACKGROUND The C60 may be used on systems with breaker-and-a-half or ring bus configurations. In these applications, each of the two three-phase sets of individual phase currents (one associated with each breaker) can be used as an input to a breaker fail- ure element.
Page 69
Source as 'Wdg 1 Current'. Once the Sources have been configured, the user has them available as selections for the choice of input signal for the pro- tection elements and as metered quantities. GE Multilin C60 Breaker Management Relay...
Page 70
Source is a transformer winding, on which a three phase voltage is mea- sured, and the sum of the currents from CTs on each of two breakers is required to measure the winding current flow. C60 Breaker Management Relay GE Multilin...
If an entered password is lost (or forgotten), consult the factory service department with the corresponding ENCRYPTED PASSWORD If the password and password are set the same, the one password will allow access to SETTING COMMAND commands and settings. NOTE GE Multilin C60 Breaker Management Relay...
0 ms The C60 is equipped with up to 3 independent serial communication ports. The faceplate RS232 port is intended for local use and has fixed parameters of 19200 baud and no parity. The rear COM1 port type will depend on the CPU ordered: it may be either an Ethernet or an RS485 port.
Page 73
When the NSAP address, any TCP/UDP Port Number, or any User Map setting (when used with DNP) is changed, it will not become active until power to the relay has been cycled (OFF/ON). NOTE GE Multilin C60 Breaker Management Relay...
Page 74
MODBUS SLAVE ADDRESS ports each C60 must have a unique address from 1 to 254. Address 0 is the broadcast address which all Modbus slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same address or conflicts resulting in errors will occur.
Page 75
The C60 supports the Distributed Network Protocol (DNP) version 3.0. The C60 can be used as a DNP slave device con- nected to a single DNP master (usually either an RTU or a SCADA master station). Since the C60 maintains one set of DNP data change buffers and connection information, only one DNP master should actively communicate with the C60 at one time.
Page 76
DNP VOLTAGE SCALE FACTOR Input points that are voltages will be returned with values 1000 times smaller (e.g. a value of 72000 V on the C60 will be returned as 72). These settings are useful when Analog Input values must be adjusted to fit within certain ranges in DNP masters.
Page 77
The web pages can be accessed by connecting the UR and a computer to an ethernet network. The Main Menu will be dis- played in the web browser on the computer simply by entering the IP address of the C60 into the "Address" box on the web browser.
Page 78
The C60 supports the IEC 60870-5-104 protocol. The C60 can be used as an IEC 60870-5-104 slave device connected to a single master (usually either an RTU or a SCADA master station). Since the C60 maintains one set of IEC 60870-5-104 data change buffers, only one master should actively communicate with the C60 at one time.
Pre-fault current and voltage phasors (one-quarter cycle before the trigger) • Fault current and voltage phasors (three-quarter cycle after the trigger) • Target Messages that are set at the time of triggering • Events (9 before trigger and 7 after trigger) GE Multilin C60 Breaker Management Relay 5-15...
# DIGITAL CHANNELS Range: FlexLogic™ operand DIGITAL CHANNEL 2: ↓ Range: FlexLogic™ operand DIGITAL CHANNEL 63: Range: 1 to 16 channels # ANALOG CHANNELS Range: Off, any analog Actual Value parameter ANALOG CHANNEL 1: ↓ 5-16 C60 Breaker Management Relay GE Multilin...
Page 81
IB signal on terminal 2 of the CT/VT module in slot F. If there are no CT/VT modules and Analog Input modules, no analog traces will appear in the file; only the digital traces will appear. When changes are made to the oscillography settings, all existing oscillography records will be CLEARED. WARNING GE Multilin C60 Breaker Management Relay 5-17...
POWER DEMAND METHOD: MESSAGE Rolling Demand Thermal Exponential Range: 5, 10, 15, 20, 30, 60 minutes DEMAND INTERVAL: MESSAGE 15 MIN Range: FlexLogic™ operand DEMAND TRIGGER: MESSAGE Note: for calculation using Method 2a 5-18 C60 Breaker Management Relay GE Multilin...
Page 83
This method calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent power) over the programmed demand time interval, in the same way as Block Interval. The value is updated every minute and indicates the demand over the time interval just preceding the time of update. GE Multilin C60 Breaker Management Relay 5-19...
LED 11 Operand BREAKER 1 TROUBLE LED 23 Operand AR RIP LED 12 Operand LED 24 Operand AR LO Refer to the CONTROL OF SETTINGS GROUPS example in the CONTROL ELEMENTS section for group activation. 5-20 C60 Breaker Management Relay GE Multilin...
Range: 0 to 65535 in steps of 1 DISP 1 ITEM 4 MESSAGE Range: 0 to 65535 in steps of 1 DISP 1 ITEM 5: MESSAGE # USER DISPLAY 2 ↓ # USER DISPLAY 8 GE Multilin C60 Breaker Management Relay 5-21...
Page 86
This item is not being used - there is no corresponding DISP 1 ITEM 5: MESSAGE Tilde marker in Top or Bottom lines. Shows the resultant display content. USER DISPLAYS Current X 0.850 A → Current Y 0.327 A 5-22 C60 Breaker Management Relay GE Multilin...
This name will appear on generated reports. This name RELAY NAME is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com- munications channel using the UCA2/MMS protocol. GE Multilin C60 Breaker Management Relay 5-23...
SRC1 currents, then PKP level of 1 pu will operate on 1000 A primary. The same rule will apply for sums of currents from CTs with different secondary taps (5 A and 1 A). 5-24 C60 Breaker Management Relay GE Multilin...
CT and VT input. For CT inputs, this is the nominal primary and secondary current. For VTs, this is the connection type, ratio and nominal secondary voltage. Once the inputs have been specified, the configuration for each Source is entered, including specifying which CTs will be summed together. 5-26 C60 Breaker Management Relay GE Multilin...
Page 91
An example of the use of Sources, with a relay with three CT/VT modules, is shown in the diagram below. A relay could have the following hardware configuration: INCREASING SLOT POSITION LETTER --> CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3 GE Multilin C60 Breaker Management Relay 5-27...
These settings specify the characteristics of the line. The line impedance value should be entered as secondary ohms. This data is used for fault location calculations. See the !" menu for assigning SETTINGS PRODUCT SETUP FAULT REPORT the Source and Trigger for fault calculations. 5-28 C60 Breaker Management Relay GE Multilin...
No. 1. BREAKER 1 FUNCTION: Set to "Enable" to allow the operation of any breaker control feature. BREAKER1 PUSH BUTTON CONTROL: Set to "Enable" to allow faceplate push button operations. BREAKER 1 NAME: GE Multilin C60 Breaker Management Relay 5-29...
Page 94
USER 1 on the relay faceplate) until the automatic de-selection of the breaker, so that the breaker does not remain selected indefinitely. This setting is active only if is "Enabled". BREAKER PUSHBUTTON CONTROL 5-30 C60 Breaker Management Relay GE Multilin...
Page 95
5 SETTINGS 5.3 SYSTEM SETUP Figure 5–5: DUAL BREAKER CONTROL SCHEME LOGIC GE Multilin C60 Breaker Management Relay 5-31...
Traditionally, protective relay logic has been relatively limited. Any unusual applications involving interlocks, blocking, or supervisory functions had to be hard-wired using contact inputs and outputs. FlexLogic™ minimizes the requirement for auxiliary components and wiring while making more complex schemes possible. 5-32 C60 Breaker Management Relay GE Multilin...
Page 97
The virtual input is presently in the ON state. Virtual Output Virt Op 1 On The virtual output is presently in the set state (i.e. evaluation of the equation which produces this virtual output results in a "1"). GE Multilin C60 Breaker Management Relay 5-33...
Page 98
5.4 FLEXLOGIC™ 5 SETTINGS The operands available for this relay are listed alphabetically by types in the following table. Table 5–10: C60 FLEXLOGIC™ OPERANDS (Sheet 1 of 3) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: AR ENABLED Autoreclosure is enabled and ready to perform...
Page 99
5 SETTINGS 5.4 FLEXLOGIC™ Table 5–10: C60 FLEXLOGIC™ OPERANDS (Sheet 2 of 3) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: FLEXELEMENT 1 PKP FlexElement 1 has picked up FlexElements™ FLEXELEMENT 1 OP FlexElement 1 has operated FLEXELEMENT 1 DPO FlexElement 1 has dropped out ↓...
Page 100
5.4 FLEXLOGIC™ 5 SETTINGS Table 5–10: C60 FLEXLOGIC™ OPERANDS (Sheet 3 of 3) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION RESETTING RESET OP Reset command is operated (set by all 3 operands below) RESET OP (COMMS) Communications source of the reset command...
Assigning the output of an operator to a Virtual Output terminates the equation. A timer operator (e.g. "TIMER 1") or virtual output assignment (e.g. " = Virt Op 1") may only be used once. If this rule is broken, a syntax error will be declared. GE Multilin C60 Breaker Management Relay 5-37...
Virtual Output and assigned the next available number (i.e. Virtual Output 3). The final output must also be assigned to a Virtual Output as Virtual Output 4, which will be programmed in the contact output section to operate relay H1 (i.e. Output Contact H1). 5-38 C60 Breaker Management Relay GE Multilin...
Page 103
Until accustomed to using FlexLogic™, it is suggested that a worksheet with a series of cells marked with the arbitrary parameter numbers be prepared, as shown below. GE Multilin C60 Breaker Management Relay 5-39...
Page 104
FLEXLOGIC ENTRY n: =Virt Op 3 827030A2.VSD Figure 5–12: FLEXLOGIC™ EQUATION & LOGIC FOR VIRTUAL OUTPUT 3 Repeating the process described for VIRTUAL OUTPUT 3, select the FlexLogic™ parameters for Virtual Output 4. 5-40 C60 Breaker Management Relay GE Multilin...
Page 105
It is now possible to check that the selection of parameters will produce the required logic by converting the set of parame- ters into a logic diagram. The result of this process is shown below, which is compared to figure: LOGIC FOR VIRTUAL OUTPUT 4, as a check. GE Multilin C60 Breaker Management Relay 5-41...
Page 106
Virt Op 1 On Virt Op 2 On Virt Ip 1 On DIG ELEM 1 PKP XOR(2) Virt Op 3 On OR(4) LATCH (S,R) Virt Op 3 On TIMER 1 Cont Ip H1c On OR(3) 5-42 C60 Breaker Management Relay GE Multilin...
This setting is used to set the time delay to pickup. If a pickup delay is not required, set this function to "0". TIMER 1 DROPOUT DELAY: This setting is used to set the time delay to dropout. If a dropout delay is not required, set this function to "0". GE Multilin C60 Breaker Management Relay 5-43...
The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice. 5-44 C60 Breaker Management Relay GE Multilin...
Page 109
The FLEXELEMENT 1 DIRECTION following figure explains the application of the FLEXELEMENT 1 DIRECTION FLEXELEMENT 1 PICKUP FLEXELEMENT 1 HYS- settings. TERESIS GE Multilin C60 Breaker Management Relay 5-45...
Page 111
"Delta". FLEXELEMENT 1 COMP MODE This setting specifies the pickup delay of the element. The setting FLEXELEMENT 1 PKP DELAY FLEXELEMENT 1 RST DELAY specifies the reset delay of the element. GE Multilin C60 Breaker Management Relay 5-47...
BF1 TIMER 1 PICKUP MESSAGE DELAY: 0.000 s Range: Yes, No BF1 USE TIMER 2: MESSAGE Range: 0.000 to 65.535 s in steps of 0.001 BF1 TIMER 2 PICKUP MESSAGE DELAY: 0.000 s 5-48 C60 Breaker Management Relay GE Multilin...
Page 113
Because breaker failure can result in tripping a large number of breakers and this affects system safety and stability, a very high level of security is required. GE Multilin C60 Breaker Management Relay 5-49...
Page 114
FlexLogic™ operands that initiate tripping required to clear the faulted zone. The trip output can be sealed-in for an adjustable period. • Target message indicating a failed breaker has been declared • Illumination of the faceplate TRIP LED (and the PHASE A, B or C LED, if applicable) 5-50 C60 Breaker Management Relay GE Multilin...
Page 115
Note that in bulk oil circuit breakers, the interrupting time for currents less than 25% of the interrupting rating can be signifi- cantly longer than the normal interrupting time. GE Multilin C60 Breaker Management Relay 5-51...
Page 116
BF1 BKR POS2 B (valid only for 1-pole breaker failure schemes): Selects the FlexLogic™ operand that represents the protected breaker normal-type auxiliary switch contact on pole B (52/ a). This may be a multiplied contact. 5-52 C60 Breaker Management Relay GE Multilin...
Page 117
The overcurrent detectors have ganged settings. Upon operation of the breaker failure element for a single pole trip command, a 3-pole trip command should be given via output operand BKR FAIL 1 TRIP OP GE Multilin C60 Breaker Management Relay 5-53...
Page 118
BF1 SOURCE : Initiated Ph C PICKUP : TO SHEET 2 OF 2 PICKUP PICKUP PICKUP TO SHEET 2 OF 2 (827070.CDR) 827069A5.CDR Figure 5–18: BREAKER FAILURE 1-POLE [INITIATE] (Sheet 1 of 2) 5-54 C60 Breaker Management Relay GE Multilin...
Page 119
BF1 BKR POS2 FLEXLOGIC OPERAND Off=0 BKR FAIL 1 T3 OP SETTING BF1 BKR POS2 Off=0 SETTING BF1 BREAKER TEST ON: Off=0 827070A3.CDR Figure 5–19: BREAKER FAILURE 1-POLE (TIMERS) [Sheet 2 of 2] GE Multilin C60 Breaker Management Relay 5-55...
Page 120
5.5 GROUPED ELEMENTS 5 SETTINGS Figure 5–20: BREAKER FAILURE 3-POLE [INITIATE] (Sheet 1 of 2) 5-56 C60 Breaker Management Relay GE Multilin...
Page 121
5 SETTINGS 5.5 GROUPED ELEMENTS Figure 5–21: BREAKER FAILURE 3-POLE [TIMERS] (Sheet 2 of 2) GE Multilin C60 Breaker Management Relay 5-57...
= Pickup Level pickup At 0% of pickup, the operating time equals the setting. UNDERVOLTAGE DELAY NOTE 20 30 80 90 100 110 % of V pickup Figure 5–22: INVERSE TIME UNDERVOLTAGE CURVES 5-58 C60 Breaker Management Relay GE Multilin...
Page 123
Source VT = Wye VCG or VCA Minimum FLEXLOGIC OPERAND SETTING PHASE UV1 PKP PHASE UV1 MODE: FLEXLOGIC OPERAND Phase to Ground Phase to Phase PHASE UV1 OP 827039A9.CDR Figure 5–23: PHASE UV1 SCHEME LOGIC GE Multilin C60 Breaker Management Relay 5-59...
Page 124
Vx Pickup AUX UV1 PKP AUX UV1 DPO SETTING SETTING AUX UV1 OP AUX UV1 MINIMUM AUX UV1 SIGNAL VOLTAGE: SOURCE: < AUX VOLT Vx Vx Minimum 827849A2.CDR Figure 5–24: AUXILIARY UNDERVOLTAGE SCHEME LOGIC 5-60 C60 Breaker Management Relay GE Multilin...
Page 125
AUX OV1 RESET Off=0 DELAY : FLEXLOGIC OPERANDS < Vx Pickup AUX OV1 OP SETTING AUX OV1 DPO AUX OV1 SIGNAL AUX OV1 PKP SOURCE: AUXILIARY VOLT (Vx) 827836A2.CDR Figure 5–25: AUXILIARY OVERVOLTAGE SCHEME LOGIC GE Multilin C60 Breaker Management Relay 5-61...
The assigned VIRTUAL OUTPUT 1 operand is used to control the ON state of a particular settings group. Figure 5–26: EXAMPLE FLEXLOGIC™ CONTROL OF A SETTINGS GROUP 5-62 C60 Breaker Management Relay GE Multilin...
SYNCHK1 MAX FREQ DIFF: This setting selects the maximum frequency difference in ‘Hz’ between the two sources. A frequency difference between the two input voltage systems below this value is within the permissible limit for synchronism. GE Multilin C60 Breaker Management Relay 5-63...
Page 128
If using a single CT/VT module with both phase voltages and an auxiliary voltage, ensure that only the auxiliary voltage is programmed in one of the Sources to be used for synchrocheck. Exception: Synchronism cannot be checked between Delta connected phase VTs and a Wye connected auxiliary voltage. 5-64 C60 Breaker Management Relay GE Multilin...
Page 129
∆Φ × 2 30° If one or both sources are de-energized, the synchrocheck programming can allow for closing of the circuit breaker using undervoltage control to by-pass the synchrocheck measurements (Dead Source function). GE Multilin C60 Breaker Management Relay 5-65...
Page 130
5.6 CONTROL ELEMENTS 5 SETTINGS Figure 5–27: SYNCHROCHECK SCHEME LOGIC 5-66 C60 Breaker Management Relay GE Multilin...
Range: FlexLogic™ operand AR RESET: MESSAGE Range: 0 to 655.35 s in steps of 0.01 AR RESET TIME: MESSAGE 60.00 s Range: FlexLogic™ operand AR BKR CLOSED: MESSAGE Range: FlexLogic™ operand AR BLOCK: MESSAGE GE Multilin C60 Breaker Management Relay 5-67...
Page 132
Scheme is permitted to operate and shot count is reset to 0 Reclose In Progress Scheme has been initiated but the reclose cycle is not finished (successful or not) Lockout Scheme is not permitted to operate until reset received 5-68 C60 Breaker Management Relay GE Multilin...
Page 133
The pause signal blocks all three dead timers. When the "pause" signal disappears the autoreclose cycle is resumed by initiating the AR 3-P DEAD TIME 2 GE Multilin C60 Breaker Management Relay 5-69...
Page 134
(there is no initiating signal and the breakers are closed) the reset timer will time out, returning the scheme to the reset state, with the shot counter set to 0, making it ready for a new reclose cycle. 5-70 C60 Breaker Management Relay GE Multilin...
Page 135
During a reclose cycle, "Extended Zone 1" goes to 0 as soon as the first CLOSE BREAKER signal is issued (AR SHOT COUNT > 0) and remains 0 until the recloser goes back to Reset. GE Multilin C60 Breaker Management Relay 5-71...
Page 136
AR BKR CLOSED: This setting selects an operand that indicates that the breaker(s) are closed at the end of the reset time and the scheme can reset. 5-72 C60 Breaker Management Relay GE Multilin...
Page 137
This setting will prevent the autoreclose scheme from transferring the close signal to the second breaker unless a successful reclose of the first breaker occurs. GE Multilin C60 Breaker Management Relay 5-73...
Page 138
(breaker No. 2 for sequence 1-2 and breaker No. 1 for sequence 2-1) must be configured to trip NOTE three-pole for any type of fault Figure 5–28: SINGLE-POLE AUTORECLOSE LOGIC (SHEET 1 OF 3) 5-74 C60 Breaker Management Relay GE Multilin...
Page 139
5 SETTINGS 5.6 CONTROL ELEMENTS Figure 5–29: SINGLE-POLE AUTORECLOSE LOGIC (SHEET 2 OF 3) GE Multilin C60 Breaker Management Relay 5-75...
Page 140
(To sheet 1) FLEXLOGIC OPERAND BREAKER 1 ONE P OPEN FLEXLOGIC OPERAND BREAKER 2 ONE P OPEN BKR ONE POLE OPEN (To sheet 1) 827833A8.CDR Figure 5–30: SINGLE-POLE AUTORECLOSE LOGIC (SHEET 3 OF 3) 5-76 C60 Breaker Management Relay GE Multilin...
Page 141
5 SETTINGS 5.6 CONTROL ELEMENTS Figure 5–31: EXAMPLE RECLOSING SEQUENCE GE Multilin C60 Breaker Management Relay 5-77...
DIGITAL ELEMENT 01 INPUT: DIG ELEM 01 PKP Off = 0 DIG ELEM 01 OP INPUT = 1 SETTING DIGITAL ELEMENT 01 BLOCK: 827042A1.VSD Off = 0 Figure 5–32: DIGITAL ELEMENT SCHEME LOGIC 5-78 C60 Breaker Management Relay GE Multilin...
Page 143
DIG ELEM 1 INPUT: MESSAGE Cont Op 1 VOff DIG ELEM 1 PICKUP MESSAGE DELAY: 0.200 s DIG ELEM 1 RESET MESSAGE DELAY: 0.100 s DIG ELEM 1 BLOCK: MESSAGE Cont Ip 1 Off GE Multilin C60 Breaker Management Relay 5-79...
Page 144
RESISTANCE POWER SUPPLY (V DC) (OHMS) (WATTS) I = Current Monitor 1000 5000 V = Voltage Monitor 10000 25000 By-pass 25000 Resistor 50000 Trip Coil 827074A1.vsd DC– Figure 5–34: TRIP CIRCUIT EXAMPLE 2 5-80 C60 Breaker Management Relay GE Multilin...
Selects the FlexLogic™ operand for decrementing the counter. If an enabled DOWN input is received when the accumu- lated value is at the limit of –2,147,483,648 counts, the counter will rollover to +2,147,483,647. GE Multilin C60 Breaker Management Relay 5-81...
Page 146
COUNTER 1 RESET: COUNTER 1 FROZEN: Off = 0 STORE DATE & TIME Date & Time SETTING COUNT1 FREEZE/RESET: Off = 0 827065A1.VSD SETTING COUNT1 FREEZE/COUNT: Off = 0 Figure 5–35: DIGITAL COUNTER SCHEME LOGIC 5-82 C60 Breaker Management Relay GE Multilin...
This setting is used to program the delay interval between the time the tripping sequence is initiated and the time the breaker contacts are expected to part, starting the integration of the measured current. BKR 1 ARC AMP LIMIT: Selects the threshold value above which the output operand is set. GE Multilin C60 Breaker Management Relay 5-83...
Page 148
COMMAND ACTUAL VALUE CLEAR BREAKER 1 ARCING AMPS: BKR 1 ARCING AMP A NO=0 BKR 1 ARCING AMP B YES=1 BKR 1 ARCING AMP C 827071A2.CDR Figure 5–37: BREAKER ARCING CURRENT SCHEME LOGIC 5-84 C60 Breaker Management Relay GE Multilin...
The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user- settable debounce time in order for the C60 to validate the new contact state. In the figure below, the debounce time is set at 2.5 ms;...
Page 150
Event Records menu, make the following settings changes: "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. 5-86 C60 Breaker Management Relay GE Multilin...
This can be realized in the UR using the ‘Cont Op 1 IOn’ FlexLogic™ operand to seal-in the Contact Output. For example, # CONTACT OUTPUT H1 CONTACT OUTPUT H1 ID Cont Op 1 OUTPUT H1 OPERATE: MESSAGE OUTPUT H1 SEAL-IN: MESSAGE Cont Op 1 CONTACT OUTPUT H1 MESSAGE EVENTS: Enabled 5-88 C60 Breaker Management Relay GE Multilin...
The status of a remote device, where ‘Offline’ indicates ‘non-communicat- ing’, can be displayed. The GOOSE facility provides for 64 remote inputs and 32 remote outputs. GE Multilin C60 Breaker Management Relay 5-89...
For more information on GOOSE specifications, see REMOTE INPUTS/OUTPUTS OVERVIEW in the REMOTE DEVICES section. NOTE 5-90 C60 Breaker Management Relay GE Multilin...
DownedOn Sync Closing SyncClsOff SyncClsOn Mode Report mode status of local GOOSE device Normal Test 28→32 Reserved For more information on GOOSE specifications, see REMOTE INPUTS/OUTPUTS OVERVIEW in the REMOTE DEVICES section. NOTE GE Multilin C60 Breaker Management Relay 5-91...
RESET OP (PUSHBUTTON), RESET OP (COMMS) or RESET OP (OPERAND) to identify the source of the command. The setting shown above selects the operand that will create the RESET OP (OPERAND) operand. 5-92 C60 Breaker Management Relay GE Multilin...
Another example would be a Watt transducer with a span from –20 to +180 MW; in this case the MIN value would be –20 and the MAX value 180. Intermediate values between the MIN and MAX are scaled linearly. GE Multilin C60 Breaker Management Relay 5-93...
This ID is also used to reference the channel as the input parameter to features designed to measure this type of parameter. Selecting the type of RTD connected to the channel configures the channel. 5-94 C60 Breaker Management Relay GE Multilin...
ON. The state of each contact output may be programmed as Disabled, Energized, De-energized, or Freeze. The Freeze option maintains the output contact in the state at which it was frozen. All contact output operations return to normal when all the settings for this feature are disabled. GE Multilin C60 Breaker Management Relay 5-95...
# SOURCE SRC 4 # SOURCE SRC 5 # SOURCE SRC 6 # SYNCHROCHECK See page 6-12. # TRACKING FREQUENCY See page 6-13. # FLEXELEMENTS See page 6-13. # TRANSDUCER I/O See page 6-13. # DCMA INPUTS GE Multilin C60 Breaker Management Relay...
Page 162
# OSCILLOGRAPHY See page 6-16. # DATA LOGGER See page 6-16. # MAINTENANCE See page 6-17. ## ACTUAL VALUES # MODEL INFORMATION See page 6-18. ## PRODUCT INFO # FIRMWARE REVISIONS See page 6-18. C60 Breaker Management Relay GE Multilin...
The state displayed will be that of the remote point unless the remote device has been established to be "Offline" in which case the value shown is the programmed default state for the remote input. GE Multilin C60 Breaker Management Relay...
The present state of up to 16 programmed Remote Devices is shown here. The message indi- ALL REMOTE DEVICES ONLINE cates whether or not all programmed Remote Devices are online. If the corresponding state is "No", then at least one required Remote Device is not online. C60 Breaker Management Relay GE Multilin...
There are 256 FlexState bits available. The second line value indicates the state of the given FlexState bit. 6.2.11 ETHERNET !" PATH: ACTUAL VALUES STATUS ETHERNET Range: Fail, OK # ETHERNET ETHERNET PRI LINK STATUS: OK Range: Fail, OK ETHERNET SEC LINK MESSAGE STATUS: OK GE Multilin C60 Breaker Management Relay...
Page 166
PF = Lag WATTS = Negative VARS = Positive PF = Lead PF = Lag PF = Lead Current UR RELAY 827239AC.CDR S=VI Generator Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS C60 Breaker Management Relay GE Multilin...
Page 167
• ABC phase rotation: • ACB phase rotation: -- - V -- - V -- - V -- - V -- - V -- - V The above equations apply to currents as well. GE Multilin C60 Breaker Management Relay...
Page 168
POWER SYSTEM FREQUENCY AND PHASE REFERENCE The example above is illustrated in the following figure. SYSTEM VOLTAGES SYMMETRICAL COMPONENTS WYE VTs DELTA VTs 827844A1.CDR Figure 6–3: ILLUSTRATION OF THE UR CONVENTION FOR SYMMETRICAL COMPONENTS C60 Breaker Management Relay GE Multilin...
0.00 Hz The Actual Values menu for SYNCHROCHECK2 is identical to that of SYNCHROCHECK1. If a Synchrocheck Function setting is set to "Disabled", the corresponding Actual Values menu item will not be displayed. 6-12 C60 Breaker Management Relay GE Multilin...
RTD INPUT xx -50 °C Actual values for each RTD input channel that is Enabled are displayed with the top line as the programmed channel "ID" and the bottom line as the value. GE Multilin C60 Breaker Management Relay 6-13...
= sought pu distance to fault, Z = positive sequence impedance of the line. The currents from the local and remote systems can be parted between their fault (F) and pre-fault load (pre) components: eqn. 2 Apre 6-14 C60 Breaker Management Relay GE Multilin...
Page 175
FAULT REPORT # SRC X 50DD OP 1 SEC DATE TIME FAULT FAULT TYPE LOCATOR FAULT LOCATION 3 _0 FAULT# RECLOSE SHOT SHOT # FROM AUTO RECLOSURE 827094A1.CDR Figure 6–5: FAULT LOCATOR SCHEME GE Multilin C60 Breaker Management Relay 6-15...
It counts up at the defined sampling rate. If Data Logger channels are defined, then both values are static. Refer to the !" menu for clearing data logger records. COMMANDS CLEAR RECORDS 6-16 C60 Breaker Management Relay GE Multilin...
There is an identical Actual Value menu for each of the 2 Breakers. The values are in units of kA BKR 1 ARCING AMP cycles. Refer to the !" menu for clearing breaker arcing current records. COMMANDS CLEAR RECORDS GE Multilin C60 Breaker Management Relay 6-17...
BOOT DATE: MESSAGE Date and time when the boot program was built. 2000/05/11 16:41:32 The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been installed. 6-18 C60 Breaker Management Relay GE Multilin...
COMMANDS CLEAR RECORDS Range: No, Yes ## COMMANDS CLEAR EVENT RECORDS? ## CLEAR RECORDS Range: No, Yes CLEAR OSCILLOGRAPHY? Range: No, Yes CLEAR DATA LOGGER? Range: No, Yes CLEAR BREAKER 1 ARCING AMPS? No GE Multilin C60 Breaker Management Relay...
Page 180
If an update occurs, the following message is shown. UPDATING... PLEASE WAIT There is no impact if there have been no changes to the hardware modules. When an update does not occur, the following message will be shown. ORDER CODE NOT UPDATED C60 Breaker Management Relay GE Multilin...
• all other output relays are de-energized and are prevented from further operation • the faceplate IN SERVICE indicator is turned off • a RELAY OUT OF SERVICE event is recorded GE Multilin C60 Breaker Management Relay...
Page 182
One or more GOOSE devices are Event driven. Occurs when a Check GOOSE setup OFFLINE not responding device programmed to receive GOOSE messages stops receiving message. Time is 1 to 60 sec. depending on GOOSE protocol packets. C60 Breaker Management Relay GE Multilin...
DNP Unsol Response Timeout Trigger Position DNP Unsol Response Max Retries Trigger Source Unsol Response Dest Address AC Input Waveforms User Map for DNP Analogs FAULT REPORT Number of Sources in Analog List Fault Report Source GE Multilin C60 Breaker Management Relay...
Digital Channel 39 Channel 3 Digital Channel 40 Channel 4 Digital Channel 41 Channel 5 Digital Channel 42 Channel 6 Digital Channel 43 Channel 7 Channel 8 Digital Channel 44 Digital Channel 45 Channel 9 C60 Breaker Management Relay GE Multilin...
Page 185
LED 14 Operand LED 37 Type LED 14 Type LED 38 Operand LED 15 Operand LED 38 Type LED 15 Type LED 39 Operand LED 16 Operand LED 39 Type LED 16 Type LED 40 Operand GE Multilin C60 Breaker Management Relay...
Page 186
Flex State Parameter 72 Flex State Parameter 26 Flex State Parameter 73 Flex State Parameter 27 Flex State Parameter 74 Flex State Parameter 28 Flex State Parameter 75 Flex State Parameter 29 Flex State Parameter 76 C60 Breaker Management Relay GE Multilin...
Page 187
Flex State Parameter 166 Flex State Parameter 120 Flex State Parameter 167 Flex State Parameter 121 Flex State Parameter 168 Flex State Parameter 122 Flex State Parameter 169 Flex State Parameter 123 Flex State Parameter 170 GE Multilin C60 Breaker Management Relay...
Page 188
Disp 1 Item 1 Flex State Parameter 214 Disp 1 Item 2 Flex State Parameter 215 Disp 1 Item 3 Disp 1 Item 4 Flex State Parameter 216 Flex State Parameter 217 Disp 1 Item 5 C60 Breaker Management Relay GE Multilin...
Page 189
Disp 6 Item 4 Disp 6 Item 5 USER DISPLAY 7 Disp 7 Top Line Disp 7 Bottom Line Disp 7 Item 1 Disp 7 Item 2 Disp 7 Item 3 Disp 7 Item 4 GE Multilin C60 Breaker Management Relay...
BF2 Use Amp Supv Phase UV2 Signal Source BF2 Use Seal-In Phase UV2 Mode BF2 3-Pole Initiate Phase UV2 Pickup BF2 Block Phase UV2 Curve BF2 Ph Amp Supv Pickup Phase UV2 Delay GE Multilin C60 Breaker Management Relay 8-19...
Page 202
Aux UV1 Events AUXILIARY OVERVOLTAGE 1 Aux OV1 Function Aux OV1 Signal Source Aux OV1 Pickup Aux OV1 Pickup Delay Aux OV1 Reset Delay Aux OV1 Block Aux OV1 Target Aux OV1 Events 8-20 C60 Breaker Management Relay GE Multilin...
Digital Element 2 Function Synchk2 Target Dig Elem 2 Name Synchk2 Events Dig Elem 2 Input AUTORECLOSE Dig Elem 2 Pickup Delay AR Function Dig Elem 2 Reset Delay AR Mode Dig Elem 2 Block GE Multilin C60 Breaker Management Relay 8-21...
Page 204
Dig Elem 12 Block Dig Elem 7 Reset Delay Digital Element 12 Target Dig Elem 7 Block Digital Element 12 Events Digital Element 7 Target DIGITAL ELEMENT 13 Digital Element 7 Events Digital Element 13 Function 8-22 C60 Breaker Management Relay GE Multilin...
Page 205
Counter 5 Name Counter 1 Block Counter 5 Units Counter 1 Set to Preset Counter 5 Preset Counter 1 Reset Counter 5 Compare Counter 1 Freeze/Reset Counter 5 Up Counter 1 Freeze/Count Counter 5 Down GE Multilin C60 Breaker Management Relay 8-23...
Page 206
Counter 8 Down Counter 8 Block Counter 8 Set to Preset Counter 8 Reset Counter 8 Freeze/Reset Counter 8 Freeze/Count BREAKER 1 ARCING CURRENT Bkr 1 Arc Amp Function Bkr 1 Arc Amp Source 8-24 C60 Breaker Management Relay GE Multilin...
Page 220
FlexElement 13 Actual 39451 FlexElement 14 OpSig FlexElement 14 Actual 39453 FlexElement 15 OpSig FlexElement 15 Actual 39455 FlexElement 16 OpSig FlexElement 16 Actual 40960 Communications Group Communications Group 40971 Active Setting Group Current Setting Group C60 Breaker Management Relay GE Multilin...
1 to 254; see Chapter 5 for details. Only the addressed slave will respond to a packet that starts with its address. Note that the faceplate port is an exception to this rule; it will act on a message containing any slave address. GE Multilin C60 Breaker Management Relay...
Page 222
19200 bps, and 300 µs at 115200 bps). Consequently, the transmitting device must not allow gaps between bytes longer than this interval. Once the dead time has expired without a new byte transmission, all slaves start listening for a new packet from the master except for the addressed slave. C60 Breaker Management Relay GE Multilin...
Yes: G (+) A --> A and continue. Is j = 8? No: go to 5 Yes: continue i + 1 --> i Is i = N? No: go to 3 Yes: continue A --> CRC GE Multilin C60 Breaker Management Relay...
DATA #1 - lo NUMBER OF REGISTERS - lo DATA #2 - hi CRC - lo DATA #2 - lo CRC - hi DATA #3 - hi DATA #3 - lo CRC - lo CRC - hi C60 Breaker Management Relay GE Multilin...
DATA STARTING ADDRESS - lo DATA STARTING ADDRESS - lo DATA - hi DATA - hi DATA - lo DATA - lo CRC - lo CRC - lo CRC - hi CRC - hi GE Multilin C60 Breaker Management Relay...
PACKET FORMAT EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte C60 Breaker Management Relay GE Multilin...
To read binary COMTRADE oscillography files, read the following filenames: • OSCnnnn.CFG • OSCnnn.DAT Replace "nnn" with the desired oscillography trigger number. For ASCII format, use the following file names • OSCAnnnn.CFG • OSCAnnn.DAT GE Multilin C60 Breaker Management Relay...
COMMAND or SETTING password security access is restricted to the particular port or particular TCP/IP connection on which the entry was made. Passwords must be entered when accessing the relay through other ports or connections, and the passwords must be re-entered after disconnecting and re-connecting on TCP/IP. C60 Breaker Management Relay GE Multilin...
...Repeated for module number 24 0418 ...Repeated for module number 25 0419 ...Repeated for module number 26 041A ...Repeated for module number 27 041B ...Repeated for module number 28 041C ...Repeated for module number 29 GE Multilin C60 Breaker Management Relay...
Page 230
...Repeated for module number 4 1561 ...Repeated for module number 5 1565 ...Repeated for module number 6 1569 ...Repeated for module number 7 156D ...Repeated for module number 8 1571 ...Repeated for module number 9 B-10 C60 Breaker Management Relay GE Multilin...
Page 231
-359.9 to 0 ° F002 1A09 Phase BG Voltage Magnitude 0 to 999999.999 0.001 F060 1A0B Phase BG Voltage Angle -359.9 to 0 ° F002 1A0C Phase CG Voltage Magnitude 0 to 999999.999 0.001 F060 GE Multilin C60 Breaker Management Relay B-11...
Page 232
1C1B Phase C Power Factor -0.999 to 1 0.001 F013 1C1C Reserved (4 items) F001 1C20 ...Repeated for module number 2 1C40 ...Repeated for module number 3 1C60 ...Repeated for module number 4 B-12 C60 Breaker Management Relay GE Multilin...
Page 233
Reserved (8 items) F001 1EA0 ...Repeated for module number 2 1EC0 ...Repeated for module number 3 1EE0 ...Repeated for module number 4 1F00 ...Repeated for module number 5 1F20 ...Repeated for module number 6 GE Multilin C60 Breaker Management Relay B-13...
Page 234
Number Of Fault Reports 0 to 65535 F001 Fault Reports (Read Only Non-Volatile) (10 modules) 3030 Fault Time 0 to 4294967295 F050 3032 ...Repeated for module number 2 3034 ...Repeated for module number 3 B-14 C60 Breaker Management Relay GE Multilin...
Page 235
...Repeated for module number 4 34F4 ...Repeated for module number 5 34F5 ...Repeated for module number 6 34F6 ...Repeated for module number 7 34F7 ...Repeated for module number 8 34F8 ...Repeated for module number 9 GE Multilin C60 Breaker Management Relay B-15...
Page 236
Passwords (Read Only) 4010 Command Password Status 0 to 1 F102 0 (Disabled) 4011 Setting Password Status 0 to 1 F102 0 (Disabled) Preferences (Read/Write Setting) 4050 Flash Message Time 0.5 to 10 F001 B-16 C60 Breaker Management Relay GE Multilin...
Page 237
UCA Communications Reserved (16 items) 0 to 1 F001 40E0 TCP Port Number for the IEC 60870-5-104 Protocol 1 to 65535 F001 2404 40E1 IEC 60870-5-104 Protocol Function 0 to 1 F102 0 (Disabled) GE Multilin C60 Breaker Management Relay B-17...
Page 238
...Repeated for module number 10 4294 ...Repeated for module number 11 4296 ...Repeated for module number 12 4298 ...Repeated for module number 13 429A ...Repeated for module number 14 429C ...Repeated for module number 15 B-18 C60 Breaker Management Relay GE Multilin...
Page 239
F060 4504 Auxiliary VT Connection 0 to 6 F166 1 (Vag) 4505 Auxiliary VT Secondary 50 to 240 F001 4506 Auxiliary VT Ratio 1 to 24000 F060 4508 ...Repeated for module number 2 GE Multilin C60 Breaker Management Relay B-19...
Page 240
Synchrocheck Dead Source Select 0 to 5 F176 1 (LV1 and DV2) 4788 Synchrocheck Dead V1 Max Volt 0 to 1.25 0.01 F001 4789 Synchrocheck Dead V2 Max Volt 0 to 1.25 0.01 F001 B-20 C60 Breaker Management Relay GE Multilin...
Page 241
...Repeated for module number 22 58B0 ...Repeated for module number 23 58B8 ...Repeated for module number 24 58C0 ...Repeated for module number 25 58C8 ...Repeated for module number 26 58D0 ...Repeated for module number 27 GE Multilin C60 Breaker Management Relay B-21...
Page 242
0 to 1 F111 0 (Definite Time) 7004 Phase UV1 Delay 0 to 600 0.01 F001 7005 Phase UV1 Minimum Voltage 0 to 3 0.001 F001 7006 Phase UV1 Block 0 to 65535 F300 B-22 C60 Breaker Management Relay GE Multilin...
Page 243
7300 DCMA Inputs x Function 0 to 1 F102 0 (Disabled) 7301 DCMA Inputs x ID F205 "DCMA Ip 1 " 7307 DCMA Inputs x Reserved 1 (4 items) 0 to 65535 F001 GE Multilin C60 Breaker Management Relay B-23...
Page 244
...Repeated for module number 16 7640 ...Repeated for module number 17 7650 ...Repeated for module number 18 7660 ...Repeated for module number 19 7670 ...Repeated for module number 20 7680 ...Repeated for module number 21 B-24 C60 Breaker Management Relay GE Multilin...
Page 245
0.001 F001 9011 FlexElement Block 0 to 65535 F300 9012 FlexElement Target 0 to 2 F109 0 (Self-reset) 9013 FlexElement Events 0 to 1 F102 0 (Disabled) 9014 ...Repeated for module number 2 GE Multilin C60 Breaker Management Relay B-25...
Page 246
0 (Disabled) B01D Digital Element x Reserved (3 items) F001 B020 ...Repeated for module number 2 B040 ...Repeated for module number 3 B060 ...Repeated for module number 4 B080 ...Repeated for module number 5 B-26 C60 Breaker Management Relay GE Multilin...
Page 247
...Repeated for module number 13 C068 ...Repeated for module number 14 C070 ...Repeated for module number 15 C078 ...Repeated for module number 16 C080 ...Repeated for module number 17 C088 ...Repeated for module number 18 GE Multilin C60 Breaker Management Relay B-27...
Page 248
...Repeated for module number 67 C218 ...Repeated for module number 68 C220 ...Repeated for module number 69 C228 ...Repeated for module number 70 C230 ...Repeated for module number 71 C238 ...Repeated for module number 72 B-28 C60 Breaker Management Relay GE Multilin...
Page 249
...Repeated for module number 14 C770 ...Repeated for module number 15 C780 ...Repeated for module number 16 C790 ...Repeated for module number 17 C7A0 ...Repeated for module number 18 C7B0 ...Repeated for module number 19 GE Multilin C60 Breaker Management Relay B-29...
Page 250
...Repeated for module number 33 CEA0 ...Repeated for module number 34 CEB0 ...Repeated for module number 35 CEC0 ...Repeated for module number 36 CED0 ...Repeated for module number 37 CEE0 ...Repeated for module number 38 B-30 C60 Breaker Management Relay GE Multilin...
Page 251
...Repeated for module number 15 D380 ...Repeated for module number 16 D390 ...Repeated for module number 17 D3A0 ...Repeated for module number 18 D3B0 ...Repeated for module number 19 D3C0 ...Repeated for module number 20 GE Multilin C60 Breaker Management Relay B-31...
Page 252
0 to 3 F131 0 (Disabled) Remote Devices (Read/Write Setting) (16 modules) E000 Remote Device x ID F202 "Remote Device 1 " E00A ...Repeated for module number 2 E014 ...Repeated for module number 3 B-32 C60 Breaker Management Relay GE Multilin...
Page 253
0 to 65535 F300 E601 Remote Output DNA x Events 0 to 1 F102 0 (Disabled) E602 Remote Output DNA x Reserved (2 items) 0 to 1 F001 E604 ...Repeated for module number 2 GE Multilin C60 Breaker Management Relay B-33...
Page 254
...Repeated for module number 16 E6C0 ...Repeated for module number 17 E6C4 ...Repeated for module number 18 E6C8 ...Repeated for module number 19 E6CC ...Repeated for module number 20 E6D0 ...Repeated for module number 21 B-34 C60 Breaker Management Relay GE Multilin...
Page 255
-4096 to 4095 F002 F0A7 Transducer Channel to Calibrate Value -1.1 to 366.5 0.001 F004 F0A9 Transducer Channel to Calibrate Gain 0.8 to 1.2 0.0001 F060 F0AB Transducer Calibration Date 0 to 4294967295 F050 GE Multilin C60 Breaker Management Relay B-35...
Page 256
0.001 F001 FC33 Auxiliary OV X Pickup Delay 0 to 600 0.01 F001 FC34 Auxiliary OV X Reset Delay 0 to 600 0.01 F001 FC35 Auxiliary OV X Block 0 to 65535 F300 B-36 C60 Breaker Management Relay GE Multilin...
Page 257
Auxiliary UV X Events 0 to 1 F102 0 (Disabled) FC69 Auxiliary UV X Reserved (7 items) 0 to 65535 F001 FC70 ...Repeated for module number 2 FC80 ...Repeated for module number 3 GE Multilin C60 Breaker Management Relay B-37...
Page 262
POWER ON SRAM DATA ERROR POWER OFF PROGRAM MEMORY RELAY IN SERVICE WATCHDOG ERROR RELAY OUT OF SERVICE LOW ON MEMORY WATCHDOG RESET REMOTE DEVICE OFF OSCILLOGRAPHY CLEAR ANY MINOR ERROR REBOOT COMMAND B-42 C60 Breaker Management Relay GE Multilin...
Page 264
0 = A, 1 = B, 2 = C 0 = A, 1 = B, 2 = C, 3 = G F186 ENUMERATION MEASUREMENT MODE 0 = Phase to Ground, 1 = Phase to Phase B-44 C60 Breaker Management Relay GE Multilin...
Page 265
Contact Inputs 81 to 96 F200 Contact Outputs 1 to 16 TEXT40 40 CHARACTER ASCII TEXT Contact Outputs 17 to 32 20 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB Contact Outputs 33 to 48 GE Multilin C60 Breaker Management Relay B-45...
Page 266
IDs. The operate bit for element ID [6] VIRTUAL OUTPUTS (1-64) X is bit [X mod 16] in register [X/16]. [10] CONTACT OUTPUTS VOLTAGE DETECTED (1-64) [11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1-64) B-46 C60 Breaker Management Relay GE Multilin...
Page 267
Password types for display in password prompts 0 = LEVEL, 1 = DELTA bitmask password type MASTER F518 ENUMERATION FlexElement Units SETTING COMMAND 0 = Milliseconds, 1 = Seconds, 2 = Minutes FACTORY GE Multilin C60 Breaker Management Relay B-47...
Page 268
B.3 MEMORY MAPPING APPENDIX B bitmask Setting Type MMI_SETTING_TYPE ENUMERATION Setting Setting types for display in web pages Command bitmask Setting Type Factory Setting Unrestricted Setting Master-accessed Setting B-48 C60 Breaker Management Relay GE Multilin...
PDIS (distance) • RREC (reclosing relay) • PDOC (directional overcurrent) • RSYN (synchronizing or synchronism-check relay) • PFRQ (frequency relay) • XCBR (circuit breaker) UCA data can be accessed through the "UCADevice" MMS domain. GE Multilin C60 Breaker Management Relay...
Page 271
SBOCF SBO Configuration Description for brick BO<n> Description for each point Actual instantiation of GCTL objects is as follows: GCTL1 = Virtual Inputs (32 total points – SI1 to SI32); includes SBO functionality. NOTE GE Multilin C60 Breaker Management Relay...
Page 272
Description for brick All MMXU.MX Description of ALL included MMXU.MX BrcbMX BasRCB Controls reporting of measurements Actual instantiation of MMXU objects is as follows: 1 MMXU per Source (as determined from the ‘product order code’) NOTE C60 Breaker Management Relay GE Multilin...
Page 273
DESCRIPTION PhsARat RATIO Primary/secondary winding ratio NeutARat RATIO Primary/secondary winding ratio Description for brick Actual instantiation of ctRATO objects is as follows: 1 ctRATO per Source (as determined from the ‘product order code’). NOTE GE Multilin C60 Breaker Management Relay...
2 minutes (120000 ms). This ensures that the UR will not abort the con- nection. If other MMS data is being polled on the same connection at least once every 2 minutes, this timeout will not apply. C60 Breaker Management Relay GE Multilin...
Address Field of the Link: Balanced Transmision Not Present (Balanced Transmission Only) Unbalanced Transmission One Octet Two Octets Structured Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin C60 Breaker Management Relay...
Page 276
<18> := Packed start events of protection equipment with time tag M_EP_TB_1 <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1 Ë <20> := Packed single-point information with status change detection M_SP_NA_1 C60 Breaker Management Relay GE Multilin...
Page 277
<103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1 <104> := Test command C_TS_NA_1 Ë <105> := Reset process command C_RP_NA_1 <106> := Delay acquisition command C_CD_NA_1 Ë <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin C60 Breaker Management Relay...
Page 278
Blank boxes indicate functions or ASDU not used. • ‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 C60 Breaker Management Relay GE Multilin...
Page 281
Long pulse duration (duration determined by a system parameter in the outstation) Ë Persistent output Ë Supervision of maximum delay in command direction of commands and setpoint commands Ë Maximum allowable delay of commands and setpoint commands: 10 s GE Multilin C60 Breaker Management Relay...
Page 282
Transmission of sequences of events Transmission of sequences of recorded analog values Ë File transfer in control direction: Transparent file Ë Background scan: Background scan Ë Acquisition of transmission delay: Acquisition of transmission delay C60 Breaker Management Relay GE Multilin...
Page 283
The suitable selection of documents from RFC 2200 defined in this standard for given projects has to be chosen by the user of this standard. Ethernet 802.3 Ë Serial X.21 interface Ë Ë Other selection(s) from RFC 2200 (list below if selected) GE Multilin C60 Breaker Management Relay...
2048 Maximum Data Link Re-tries: Maximum Application Layer Re-tries: None None Ë Ë Fixed at 2 Configurable Ë Ë Ë Configurable Requires Data Link Layer Confirmation: Never Ë Always Ë Sometimes Ë Configurable Ë GE Multilin C60 Breaker Management Relay...
Page 288
FlexLogic™. The On/Off times and Count value are ignored. "Pulse Off" and "Latch Off" operations put the appropriate Virtual Input into the "Off" state. "Trip" and "Close" operations both put the appropriate Virtual Input into the "On" state. C60 Breaker Management Relay GE Multilin...
Page 289
Default Object: Ë 16 Bits (Counter 8) Default Variation: 1 32 Bits (Counters 0 to 7, 9) Ë Point-by-point list attached Ë Other Value: _____ Ë Point-by-point list attached Ë Sends Multi-Fragment Responses: Ë Ë GE Multilin C60 Breaker Management Relay...
Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the UR is not restarted, but the DNP process is restarted. C60 Breaker Management Relay GE Multilin...
Page 291
Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the UR is not restarted, but the DNP process is restarted. GE Multilin C60 Breaker Management Relay...
Page 292
Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the UR is not restarted, but the DNP process is restarted. C60 Breaker Management Relay GE Multilin...
Page 293
Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the UR is not restarted, but the DNP process is restarted. GE Multilin C60 Breaker Management Relay...
Page 297
LED State 13 (PHASE A) AR 3 Element OP LED State 14 (PHASE B) AR 4 Element OP LED State 15 (PHASE C) AR 5 Element OP LED State 16 (NTL/GROUND) AR 6 Element OP BATTERY FAIL GE Multilin C60 Breaker Management Relay E-11...
Page 298
REMOTE DEVICE OFF ANY MINOR ERROR ANY MAJOR ERROR ANY SELF-TESTS IRIG-B FAILURE DSP ERROR NOT USED NO DSP INTERUPTS UNIT NOT CALIBRATED PROTOTYPE FIRMWARE FLEXLOGIC ERR TOKEN EQUIPMENT MISMATCH UNIT NOT PROGRAMMED SYSTEM EXCEPTION E-12 C60 Breaker Management Relay GE Multilin...
Digital Counter 5 Digital Counter 6 Digital Counter 7 Digital Counter 8 Oscillography Trigger Count Events Since Last Clear Note that a counter freeze command has no meaning for counters 8 and 9. E-14 C60 Breaker Management Relay GE Multilin...
SRC 1 Phase B Current RMS SRC 1 Phase C Current RMS SRC 1 Neutral Current RMS SRC 1 Phase A Current Magnitude SRC 1 Phase A Current Angle SRC 1 Phase B Current Magnitude GE Multilin C60 Breaker Management Relay E-15...
Page 302
SRC 1 Negative Sequence Voltage Magnitude SRC 1 Negative Sequence Voltage Angle SRC 1 Three Phase Real Power SRC 1 Phase A Real Power SRC 1 Phase B Real Power SRC 1 Phase C Real Power E-16 C60 Breaker Management Relay GE Multilin...
Page 303
FlexElement 1 Actual FlexElement 2 Actual FlexElement 3 Actual FlexElement 4 Actual FlexElement 5 Actual FlexElement 6 Actual FlexElement 7 Actual FlexElement 8 Actual FlexElement 9 Actual FlexElement 10 Actual FlexElement 11 Actual GE Multilin C60 Breaker Management Relay E-17...
Page 304
E.3 DNP POINT LISTS APPENDIX E Table E–6: ANALOG INPUT POINTS (Sheet 4 of 4) POINT DESCRIPTION FlexElement 12 Actual FlexElement 13 Actual FlexElement 14 Actual FlexElement 15 Actual FlexElement 16 Actual Current Setting Group E-18 C60 Breaker Management Relay GE Multilin...
1601-0093-B5 2.9X 03 December 2001 URC-025 1601-0093-B8 2.9X 10 September 2004 URX-162 F.1.2 CHANGES TO C60 MANUAL Table F–2: MAJOR UPDATES FOR C60 MANUAL-B8 PAGE CHANGE DESCRIPTION (B5) Title Update Manual part number from B5 to B8 Update Updated BINARY INPUTS table Table F–3: MAJOR UPDATES FOR C60 MANUAL-B5...
Page 306
F.1 CHANGE NOTES APPENDIX F Table F–4: MAJOR UPDATES FOR C60 MANUAL-B4 PAGE (B3) CHANGE DESCRIPTION Title Update Manual part number from B3 to B4 Update Updated SINGLE LINE DIAGRAM from 813710A8 to 813710A9 Update Updated DEVICE NUMBERS AND FUNCTIONS table...
24 months from date of shipment from factory. In the event of a failure covered by warranty, GE Multilin will undertake to repair or replace the relay providing the warrantor determined that it is defective and it is returned with all transportation charges prepaid to an authorized service centre or the factory.