Chapter 3
Switch Installation
The plug-socket combination must be accessible at all times, because it serves
Warning
as the main disconnecting device.
This equipment is intended to be grounded. Ensure that the host is connected to
Warning
earth ground during normal use.
When installing or replacing the unit, the ground connection must always be
Warning
made first and disconnected last.
To prevent the switch from overheating, do not operate it in an area that
Warning
exceeds the maximum recommended ambient temperature of 113°F (45°C). To
prevent airflow restriction, allow at least 3 inches (7.6 cm) of clearance around
the ventilation openings.
Do not work on the system or connect or disconnect cables during periods of
Warning
lightning activity.
Ultimate disposal of this product should be handled according to all national
Warning
laws and regulations
If a redundant power system (RPS) is not connected to the switch, install an RPS
Warning
connector cover on the back of the switch.
78-16057-01
Catalyst 3560 Switch Hardware Installation Guide
Preparing for Installation
3-3