hit counter script

Changeover Of Operating Mode - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

D.h.w.
Changeover of system
Changeover of segment
Siemens Building Technologies
Landis & Staefa Division
2.55.1

Changeover of operating mode

Setting 0/1)
A remote telephone switch is a potential-free relay contact, e.g. in the form of a modem,
which can be switched by making a phone call plus dialing a code.
The operating modes of heating circuit and d.h.w. change when the contact connected
to terminal H1 (e.g. a remote telephone switch) closes. In that case, the LEDs in the
operating mode buttons
Whether or not d.h.w. heating can take place when the remote telephone switch is
activated depends on the following setting:
Setting 0:
D.h.w. heating is locked when changeover is activated.
Setting 1:
D.h.w. heating remains released when changeover is activated.
Effect on the system
Depending on the type of unit to which operating mode changeover in a heating system
is connected, an activation produces different changeover statuses:
Changeover of all controllers in the system (line 145 = 1)
Prerequisite:
The contact must be connected to the master controller in
segment 0
Possible address:
Effect:
All controllers in the system switch to operating mode
With setting 0, d.h.w. heating is switched off in the entire system;
with setting 1, it is released in the entire system
With all controllers, operating mode changeover with the buttons is
no longer possible
When the contact of the remote telephone switch opens, all
controllers will return to the operating mode selected last
Check
Buttons
1)
With setting 0 as selected above (d.h.w. heating locked), buttons
With setting 1 as selected above (d.h.w. heating remains released), only operating mode button
Changeover of all controllers in the same segment (line 145 = 0)
Prerequisite:
The contact must be connected to the master controller in segments 0
to 14
Possible address:
Effect:
All controllers in the same segment switch to operating mode
With setting 0, d.h.w. heating is switched off in the entire segment;
with setting 1, it is released in the entire segment
With all controllers in the same segment, operating mode
changeover with the buttons is no longer possible
When the contact of the remote telephone switch opens, all
controllers will return to the operating mode selected last
Check
Buttons
segment 1)
Basic Dokumentation RVA63.280, RVA53.280
and
will flash.
Device address 1
Segment address 0 (line 141)
or
+
flash on all controllers in the system 1)
Device address 1
Segment address 0...14 (line 141)
or
+
flash
or
+
(line 140)
and
will flash.
(line 140)
flash on all controllers in the same
will flash.
123/184
CE1P2374E
19.04.2001

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rva53.280

Table of Contents