Page 2
4400 Series Installation and Operation Manual – 64527-006...
Page 3
UNINTERRUPTIBLE POWER SYSTEM (UPS) 4400 SERIES INSTALLATION AND OPERATION MANUAL THREE PHASE – 15/20/25/30/50/80 KVA Part # 64527-006 January 2016 4400 Series Installation and Operation Manual – 64527-006...
Usage includes atomic energy control instruments, airplane or spaceship instruments, transportation instruments, traffic signal instruments, combustion control instruments, life-support equipment, all types of safety devices, etc. Unintended Usage of Toshiba products listed in this document shall be made at the customer’s own risk.
Page 5
Unless otherwise specified, the warranty period for the UPS or UPS part is 36 months from the shipment date (see Toshiba International Corporation bill of lading). Unless otherwise specified, the warranty period for a UPS battery or battery cabinet is 36 months from the shipment date (see Toshiba International Corporation bill of lading). JOB NUMBER MODEL NUMBER...
Page 6
) Toshiba is a registered trademark of the Toshiba Corporation. All other product or trade references appearing in this manual are registered trademarks of their respective owners. Toshiba International Corporation shall not be liable for direct, indirect, special, or consequential damages resulting from the use of the information contained within this manual.
Power Cable Access ...............29 UPS Parts Identification – 15–30kVA ..........31 UPS Parts Identification – 50kVA ............33 UPS Parts Identification – 80kVA ............35 UPS Wiring ....................37 Wiring Safety .................37 One-Line Diagram .................38 Multiple Battery Cabinets ...............41 4400 Series Installation and Operation Manual – 64527-006...
Page 8
12.12 Toolbar: QUICK VIEW ON/OFF ...........75 12.13 Tab: Main – RUN/STOP ...............76 12.14 Tab: Monitor .................78 12.15 Tab: Setup ..................80 12.16 Setup: Calibrating the Touchscreen ..........82 12.17 Tab: Record .................83 12.18 Tab: Help ..................84 4400 Series Installation and Operation Manual – 64527-006...
Page 9
D.5 – Cable Size for 3-Phase/3-Wire + G ..........115 D.6 – Battery Cabling................115 D.7 – Input Transformer Current for Given Input Voltage ......115 D.8 – Output Transformer Current for Given Output Voltage....116 4400 Series Installation and Operation Manual – 64527-006...
Page 10
This page intentionally left blank 4400 Series Installation and Operation Manual – 64527-006...
• Safety Precautions • Installation Precautions Read this 4400 Series Operation Manual for important instructions on operating the UPS. This manual and the accompanying drawings should be considered a permanent part of the equipment and should be readily available for reference and review.
Ground Symbol indicates the location of the equipment grounding conductor. Electrical – Voltage & Shock Hazard Symbol indicates parts inside may cause electric shock. Explosion Hazard Symbol indicates parts may explode. 4400 Series Installation and Operation Manual – 64527-006...
Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves, hard hats, safety glasses, face shields, flash clothing, etc., in accordance with established safety practices. • Be trained in rendering first aid. For further information on workplace safety visit www.osha.gov. 4400 Series Installation and Operation Manual – 64527-006...
Factory Authorized Personnel Factory authorized personnel have been factory trained and certified to install, service, and repair the UPS. Contact the Toshiba Customer Support Center for assistance in locating the factory 4400-authorized personnel nearest you. Important Safety Instructions The following contains important instructions that should be followed during the installation, operation, and maintenance of the 4400 Series UPS.
(computer, personal equipment, office equipment, measuring equipment, industrial robotics, domestic appliances, etc.). These Toshiba products are neither intended nor warranted for use in equipment that, if a malfunction or failure occurs, may result in loss of human life or bodily injury (collectively referred to as “Unintended Usage”).
UPS to move it. Always use a crane, forklift, or pallet jack for transporting and positioning the UPS. Pushing/pulling on the sides of the unit to move it may result in damage to the UPS. 4400 Series Installation and Operation Manual – 64527-006...
Packing materials should be disposed by the appropriate means. • Immediately report any abnormalities to Toshiba Customer Support Center or an authorized representative. • Retain the packing rails for offloading the UPS from the shipping pallet, and for final UPS installation.
Page 18
SLOWLY roll the unit down the ramp. 8. Save the loading rails for anchoring of the UPS. See Section 8.3. FIGURE 4.1 – UNSHIPPING 15-30KVA UPS 4400 Series Installation and Operation Manual – 64527-006...
6. SLOWLY roll the unit down the ramp. 7. Save the loading rails for anchoring the UPS. See Section 8.3. FIGURE 4.2 – UNSHIPPING 50KVA UPS 4400 Series Installation and Operation Manual – 64527-006...
4. Put down the UPS and remove the pallet. 5. Use a forklift or pallet jack to transport the UPS to it’s installation location. See Section 8.3. FIGURE 4.3 – UNSHIPPING 80KVA UPS 4400 Series Installation and Operation Manual – 64527-006...
During periods of non-use, the following guidelines are recommended for storage. These instructions apply to installations that have already been through initial Start-up with Toshiba Service. For installations that have not been through initial startup, arrange the power up with Toshiba Service. Storage Preparation 1) If the UPS has a battery backup, power up the UPS and allow it to operate with no load for 24 hours to fully charge the batteries.
Make sure all the warning labels are installed in the appropriate locations. Allow equipment to cool before TEXT AREA BACKGROUND COLOR: ANSI WHITE If a label is missing or illegible, contact Toshiba Customer Support Center or an TEXT AREA TEXT COLOR: ANSI BLACK servicing.
Page 23
WLM 11-13 FULL D A N G E R D A N G E R THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF TOSHIBA INTERNATIONAL DC VOLTAGE THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF TOSHIBA INTERNATIONAL DC VOLTAGE-FR CORPORATION AND SHALL NOT BE REPRODUCED, USED, OR DISCLOSED...
Page 24
JEE 10-14-13 WLM 11-13 WLM 11-13 OIL SOLVENTS and rating of fuse. THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF TOSHIBA INTERNATIONAL THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF TOSHIBA INTERNATIONAL PLP-FRENCH ALL MATERIALS USED MUST ALL MATERIALS USED MUST PN 40830...
Page 25
Their location in the 15-30kVA UPS cabinet is shown in Figures 5.2 – 5.3, for the 50kVA cabinet in Figures 5.4 – 5.5, and for the 80kVA cabinet in Figures 5.6 – 5.7. FIGURE 5.2 – 15-30KVA CABINET EXTERNAL FIGURE 5.3 – 15-30KVA CABINET INTERNAL WARNING LABEL LOCATIONS WARNING LABEL LOCATIONS 4400 Series Installation and Operation Manual – 64527-006...
Less than or equal to 0.002 PPM Hydrochloric acid mist (HCl) Less than or equal to 0.1 mg/m Operating Precautions Initial startup/commissioning of the UPS should be performed by factory authorized personnel. 4400 Series Installation and Operation Manual – 64527-006...
Page 29
UPS. 4. If using the UPS to provide power to motors that require high starting current or with motors that require a long starting time, call Toshiba support for guidance in over sizing the UPS for lock rotor current.
3. The maximum ambient operating temperature at 1.0 PF is 86 °F (30 °C) , and at 0.9 PF 104 °F (40 °C). 4. Only factory authorized personnel should service the UPS. Contact Toshiba for the nearest authorized service center.
UPS to move it. Always use a crane, forklift, or pallet jack for transporting and positioning the UPS. Pushing/pulling on the sides of the unit to move it may result in damage to the UPS. See Figure 4.1 Exterior Handling label. 4400 Series Installation and Operation Manual – 64527-006...
Page 32
Electrical shock, injury or UPS failure may occur if non-authorized technicians attempt to modify or relocate the UPS. Please contact Toshiba Customer Support Center if you plan to move or make modifications to the UPS 4400 Series Installation and Operation Manual – 64527-006...
Page 33
3. Always ground the unit to reduce the potential for electrical shock and to help reduce electrical noise. 4. A separate ground cable should be run inside the conduit with the input power, output power, and control circuits. 4400 Series Installation and Operation Manual – 64527-006...
Do not remove the fan covers until UPS start up. The fan covers should be removed by factory authorized personnel. Packing materials should be disposed by the appropriate means. • Immediately report any abnormalities to Toshiba Customer Support Center or an authorized representative. UPS Clearance Maintain the indicated clearance during installation.
Page 35
Top 16 in (406 mm) Front 36 in (900 mm) Side Clearance Back Clearance 15-80kVA: 0 in (0 mm) 15-80kVA: 0 in (0 mm) FIGURE 8.2 CLEARANCE FOR SEISMIC INSTALLATIONS 4400 Series Installation and Operation Manual – 64527-006...
UPS Anchorage All 4400 Series models, except the 80 kVA, come with casters and leveling feet. The 80kVA model comes with Angle Bracket skids. The leveling feet allow the 15-50kVA models to be rolled into place, then the leveling feet extended to remove weight from the casters to ensure the UPS remains stationary.
Feet Leveling Feet 20.12 in (511 mm) 32.1 in (816 mm) FIGURE 8.4 – FOOTPRINT FOR 15-30 FIGURE 8.5 FOOTPRINT FOR 50 KVA USING KVA USING LOAD LEVELING FEET LOAD LEVELING FEET 4400 Series Installation and Operation Manual – 64527-006...
2.0 in (51 mm) Angle Bracket Skids FRONT 80kVA ANCHORAGE SPACING Back 4 x 0.703 in Dia. (17.9 mm) Front 27.1 in (689 mm) FIGURE 8.6 ANCHORAGE HOLE LOCATIONS – 80kVA UNITS (Standard) 4400 Series Installation and Operation Manual – 64527-006...
*NOTE: Although the entire width of the top and bottom main conduit landing plates can be used for cable access, using the far right and left sides of the plates will make it easier to remove the UPS deadfront panel(s) for servicing and battery replacement. 4400 Series Installation and Operation Manual – 64527-006...
Page 40
Left and Right Side Conduit Landing Plate Cable Access Conduit Cable Access Conduit Landing Plate Landing Plate NOTE: See Appendix A – Dimensional Drawings for Conduit Landing Plate dimensions FIGURE 8.7 – CONDUIT LANDING LOCATIONS 4400 Series Installation and Operation Manual – 64527-006...
MCCB1 – Primary Input Cir- cuit Breaker MCCB2 Secondary Input Cir- cuit Breaker (on Dual Input) (Optional) Air filter PCB 9 – Display Control Board RemotEye Control Board – PCB-9B RS-232C Plug Dry Contact Plug 4400 Series Installation and Operation Manual – 64527-006...
Page 42
Input Power Lugs TB3 – Terminals for Battery Cabi- net Breaker Shunt Trip and Aux. Ground Bus Shunt Trip DC Power Supply Bottom Cable Access Port Side Cable Access Ports Top Cable Access Port 4400 Series Installation and Operation Manual – 64527-006...
MCCB1 – Primary Input Circuit Breaker MCCB2 Secondary Input Circuit Breaker (Dual Input) (Optional) Air filter PCB 9 – Display Control Board RemotEye Control Board – PCB-9B RS-232 Plug Dry Contact Connector Plug 4400 Series Installation and Operation Manual – 64527-006...
Page 44
TB3 – Terminals for Battery Cabinet Breaker Shunt Trip and Aux. Ground Bus Shunt Trip DC Power Supply 28 29 Bottom Cable Access Port Side Cable Access Ports Top Cable Access Port 4400 Series Installation and Operation Manual – 64527-006...
MCCB1 – Primary Input Circuit Breaker MCCB2 Secondary Input Circuit Breaker (Dual Input) (Optional) Air filter PCB 9 – Display Control Board RemotEye Control Board – PCB-9B RS-232 Plug Dry Contact Plug 4400 Series Installation and Operation Manual – 64527-006...
Page 46
Power Box Lugs TB3 – Terminals for Battery Cabinet Breaker Shunt Trip and Aux. Ground Bus Shunt Trip DC Power Supply Bottom Cable Access Port Side Cable Access Ports Top Cable Access Port 4400 Series Installation and Operation Manual – 64527-006...
NOTICE Follow the torque criteria for tightening screws. Loose connections may cause fire due to heating. See Chapter 9 – UPS Wiring 4400 Series Installation and Operation Manual – 64527-006...
AC Input 3Φ 3W 3Φ 3W MCCB or 3Φ 4W or 3Φ 4W Input Output AC/DC DC/AC Contactor Contactor Converter Inverter DC/DC Converter Ground Wire FIGURE 9.2 – 4400 DUAL INPUT ONE-LINE DIAGRAM 4400 Series Installation and Operation Manual – 64527-006...
Page 49
4400 Series Installation and Operation Manual – 64527-006...
Page 50
3Φ/4W DC/DC Converter 3Φ/3W or 4W 208/120V 6. 4400 WITH DUAL INPUT TRANSFORMERS (15-50KVA) FIGURE 9.4 – ONE LINE DIAGRAMS OF POSSIBLE 4400 CONFIGURATIONS (NOT INCLUDING MATCHING EXTERNAL BATTERY OR AUXILIARY CABINETS) 4400 Series Installation and Operation Manual – 64527-006...
One battery string. (Consult factory if using more than one battery string.) Size neutral cable appropriate to actual load type: balanced, unbalanced, non-linear. The terminal blocks for the 15-30 kVA UPS are shown in Figure 9.4. 4400 Series Installation and Operation Manual – 64527-006...
Page 52
Use these values to determine the correct power cable size per the National Electrical Code (Ref. Table 310.16.) Lug tightening torque is the same as given in Tables 9.1 thru 9.3. 4400 Series Installation and Operation Manual – 64527-006...
Page 53
TB 3 See Section 9.7 for Control Wiring Details. TB 1 – GROUND LUG EARTH GROUND BUS TB 4 FIGURE 9.5 – 15–30KVA POWER CABLING LUGS 4400 Series Installation and Operation Manual – 64527-006...
Page 54
GROUND F - GROUND LUGS TB 3 TB 4 See Section 9.7 for Control Wiring Details. SECONDARY INPUT/ BYPASS TB 1 – BATTERY INPUT OUTPUT FIGURE 9.6 – 50KVA POWER CABLING LUGS 4400 Series Installation and Operation Manual – 64527-006...
Page 55
TB 3 See Section 9.7 for Control Wiring Details. GROUND & EARTH GROUND BUS TB 1 – – INPUT SECONDARY BATTERY OUTPUT INPUT/ BYPASS FIGURE 9.7 – 80KVA POWER CABLING LUGS 4400 Series Installation and Operation Manual – 64527-006...
1/2 in bolts. Ground wire must have a crimp terminal with a corresponding diameter bolt hole. Connect the crimp terminal and ground bus together using the appropriate diameter bolt. 4400 Series Installation and Operation Manual – 64527-006...
If the computer is started/restarted within 10 minutes after the recovery from a power failure, the power supply may be reset while the computer is restarting. FIGURE 10.2 – R 4400 Series Installation and Operation Manual – 64527-006...
DB9 female connector located to on the inside of the UPS door just to the right of the Display PCB. For reference, the pinout of the connector is illustrated below. NOTE: Use the cross cable provided by Toshiba to avoid potential communications problems. RS-232C CONNECTOR PIN ASSIGNMENT...
Output Voltage Adjustment (%) ± 5% via Touchscreen Voltage Transient Response ± 3% @ 100% Step Load Change (%) @ 100% Step Load Change 1 - Requires adjustment of factory/service adjustable parameters. 4400 Series Installation and Operation Manual – 64527-006...
Page 61
5 x 250 cfm (Max) Operating Temperature (°F/°C) 32°F – 104°F (0 °C – 40 °C) Storage Temperature (°F/°C) 14°F – 122°F (-10 °C – 50 °C) Operating Humidity (%) 5 – 95% RH 4400 Series Installation and Operation Manual – 64527-006...
Page 62
UPS must be at least the width of the front door of the UPS, or per NEC 110.34(A)(36 in./900 mm) and local requirements, whichever is greater. 2 - Approximate weights for dual-input units. Actual weights may vary depending on exact UPS configu- ration. 4400 Series Installation and Operation Manual – 64527-006...
11.2 Estimated Runtime on Internal Batteries – 15-30kVA Following are charts of the estimated runtime for the 4400 Series 15, 20, 25, and 30kVA on internal bat- teries at various loads at a 0.8 and 0.9 Power Factor. These runtimes are estimates based on new batteries operating at 76 °F. Actual runtimes may vary due to manufacturing variations, previous discharge profiles, battery age, and operating temperature.
Page 64
Voltage Total Harmonic Distor- < 3% tion (Full Linear Load) (%) Output Voltage Adjustment (%) ± 5% via Touchscreen Voltage Transient Response ± 3% @ 100% Step Load Change (%) @ 100% Step Load Change 4400 Series Installation and Operation Manual – 64527-006...
Page 65
65 Adc 87 Adc 109 Adc 130 Adc Battery Capacity Required at 15 kWB 20 kWB 25 kWB 30 kWB Full Load (kWB) Battery Test (Interval per hr) Pre-alarm Level (Vdc) 259 Vdc 4400 Series Installation and Operation Manual – 64527-006...
Page 66
Touchscreen and LED Monitoring Operator Interface (Front Panel) Touchscreen and LED Dry Contacts Included RS-232 Inrterface Optional – Intelligent Monitoring Yes – RemotEye 4 Optional – Remote Status Alarm Panel (RSAP) Additional Features 4400 Series Installation and Operation Manual – 64527-006...
Cold Start (0-100% load) (sec) 25 sec. from cold start BYPASS 208/120 V, 3P/4W +GND Voltage (V) Frequency (Hz) 50/60 Hz ±5% Bypass Overload @ 125% Load 10 min. @ 125% Load 4400 Series Installation and Operation Manual – 64527-006...
Page 69
See: Section 11.7 - Estimated Runtime on Internal Batteries Type / Rating (Ah) Yuasa NPX-150RFR, 12 V, 40 Ah Number of Batteries Replaceable Batteries Yes – Field Replaceable 1 - Requires adjustment of factory/service adjustable parameters. 4400 Series Installation and Operation Manual – 64527-006...
Page 70
UPS must be at least the width of the front door of the UPS, or per NEC 110.34(A) (36 i n./900 mm) and local requirements, whichever is greater. 3 - Approximate weights for dual-input units. Actual weights may vary depending on exact UPS configu- ration. 4400 Series Installation and Operation Manual – 64527-006...
11.7 Estimated Runtime on Internal Batteries – 50kVA Below are charts of the estimated runtime for the 4400 Series 50kVA on internal batteries at various loads at a 0.9 and 0.8 Power Factor. The 80kVA UPS is not available with internal batteries. An external battery cabinet (or equivalent) is required to provide backup power.
Bypass Overload @ 150% Load 2 min. @ 150% Load Bypass Overload @ 1000% Load 1 cycle @ 1000% Load Automatic Retransfer (Max load % for Retansfer) OUTPUT 1 - Requires adjustment of factory/service adjustable parameters. 4400 Series Installation and Operation Manual – 64527-006...
Page 73
Surge Protection Auto transfer to bypass, retransfer to inverter BATTERY GENERAL, EXTERNAL Type VRLA Batteries Voltage – Nominal (Vdc) 288 Vdc Voltage – Minimum (Vdc) 230.4 Vdc Voltage -Float (Vdc) 324 Vdc 4400 Series Installation and Operation Manual – 64527-006...
Page 74
NEMA 1 Construction Welded Steel Chassis Color Powder Coat, Dupont O’Brien Black Emergency Power Off (EPO) Control Panel Touchscreen and LED MONITORING Operator Interface (Front Panel) Touchscreen and LED Dry Contacts Included 4400 Series Installation and Operation Manual – 64527-006...
The display may not respond if the button press is too short. Touch Screen Display and Control Panel Touch Screen Display Indicators Display Reset On-Line/Fault Button Warning AC Input EPO – Emergency Power Off Switch FIGURE 12.1 – UPS DISPLAY PANEL 4400 Series Installation and Operation Manual – 64527-006...
Green – Flashing Input or Bypass voltage is over specified range. Green – OFF Input or Bypass voltage is under specified range. NOTE: On-Line/Fault LEDs – Appear Amber if Green and Red flash concurrently. 4400 Series Installation and Operation Manual – 64527-006...
Warning – Displays last warning sensed by UPS. Multiple frequent warnings of the same type may induce a fault condition. UPS Mode – Current state of UPS. FIGURE 12.5 – FOOTER BAR DISPLAY COMPONENTS 4400 Series Installation and Operation Manual – 64527-006...
Security Level (USR, ADM) Warning Buzzer Switch/Status (press for ON, press again for OFF) Touchscreen Enable/Disable Quick View Selector (press for Quick View, press again for Normal View) FIGURE 12.6 – TOUCHSCREEN CONTROLS 4400 Series Installation and Operation Manual – 64527-006...
OFF disables all touchscreen areas except the TOUCH button. Quick View On/Off Selector – Press to toggle between Normal view and Quick view. Quick view displays a simultaneous summary of the Input/Output/Bypass/DC Voltages and Currents See Section 12.12. 4400 Series Installation and Operation Manual – 64527-006...
The touchscreen can be turned OFF (locked) by pressing the TOUCH ON/OFF button. With TOUCH OFF, only the TOUCH button is active, the rest of the display will not respond to touch. 4400 Series Installation and Operation Manual – 64527-006...
Amps (A), or as a % of rated current (%). The highlighted icon indicates the current display mode. Displays DC Bus voltage, Battery voltage, and Battery discharge current. FIGURE 12-9 QUICK VIEW DISPLAY 4400 Series Installation and Operation Manual – 64527-006...
Press Run: UPS switches to On-Line mode, label changes to STOP. Press STOP: UPS switches to Bypass mode, label changes to RUN. Information Bar – Randomly displays status, helpful hints, acronym definitions every two seconds. FIGURE 12.10 – MAIN TAB COMPONENTS 4400 Series Installation and Operation Manual – 64527-006...
Page 87
4. To put the UPS back into Bypass mode, press the STOP button. The hourglass will display as in step 2, then the 2013012345 button will display the RUN icon. 4400F3F300FAB 30KVA FIGURE 12.11 – RUN/STOP BUTTON OPERATION 4400 Series Installation and Operation Manual – 64527-006...
Flow Indicator illustration on the following page. The figure below illustrates the data displayed when the corresponding button is pressed. MONITOR TAB 4400F Series UPS 4400F3F050 FIGURE 12-12 MONITOR TAB DISPLAY OPTIONS 4400 Series Installation and Operation Manual – 64527-006...
Page 89
The mimic display indicates the power flow through, or around, the UPS. There are four possible modes the UPS operates in: Off, Bypass, On-Line, and Backup. The figure below illustrates the display for each of these modes. FIGURE 12-13 MIMIC DISPLAY CURRENT FLOW INDICATOR 4400 Series Installation and Operation Manual – 64527-006...
UPS Operation time, Number of Faults, Backup, Operations. Display and Ext Comm. – Disp. S/W version, buzzer status, display calibration values. RemotEye I/P address, data and network status. FIGURE 12.14 – PARAMETER CATEGORIES 4400 Series Installation and Operation Manual – 64527-006...
Page 91
Write information (Enter) (Pressing Quit without first press- ing Write will cause the newly entered data to be lost.) Quit Exit keypad. Example 3 – Binary choice (On/Off, Enable/Disable, Contact A/Contact B) 4400 Series Installation and Operation Manual – 64527-006...
After the touchscreen has been recalibrated the display will indicate that the calibration routine has passed. Press Quit to return to the main display. See Fig. 12-15 C. FIGURE 12-15 TOUCHSCREEN DISPLAY CALIBRATION 4400 Series Installation and Operation Manual – 64527-006...
Pressing will cause the records to auto-page every 2 seconds. The button will alternately blink in black- on-white/white-on-black while in Auto-Page mode. Press the button again to stop Auto-Page. FIGURE 12.16 – RECORDS 4400 Series Installation and Operation Manual – 64527-006...
Auto-Page mode. Press the button again to exit Auto-Page mode. FIGURE 12.17 – HELP CATEGORIES 12.19 4400 Parameter Definitions See Appendix A for the Command Parameter definitions and functions. 4400 Series Installation and Operation Manual – 64527-006...
Toshiba Authorized service representative. INVCER OUTPUT CIRCUIT ABNORMAL Contact nearest Toshiba Authorized service representative. INVERR UPS CONTROL CIRCUIT Inverter voltage is out of spec. Contact nearest ERROR Toshiba Authorized service representative. 4400 Series Installation and Operation Manual – 64527-006...
When a Warning condition exists, the amber LED on the UPS display panel will flash for the duration of the Warning condition. TABLE 12.6 – SYSTEM WARNING MESSAGES System Warning Messages Display Meaning Action ASYN Output and Input do not match Contact nearest Toshiba Authorized service repre- sentative 4400 Series Installation and Operation Manual – 64527-006...
Page 97
BATTERY VOLTAGE Supplied battery voltage is incorrect or is not con- ABNORMAL nected. Check if battery cabinet circuit breaker is open, the battery polarity is correct, or the battery Voltage is correct.. 4400 Series Installation and Operation Manual – 64527-006...
No action needed. BTDIS Battery Test Disabled No action needed. BTING Battery Test in Progress Bypass mode – Power is sup- No action needed. plied by UPS input. BYPEN Bypass Enable No action needed. 4400 Series Installation and Operation Manual – 64527-006...
Page 99
Input and output are synchronized. TIMEDSD UPS is counting down prior to Immediately shut down the load equipment in an shutdown. orderly fashion and then press the STOP key. A warning has occurred. See Warning record. 4400 Series Installation and Operation Manual – 64527-006...
HH is the two digit hour followed by a colin (:) MM is the two digit month. AM/PM is before or after noon. Press Write to set the time. Press Quit to exit System Time setup. 4400 Series Installation and Operation Manual – 64527-006...
After shutting down the UPS by pressing the EPO switch, restore system power as follows: Ensure the cause of the EPO action has been resolved. Reset the UPS main circuit breaker MCCB, located behind the UPS front door, by first switching the breaker OFF, then ON. 4400 Series Installation and Operation Manual – 64527-006...
288 Vdc 288 Vdc Alarm voltage (V 246 Vdc 246 Vdc Shutdown voltage (V 230 Vdc 230 Vdc CURRENT VOLTAGE Shutdown Voltage TIME 100% Battery Capacity FIGURE 13.1 – TYPICAL BATTERY DISCHARGE CURVE 4400 Series Installation and Operation Manual – 64527-006...
CHARGING BATTERY CURRENT CHARGE CHARGE VOLTAGE (11.5A) = 324 V = 230 V DISCHARGE SHUT-OFF POINT FULLY CHARGED TIME PERIOD 1 PERIOD 2 PERIOD 3 FIGURE 13.2 – TYPICAL BATTERY CHARGING CURVE 4400 Series Installation and Operation Manual – 64527-006...
The buzzer can be disabled permanently by selecting the Settings tab then setting the parameter Buzzer Disable to Disable. This will disable the alarm so that no alarm sounds for any Fault or Warning condition. 4400 Series Installation and Operation Manual – 64527-006...
BACnet IP/MSTP (Internet Protocol /Master Slate Token Passing) 14.3 Remote System Monitoring – Remote Radar A network of Toshiba UPS’s equipped with the RemotEye network cards can be viewed and monitored using the optional RemotRadar application software on any MS-Windows machine. •...
25 kVA 25 kVA w/ Int. Batt. 1000 1155 25 kVA w/ 2 Xfmrs 1120 1275 30 kVA 30 kVA w/ Int. Batt. 1000 1155 30 kVA w/ 2 Xfmrs 1115 1270 4400 Series Installation and Operation Manual – 64527-006...
Page 107
80 kVA 1500 1655 80 kVA w/ 1 Xfmr Subject to change without notice. Shipping weights include 120 lb. (54.4 kg) for shipping pallet, and 35 lb. (15.9 kg) for shipping rails. 4400 Series Installation and Operation Manual – 64527-006...
Page 108
4400 Series Installation and Operation Manual – 64527-006...
Maximum battery discharge current based on lowest permissible discharge voltage of 1.6 VPC. 9. DC Circuit Breaker size based on breakers external to Toshiba-supplied Battery Cabinet(s) or UPS(s). (NOTE: Toshiba-supplied Battery Cabinets come equipped with internal circuit breakers sized to meet specific operating conditions) 10.
Page 122
(1) x 2 AWG / (1) x 2 AWG 200 A (1) x 4/0 / (1) 250 kcmil 300 A (1) x 500 kcmil / (2) 500 kcmil 4400 Series Installation and Operation Manual – 64527-006 Rev. 1.4 Page 1 of 2 4400-IPG-208/120v-208/120V...
Appendix D – Input/Output Cabling Guide The 4400 Series UPS can be configured with a variety of Input and Output voltage transformers to accommodate different Input/Output voltage combinations. Table D.1 – UPS Power Lug Cable Capacity and Torque Specifications Table D.2 –...
TABLE D.8 – OUTPUT TRANSFORMER CURRENT AT GIVEN OUTPUT VOLTAGE Output Output Current at Full Load (A) Voltage 15 kVA 20 kVA 25 kVA 30 kVA 50 kVA 80 kVA 208/120V 220/127V 230/133V 240/139V 380/220V 400/227V 415/240V 480/277V 600/347V 4400 Series Installation and Operation Manual – 64527-006...
Page 128
SOCIAL INFRASTRUCTURE SYSTEMS GROUP POWER ELECTRONICS DIVISION - UPS 13131 West Little York Road, Houston, Texas 77041 US (855) 803-7087 Fax. (713) 896-5212 Canada (800) 872-2192 www.toshiba.com/tic/industrial/uninterruptible-power-systems Printed in the U.S.A.