(c) Triple type
FDEN140VNTVF
Model
Indoor unit
Cool Mode
Outdoor
18 DB
21 DB
air temp.
12 WB
14 WB
DB
TC
SHC
TC
SHC
11
13
15
17
19
21
23
25
12.50 10.06 13.50 9.94 14.43 10.64 14.86 10.57 15.33 10.51 16.25 10.99 17.18 10.80
27
12.41 10.01 13.50 9.94 14.47 10.66 14.91 10.59 15.34 10.51 16.20 10.97
29
12.32 9.97 13.29 9.84 14.23 10.56 14.68 10.50 15.13 10.43 16.02 10.90
31
12.23 9.92 13.09 9.75 13.99 10.45 14.45 10.40 14.92 10.35 15.85 10.84
33
11.51 9.33 12.01 9.82 12.89 9.66 13.75 10.35 14.23 10.31 14.71 10.26 15.67 10.78
35
11.28 9.21 11.82 9.72 12.68 9.56 13.50 10.24 14.00 10.22 14.50 10.18 15.49 10.71
37
11.08 9.11 11.62 9.63 12.47 9.47 13.25 10.14 13.71 10.10 14.18 10.05 15.12 10.58
39
10.89 9.01 11.43 9.53 12.26 9.37 12.99 10.03 13.43 9.98 13.86 9.93 14.74 10.44
41
10.70 8.91 11.23 9.44 12.04 9.27 12.73 9.92 13.14 9.87 13.55 9.81 14.36 10.30
43
10.51 8.82 11.03 9.34 11.83 9.18 12.47 9.81 12.85 9.75 13.23 9.69 13.98 10.17
Model
FDEN140VSTVF
Indoor unit
Cool Mode
Outdoor
18 DB
21 DB
air temp.
12 WB
14 WB
DB
TC
SHC
TC
SHC
11
13
15
17
19
21
23
25
12.50 10.06 13.50 9.94 14.43 10.64 14.86 10.57 15.33 10.51 16.25 10.99 17.18 10.80
27
12.41 10.01 13.50 9.94 14.47 10.66 14.91 10.59 15.34 10.51 16.20 10.97
29
12.32 9.97 13.29 9.84 14.23 10.56 14.68 10.50 15.13 10.43 16.02 10.90
31
12.23 9.92 13.09 9.75 13.99 10.45 14.45 10.40 14.92 10.35 15.85 10.84
33
11.51 9.33 12.01 9.82 12.89 9.66 13.75 10.35 14.23 10.31 14.71 10.26 15.67 10.78
35
11.28 9.21 11.82 9.72 12.68 9.56 13.50 10.24 14.00 10.22 14.50 10.18 15.49 10.71
37
11.08 9.11 11.62 9.63 12.47 9.47 13.25 10.14 13.71 10.10 14.18 10.05 15.12 10.58
39
10.89 9.01 11.43 9.53 12.26 9.37 12.99 10.03 13.43 9.98 13.86 9.93 14.74 10.44
41
10.70 8.91 11.23 9.44 12.04 9.27 12.73 9.92 13.14 9.87 13.55 9.81 14.36 10.30
10.51 8.82 11.03 9.34 11.83 9.18 12.47 9.81 12.85 9.75 13.23 9.69 13.98 10.17
43
Note(1) These data show average statuses.
Note(1)
Depending on the system control, there may be ranges where the operation is not conducted continuously.
Note(1)
These data show the case where the operation frequency of a compressor is fixed.
(2) Capacities are based on the following conditions.
(2)
Corresponding refrigerant piping length :7.5m
(2)
Level difference of Zero.
(3) Symbols are as follows.
TC : Total cooling capacity
SHC : Sensible heat capacity
FDEN50VF (3 units)
Indoor air temperature
23 DB
26 DB
27 DB
16 WB
18 WB
19 WB
TC
SHC
TC
SHC
TC
SHC
11.37 8.98 12.02 9.63 12.35 9.55 12.70 9.48 13.39 9.96 14.08 9.78
11.90 9.21 12.61 9.87 12.96 9.80 13.33 9.72 14.09 10.21 14.84 10.02
12.43 9.45 13.19 10.11 13.57 10.04 13.97 9.97 14.78 10.45 15.59 10.27
12.96 9.69 13.77 10.36 14.17 10.29 14.61 10.22 15.48 10.71 16.34 10.52
13.24 9.82 14.06 10.48 14.48 10.41 14.92 10.35 15.80 10.82 16.68 10.63
13.51 9.94 14.36 10.61 14.78 10.54 15.23 10.47 16.12 10.94 17.02 10.75
13.51 9.94 14.40 10.63 14.82 10.56 15.28 10.49 16.19 10.97 17.10 10.77
FDEN50VF (3 units)
Indoor air temperature
23 DB
26 DB
27 DB
16 WB
18 WB
19 WB
TC
SHC
TC
SHC
TC
SHC
11.37 8.98 12.02 9.63 12.35 9.55 12.70 9.48 13.39 9.96 14.08 9.78
11.90 9.21 12.61 9.87 12.96 9.80 13.33 9.72 14.09 10.21 14.84 10.02
12.43 9.45 13.19 10.11 13.57 10.04 13.97 9.97 14.78 10.45 15.59 10.27
12.96 9.69 13.77 10.36 14.17 10.29 14.61 10.22 15.48 10.71 16.34 10.52
13.24 9.82 14.06 10.48 14.48 10.41 14.92 10.35 15.80 10.82 16.68 10.63
13.51 9.94 14.36 10.61 14.78 10.54 15.23 10.47 16.12 10.94 17.02 10.75
13.51 9.94 14.40 10.63 14.82 10.56 15.28 10.49 16.19 10.97 17.10 10.77
Outdoor unit
FDC140VN
28 DB
31 DB
33 DB
20 WB
22 WB
24 WB
TC
SHC
TC
SHC
TC
Outdoor unit
FDC140VS
28 DB
31 DB
33 DB
20 WB
22 WB
24 WB
TC
SHC
TC
SHC
TC
177
-
-
'12 • PAC-T-174
(kW)
Heat Mode
Outdoor
Indoor air temperature
air temp.
DB
WB
16
18
SHC
-19.8 -20
8.06 8.03 8.00 7.97 7.94
-17.7 -18
8.53 8.50 8.46 8.43 8.39
-15.7 -16
9.00 8.96 8.92 8.88 8.85
-13.5 -14
9.52 9.48 9.43 9.39 9.35
-11.5 -12
10.04 9.99 9.95 9.90 9.85
-9.5
-10
10.56 10.51 10.46 10.41 10.36
-7.5
-8
11.08 11.02 10.97 10.91 10.86
-5.5
-6
11.32 11.26 11.21 11.15 11.09
-3.0
-4
11.56 11.50 11.44 11.38 11.31
-1.0
-2
11.81 11.75 11.68 11.61 11.54
1.0
0
12.05 11.99 11.92 11.84 11.77
2.0
1
12.18 12.11 12.04 11.96 11.89
3.0
2
12.98 12.90 12.83 12.77 12.72
5.0
4
14.58 14.50 14.41 14.40 14.38
7.0
6
16.19 16.09 16.00 16.02 16.05
9.0
8
16.83 16.73 16.63 16.59 16.55
11.5
10
17.46 17.37 17.27 17.17 17.06
13.5
12
18.44 18.33 18.22 18.08 18.00
15.5
14
19.41 19.29 19.17 18.99 18.95
16.5
16
19.90 19.77 19.64 19.45 19.42
PFA003Z924
Heat Mode
(kW)
Indoor air temperature
Outdoor
air temp.
DB
WB
16
18
SHC
-19.8 -20
8.06 8.03 8.00 7.97 7.94
-17.7 -18
8.53 8.50 8.46 8.43 8.39
-15.7 -16
9.00 8.96 8.92 8.88 8.85
-13.5 -14
9.52 9.48 9.43 9.39 9.35
-11.5 -12
10.04 9.99 9.95 9.90 9.85
-9.5
-10
10.56 10.51 10.46 10.41 10.36
-7.5
-8
11.08 11.02 10.97 10.91 10.86
-5.5
-6
11.32 11.26 11.21 11.15 11.09
-3.0
-4
11.56 11.50 11.44 11.38 11.31
-1.0
-2
11.81 11.75 11.68 11.61 11.54
1.0
0
12.05 11.99 11.92 11.84 11.77
2.0
1
12.18 12.11 12.04 11.96 11.89
3.0
2
12.98 12.90 12.83 12.77 12.72
5.0
4
14.58 14.50 14.41 14.40 14.38
16.19 16.09 16.00 16.02 16.05
7.0
6
16.83 16.73 16.63 16.59 16.55
9.0
8
17.46 17.37 17.27 17.17 17.06
11.5
10
18.44 18.33 18.22 18.08 18.00
13.5
12
19.41 19.29 19.17 18.99 18.95
15.5
14
16.5
16
19.90 19.77 19.64 19.45 19.42
PFA003Z924
(kW)
DB
20
22
24
A
(kW)
DB
20
22
24
A