Summary of Contents for Mitsubishi Electric 800 Series
Page 1
なお、この取扱説明書(導入編)と同梱CD-ROMは、ご使用になるお客様の手元に届くようご配慮をお願いい たします。 INSTRUCTION MANUAL (STARTUP) (ENGLISH) Thank you for choosing this Mitsubishi Electric Inverter. This Instruction Manual (Startup) and the enclosed CD-ROM give handling information and precautions for use of this product. Do not use this product until you have a full knowledge of the equipment, safety information and instructions.
Page 19
付録 7 欧州 ErP( エコデザイン ) 指令について 欧州 ErP( エコデザイン ) 指令に基づき、効率データの内容を下記に記載します。 0.12kW 〜 1000kW の 3 相インバータが対象となります。 • SLD 定格 Rated Stand by load point 1 load point 2 load point 3 load point 4 load point 5 load point 6 load point 7 load point 8 Apparent Model name loss (90;100) (50;100) (0;100) (90;50) (50;50) (0;50) (50;25) (0;25) IE class power (kVA)
Page 20
Rated Stand by load point 1 load point 2 load point 3 load point 4 load point 5 load point 6 load point 7 load point 8 Apparent Model name loss (90;100) (50;100) (0;100) (90;50) (50;50) (0;50) (50;25) (0;25) IE class power (kVA) FR-F840-00620(30K)(-**) 34.5 FR-F840-00770(37K)(-**) 40.3 FR-F840-00930(45K)(-**) 49.7 FR-F840-01160(55K)(-**) 49.7 FR-F840-01800(75K)(-**) 49.7 FR-F840-02160(90K)(-**) 70.9 FR-F840-02600(110K)(-**) 70.9 FR-F840-03250(132K)(-**) 99.1 FR-F840-03610(160K)(-**) 99.1 FR-F840-04320(185K)(-**)
INSTRUCTION MANUAL (STARTUP) (ENGLISH) ─CONTENTS─ INVERTER INSTALLATION AND PRECAUTIONS ............3 WIRING........................... 4 BASIC OPERATION ...................... 9 FAILSAFE SYSTEM WHICH USES THE INVERTER ..........11 PRECAUTIONS FOR USE OF THE INVERTER ............11 This Instruction Manual provides handling information and WARNING precautions for use of this product. Please forward this Instruction Manual to the end user.
Page 31
Application of caution labels Depending on the product's function settings, the product does not stop its Caution labels are used to ensure safety during use of Mitsubishi Electric output even when the STOP/RESET key on the operation panel is inverters.
INVERTER INSTALLATION AND PRECAUTIONS Inverter model FR - F8 0 00046 Symbol Voltage class Symbol Description Symbol Type
Circuit board coating Symbol Plated conductor (conforming to IEC 60721-3-3:1994 3C2/3S2) 00023 to 06830 Inverter SLD rated current (A) 200 V class 400 V class 0.75 to 315K Inverter ND rated capacity (kW)
Terminal connection diagrams WIRING Terminal connection diagrams FM type FR-F820-00770(18.5K) to 01250(30K), FR-F840-00470(22K) to 01800(75K) DC reactor (FR-HEL)
DC reactor Brake unit (Option) (FR-HEL)
Sink logic Brake unit (Option) Jumper Main circuit terminal Earth (Ground) Control circuit terminal Jumper
Jumper Earth PR
N/-...
Page 34
Terminal connection diagrams CA type FR-F820-00770(18.5K) to 01250(30K), FR-F840-00470(22K) to 01800(75K) DC reactor (FR-HEL)
DC reactor Brake unit (Option) (FR-HEL)
Source logic Brake unit Jumper (Option) Main circuit terminal Earth (Ground) Control circuit terminal Jumper Jumper
Earth PR
N/- (Ground) Inrush PX
PR
N/-...
Page 35
Main circuit terminals Main circuit terminals Cable gauge of main circuit terminals and earth (ground) terminals Use an appropriate cable gauge to suppress the voltage drop to 2% or less. If the wiring distance is long between the inverter and motor, the voltage drop in the main circuit will cause the motor torque to decrease especially at a low speed. The following table indicates a selection example for the wiring length of 20 m.
Page 36
Main circuit terminals SLD rating (Pr.570 Multiple rating setting = "0") • 200 V class (220 V input power supply) Cable gauge Crimp terminal Terminal AWG/MCM HIV cables, etc. (mm PVC cables, etc. (mm Applicable inverter Tightening screw R/L1,...
Page 37
Control circuit terminal Control circuit terminal Wiring precautions • It is recommended to use a cable of 0.3 to 0.75 mm for connection to the control circuit terminals. • The wiring length should be 30 m (200 m for the terminal FM) at the maximum. •...
BASIC OPERATION Operation panel (FR-DU08) Name Description The setting dial of the Mitsubishi Electric inverters. Turn the setting dial to change the setting of frequency or parameter, etc. Press the setting dial to perform the following operations: Setting dial • To display a set frequency in the monitoring mode (The monitor item shown on the display can be changed by using Pr.992.)
Page 39
Operation panel (FR-DU08) 3.1.1 Basic operation (factory setting) Operation mode switchover/Frequency setting External operation mode At power-ON) PU Jog operation mode PU operation mode Alternating (Example) Frequency setting written and complete!! Value change Second screen Third screen (Output current monitoring) (Output voltage monitoring) First screen (Output frequency...
When a fault is detected by the protective function, the protective function is activated and outputs a fault signal (ALM). However, a fault signal may not be output at an inverter's fault occurrence when the detection circuit or output circuit fails, etc. Although Mitsubishi Electric assures the best quality products, provide an interlock which uses inverter status output signals to prevent accidents such as damage to the machine when the inverter fails for some reason.
Page 41
• Electrical corrosion of the bearing When a motor is driven by the inverter, axial voltage is generated on the motor bearing, which may cause electrical corrosion of the bearing in rare cases depending on: condition of the grease used for the bearing, wiring, load, operating conditions of the motor, or specific inverter settings (high carrier frequency, EMC filter ON).
Page 42
Directive, the manufacturer must declare the conformity and affix the CE marking. • The authorized representative in the EU The authorized representative in the EU is shown below. Name: Mitsubishi Electric Europe B.V. Address: Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany EMC Directive We declare that this inverter conforms with the EMC Directive and affix the CE marking on the inverter.
Page 43
• To use the inverter of FR-F820-00930(22K) or lower and FR-F840-00620(30K) or lower (IP20) outside of an enclosure in the environment of pollution degree 2, fix the fan cover with fan cover fixing screws enclosed. Fan cover Fan cover fixing screw fixing screw Fan cover Fan cover...
Page 44
The % value denotes the percentage to the inverter rated current. It is not the percentage to the rated motor current. When you set the electronic thermal relay function dedicated to the Mitsubishi Electric constant-torque motor, this characteristic curve applies to Range for operation at 6 Hz or higher. the transistor ...
Page 45
Model Manufacturer Rated voltage, VAC MMP-T32 Mitsubishi Electric Corp. 480Y/277 Suitable for use in a circuit capable of delivering not more than 50 or 25 kA rms symmetrical amperes, 480Y/277 volts maximum when protected by the Type E combination motor controllers indicated in the above table.
Page 46
The % value denotes the percentage to the inverter rated current. It is not the percentage to the rated motor current. When you set the electronic thermal relay function dedicated to the Mitsubishi Electric constant-torque motor, this characteristic curve applies to Range for operation at 6 Hz or higher. the transistor ...
Page 47
1 to 9, X (October), Y (November), or Z (December). • Authorized sales representative (importer) in the CU area The authorized sales representative (importer) in the CU area is shown below. Name: Mitsubishi Electric (Russia) LLC Address: 52, bld 1 Kosmodamianskaya Nab 115054, Moscow, Russia Phone: +7 (495) 721-2070...
Page 48
Appendix 4 Restricted Use of Hazardous Substances in Electronic and Electrical Products The mark of restricted use of hazardous substances in electronic and electrical products is applied to the product as follows based on the “Management Methods for the Restriction of the Use of Hazardous Substances in Electrical and Electronic Products” of the People's Republic of China. 电器电子产品有害物质限制使用标识要求...
Page 49
Appendix 7 Compliance with the EU ErP Directive (Ecodesign Directive) The following table shows the power loss data according to Ecodesign Directive. The regulation covers 3-phase variable speed drives from 0.12 kW .. Pn .. 1 000 kW. • SLD rated Rated ...
Page 50
Rated Stand by load point 1 load point 2 load point 3 load point 4 load point 5 load point 6 load point 7 load point 8 Apparent Model name loss (90;100) (50;100) (0;100) (90;50) (50;50) (0;50) (50;25) (0;25) IE class power (kVA) FR-F840-00620(30K)(-**) 34.5 FR-F840-00770(37K)(-**) 40.3 FR-F840-00930(45K)(-**) 49.7 FR-F840-01160(55K)(-**) 49.7 FR-F840-01800(75K)(-**) 49.7 FR-F840-02160(90K)(-**) 70.9 FR-F840-02600(110K)(-**) 70.9 FR-F840-03250(132K)(-**) 99.1 FR-F840-03610(160K)(-**) 99.1 FR-F840-04320(185K)(-**)
Page 52
4. Exclusion of loss in opportunity and secondary loss from warranty liability Regardless of the gratis warranty term, Mitsubishi Electric shall not be liable for compensation to: Damages caused by any cause found not to be the responsibility of Mitsubishi Electric.
Page 53
• The copyright and other rights of the enclosed CD-ROM all belong to Mitsubishi Electric Corporation. • No part of the enclosed CD-ROM may be copied or reproduced without the permission of Mitsubishi Electric Corporation. • Specifications of the enclosed CD-ROM are subject to change for modification without notice.
Page 54
FR-F800 Series Instruction Manual Supplement Monitoring terminals S1 and S2 (FR Configurator2) Graph display using FR Configurator2 is supported for terminals S1 and S2 (data from the high speed sampling and the USB trace file). The state of terminals S1 and S2 can be displayed in graph form using FR Configurator2. The FR Configurator2 version 1.28E or later supports graph display for terminals S1 and S2.
Page 55
FR-F800 Series Instruction Manual Supplement Earth (ground) fault detection at start / restricting reset method for an earth (ground) fault The reset method for the output side earth (ground) fault overcurrent (E.GF) can be restricted. • Select whether to enable or disable the earth (ground) fault detection at start. When enabled, the earth (ground) fault detection is performed immediately after a start signal input to the inverter.
Page 56
Output short-circuit fault (E.SCF) Select the reset operation and fault indication for an output short-circuit. Description Initial Name Setting range value Operation after detection Reset method E.OC1 to E.OC3 Not restricted Output short-circuit H194 detection E.SCF Restricted • The fault indication for an output short-circuit (E.OC1 to E.OC3, and E.SCF) can be changed by the Pr.521 setting.
Page 57
Extended detection time of the output current and zero current The setting range of the Pr.151 Output current detection signal delay time and Pr.153 Zero current detection time is extended. Initial Name Setting range Description value Set the output current detection time. Enter the time from Output current detection 0 to 300 s when the output current reaches the set current or higher...
Page 58
REVISIONS *The manual number is given on the bottom left of the back cover. Revision Date *Manual Number Revision Jul. 2014 IB-0600545-A First edition Added • Setting values "4 to 7, 14 to 17" of Pr.554 PID signal operation selection Aug.
Page 59
SE- 223 55 Lund Phone: +30 (0)211 / 1206-900 Phone: +46 (0) 8 625 10 00 Fax: +30 (0)211 / 1206-999 Mitsubishi Electric Turkey Elektrik Ürünleri A.Ş.TURKEY MELTRADE Kft.HUNGARY Fabrika Otomasyonu Merkezi Fertő utca 14. Şerifali Mahallesi Nutuk Sokak No.5 HU-1107 Budapest TR-34775 Ümraniye-İSTANBUL...
Page 78
附录 7 根据欧洲 ErP (生态设计)指令 根据欧洲 ErP (生态设计)指令,效率数据的内容如下所述。 0.12kW ~ 1000kW 功率的三相变频器为对象。 • SLD 额定时 Rated load load load load load load load load Stand by Apparent point 1 point 2 point 3 point 4 point 5 point 6 point 7 point 8 Model name loss...
Page 79
Rated load load load load load load load load Stand by Apparent point 1 point 2 point 3 point 4 point 5 point 6 point 7 point 8 Model name loss IE class power (90;100) (50;100) (0;100) (90;50) (50;50) (0;50) (50;25) (0;25) (kVA)
Page 88
HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN FR-F800 形 名 取扱説明書(導入編) 形名コード 1A2-P80 お断りなしに仕様を変更することがありますのでご了承ください Specifications subject to change without notice. IB(名)-0600545-E(2111)MEE Printed in Japan...