Honeywell T7200D Product Data

Honeywell T7200D Product Data

Series 2000 programmable commercial thermostats and subbases
Hide thumbs Also See for T7200D:

Advertisement

Series 2000 Programmable Commercial

APPLICATION

The T7200, T7300 Thermostats and Q7300 Subbases control
24 Vac commercial single zone heating, ventilating and air
conditioning (HVAC) equipment.

FEATURES

All Models:
• 7-day programming.
• Two Occupied and two Unoccupied periods per day.
• Individual heat and cool setpoints available for
Occupied and Unoccupied periods.
• Proportional plus Integral (P+I) control eliminates
temperature fluctuations.
• Intelligent Recovery® control automatically optimizes
equipment start times based on building load.
• Intelligent Fan™ feature energizes fan continuously in
the Occupied periods. Fan can also be configured for
conventional heat or electric heat fan operation.
® U.S. Registered Trademark
Copyright © 1997 Honeywell Inc. •
T7200D,E, T7300D,E,F and Q7300
Thermostats and Subbases
• All Rights Reserved
• Automatic or manual changeover models available.
• Universal Versaguard™ Thermostat guards available.
• Convenient overrides allow temporary setpoint changes.
• Keypad lockout available.
T7200D,E Thermostats
• Use on single-stage conventional (T7200D) or heat
pump (T7200E) applications.
T7300D,E Thermostats:
• Use on multistage conventional (T7300D) or heat
pump (T7300E) applications.
• Models available with remote sensor capability.
T7300F Thermostats:
• Use on single-stage or multistage system in
conventional or heat pump applications.
• Auxiliary contacts on Q7300 can be used to interface
with C7400/W7459 Economizer System for total
integration of rooftop control.
• Remote temperature sensors available for use with
all models.
• Different levels of keypad lockout available.
Q7300 Subbase:
• Use with T7300D,E,F Thermostats.
• Auxiliary contacts can be used to interface with
C7400/W7459 Economizer System for total
integration of rooftop control.
Application ........................................................................... 1
Features .............................................................................. 1
Specifications ...................................................................... 2
Ordering Information ........................................................... 2
Installation ........................................................................... 5
Wiring Subbase or Wallplate ............................................... 7
Settings ............................................................................... 9
Installer Setup ..................................................................... 10
Installer System Test ........................................................... 14
Programming ....................................................................... 16
Operation ............................................................................ 20
General Operation Information ............................................ 22
Troubleshooting Guide ........................................................ 23
Cross Reference ................................................................. 25
Wiring Diagrams .................................................................. 34
PRODUCT DATA
Contents
63-4355-1

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell T7200D

  • Page 1: Table Of Contents

    • Universal Versaguard™ Thermostat guards available. • Convenient overrides allow temporary setpoint changes. • Keypad lockout available. T7200D,E Thermostats • Use on single-stage conventional (T7200D) or heat pump (T7200E) applications. T7300D,E Thermostats: • Use on multistage conventional (T7300D) or heat pump (T7300E) applications.
  • Page 2: Specifications

    Honeywell Inc., 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386 (612) 951-1000 In Canada—Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 2C9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
  • Page 3 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 5. Temperature Offset. Electrical Rating: 24 Vac, 50/60 Hz. Temperature 20 to 30 Vac, 50/60 Hz. Range 18 AWG 20 AWG 22 AWG Batteries: 50-90°F -0.4°F -0.7°F -1.0°F No batteries required.
  • Page 4 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES 6-3/4 (172) 1/16 (2) 3-1/4 (82) 1-3/8 (35) 1-7/8 (47) 4-1/8 (105) 4-3/4 (121) 1-11/16 (43) 7-5/16 (186) (22) 5 (127) 4-5/8 Set Program Set Temperat ure Change (117)
  • Page 5: Installation

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES INSTALLATION Q7300 Subbase with Remote-Mounted Temperature Sensor(s) When Installing this Product… If only the remote-mounted temperature sensor(s) is used to sense and control room temperature, then install the 1. Read these instructions carefully. Failure to follow the...
  • Page 6 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES IMPORTANT SUBBASE To avoid electrical interference, which can cause erratic performances, keep wiring runs as short as T7047G T7047G possible and do not run thermostat wires adjacent to the line voltage electrical distribution systems. Use shielded cable (Belden type 8762 or equivalent for 2-wire and Belden type 8772 or equivalent for 3-wire).
  • Page 7: Wiring Subbase Or Wallplate

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES 3. Remove the subbase or wallplate from the wall and drill two 3/16 inch holes in the wall (if drywall) as marked. WALL For firmer material such as plaster or wood, drill two 7/32 inch holes.
  • Page 8 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 6. Terminal Designations (continued). Standard Alternate Terminal Terminal Terminal Designations Designations Typical Connection Function Type H2, R4, W3, Y Stage 2 heating relay Output 24V powered contact —...
  • Page 9: Settings

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES SETTINGS Using Thermostat Keys The thermostat keys are used to: • set current time and day, • program times and setpoints for heating and cooling, • override the program temperatures, •...
  • Page 10: Installer Setup

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES ENTER UNOCCUPIED SET OCCUPIED SET UNOCCUPIED TEMPERATURE PROGRAM MODE TEMPERATURE SETPOINTS AND SCROLLS ENTER OCCUPIED SETPOINTS THROUGH INSTALLER SETUP SET CURRENT DAY OR PROGRAM MODE AND SYSTEM TEST PROGRAM DAY...
  • Page 11 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES — To advance to the next Installer Setup number, press the CAUTION Unoccupied Temp key. — To return to an Installer Setup number, press the Heat/ Heat pump and electric heat systems must be Cool Settings key.
  • Page 12 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 8. Thermostat Installer Setup Options (Continued). Installer Setup Number (Press Other Choices Unoccupied (Press key to change) Factory-Setting Temp key Actual to change) Setting Select Display Description Display Description Intelligent Fan™...
  • Page 13 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 8. Thermostat Installer Setup Options (Continued). Installer Setup Number (Press Other Choices Unoccupied (Press key to change) Factory-Setting Temp key Actual to change) Setting Select Display Description Display...
  • Page 14: Installer System Test

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES IMPORTANT To start the system test: Review the settings to confirm that they match the system. Press Run Program to exit the Installer CAUTION Setup. The thermostat has saved the Installer Setup...
  • Page 15 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 10. Installer System Test Options. Key to Test Press Number Description Heating Equipment System Test Heat/Cool Settings Enter heating equipment system test. Stage-one heat comes on. The system fan is also energized.
  • Page 16: Programming

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Thermostat Information 7. Press Run Program to exit the self-test. The self-test times out after four minutes without any key presses. 1. Press the Heat/Cool Settings key to access the thermostat information.
  • Page 17 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 11. Occupied and Unoccupied Periods Start Times. 3. Press increase or decrease key until the current time is displayed. Occupied Unoccupied Occupied Unoccupied Period 1 Period 1 Period 2...
  • Page 18: Copying A Day

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES 5. Press increase or decrease key until the desired 3. Press Copy. start time is displayed. Copy ProgramStart Time Set Program Set Temperature Change Time/Temp Occupied Unoccupied Occupied Unoccupied...
  • Page 19 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES 4. Press increase or decrease key until the desired 3. Press Clear Start Time. temperature is displayed. Set Program Start Time Clear Set Program Setting Start Time Set Program...
  • Page 20: Operation

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES 1. Press Temporary Occupied. Changing Temperature Setpoint Until Next Program Period NOTE: The default temperature setting is the Occupied setpoint. 1. Press increase or decrease key until the desired temperature is displayed.
  • Page 21 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES offset. This makes temperature control more accurate than the installer setup number 32. Using the minimum on and off the conventional electromechanical or electronic thermostats. times assures that rapid cycling of equipment does not occur, The temperature control algorithm is called proportional plus which extends equipment life.
  • Page 22: General Operation Information

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 13. Operation of Q7300 O and B terminals. Intelligent Recovery® Feature Intelligent Recovery® feature is a Honeywell trademark for System Selection O Terminal B Terminal the way the thermostat controls the heating and cooling...
  • Page 23: Troubleshooting Guide

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Interfacing with Other Uses for the Auxiliary Relay Examples of other uses of the auxiliary relay are hot water Electromechanical Economizers heaters, lighting or baseboard heat. The additional loads are (Subbases with Auxiliary Relay) connected to the auxiliary relay contacts on the subbase.
  • Page 24 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 14. Troubleshooting Information. Symptom Possible Cause Action Display will not come Thermostat is not being powered. • Check that X terminal is connected to the system transformer. • Check for 24 Vac between X and R or RH terminals.
  • Page 25: Cross Reference

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 14. Troubleshooting Information (Continued). Symptom Possible Cause Action Heating will not come Thermostat minimum off time is • Wait up to five minutes for the system to respond.
  • Page 26 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 16. Thermostat and Subbase Cross Reference (Continued) . Model Number Description Trade Replacement Remarks Q7300A1042 Two-stage heat and two-stage cool; Trane T7300F2002/Q7300A2016 part no. BAS-0445. Q7300A1059 Two-stage heat and two-stage cool; Micrometl T7300F2002/Q7300A2016 part no.
  • Page 27 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 16. Thermostat and Subbase Cross Reference (Continued) . Model Number Description Trade Replacement Remarks Q7300C1097 Single-stage heat pump with auxiliary heat T7300F2010/Q7300C2004 Wiring differences (2H/1C). (old=new): W1=W2, B=A3.
  • Page 28 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 16. Thermostat and Subbase Cross Reference (Continued) . Model Number Description Trade Replacement Remarks T7200A One-stage heat and one-stage cool conventional thermostat. T7200A1006 Honeywell logo. T7200D2008 T7200A1022 Honeywell logo with international faceplate.
  • Page 29 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 16. Thermostat and Subbase Cross Reference (Continued) . Model Number Description Trade Replacement Remarks T7300C1019 Honeywell logo; Premier White® color. See subbase description for replacement information. T8611M Three-stage heat and two-stage cool heat pump thermostat;...
  • Page 30 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 16. Thermostat and Subbase Cross Reference (Continued) . Model Number Description Trade Replacement Remarks T8621B7018 BDP multi-logo; LOW and HIGH SPEED LEDs; T7300D2007/Q7300A2008 Wiring differences used on multispeed equipment;...
  • Page 31 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES Table 16. Thermostat and Subbase Cross Reference (Continued) . Model Number Description Trade Replacement Remarks T8621D7139 McQuay logo; Premier White® color; T7300D2007/Q7300A2008 Wiring differences part no. 067114301. (old=new): C=X.
  • Page 32 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES T7300/Q7300 Series 2000 Cross Reference. Figure Trade Model Number Number Description Replacement Remarks Q7300A Multistage conventional subbase used with T7300D or F Thermostat. Q7300A2008 One-stage heat and one-stage cool;...
  • Page 33 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES T7300/Q7300 Series 2000 Cross Reference (Continued) . Figure Trade Model Number Number Description Replacement Remarks T7300D Multistage conventional thermostat used with Q7300A,G, or L Subbase. T7300D2007 Refer to Honeywell logo; TRADELINE® model;...
  • Page 34: Wiring Diagrams

    T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES WIRING DIAGRAMS (FIG. 19-32) THERMOSTAT THERMOSTAT COMPRESSOR COOL CHANGEOVER CONTACTOR VALVE HEATING COMPRESSOR CONTACTOR RELAY OR VALVE COIL RELAY RELAY (HOT) (HOT) POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
  • Page 35 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES SUBBASE COMPRESSOR HEAT CONTACTOR RELAY 2 HEAT RELAY RELAY 1 (HOT) (HOT) HEATING COOLING TRANSFORMER TRANSFORMER POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER.
  • Page 36 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES SUBBASE A2 A3 COMPRESSOR HEAT ECONOMIZER EQUIPMENT CONTACTOR 1 RELAY 2 DISCHARGE MONITOR 2 SENSOR COMPRESSOR T7147 REMOTE COMFORT ADJUST MODULE EQUIPMENT RELAY CONTACTOR 2 MONITOR 1 HEAT RELAY 1...
  • Page 37 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES SUBBASE AUX. EQUIPMENT HEAT COMPRESSOR DISCHARGE CONTACTOR 2 MONITOR 2 SENSOR RELAY T7147 REMOTE COMFORT ADJUST MODULE COMPRESSOR EQUIPMENT CONTACTOR 1 EM. HT. MONITOR 1 RELAY ECONOMIZER COOL HEAT...
  • Page 38 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES SUBBASE A2 A3 EM. HT. HEAT COMPRESSOR ECONOMIZER EQUIPMENT RELAY RELAY 2 CONTACTOR 1 DISCHARGE MONITOR 2 SENSOR T7147 REMOTE COMFORT ADJUST MODULE EQUIPMENT HEAT RELAY RELAY 3 MONITOR 1...
  • Page 39 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES SUBBASE A2 A3 HEAT COMPRESSOR ECONOMIZER COMPRESSOR EQUIPMENT RELAY 2 CONTACTOR 1 DISCHARGE CONTACTOR 2 MONITOR 2 SENSOR T7147 REMOTE COMFORT ADJUST MODULE EQUIPMENT COMPRESSOR RELAY CONTACTOR 3 MONITOR 1...
  • Page 40 T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES SUBBASE HIGH-SPEED PUMP COOLING FAN RELAY INTERLOCK RELAY RELAY DAMPER T7147 REMOTE COMFORT ADJUST MODULE SPEED CONTROL RELAY RELAY (HOT) POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

Table of Contents