Safety Precautions Safety Precautions To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications. WARNING This symbol indicates the possibility of death or serious injury.
Page 4
Safety Precautions Do not modify or extend the Do not install, remove, or re- Be cautious when unpacking power cable. install the unit by yourself and installing the product. (customer). • There is risk of fire or electric shock. • There is risk of fire, electric shock, •...
Page 5
Safety Precautions Do not store or use flammable gas or com- If strange sounds, or smell or smoke comes bustibles near the product. from product. Turn the breaker off or discon- nect the power supply cable. • There is risk of fire or failure of product. •...
Page 6
Safety Precautions CAUTION Installation check for gas (refrigerant) Install the drain hose to Keep level even when leakage after installation or ensure that water is drained installing the product. repair of product. away properly. • Low refrigerant levels may cause fail- •...
Details of LG Model Name Details of LG Model Name Outdoor Unit A 3 U H 2 1 6 F A 0 Development Sequence Function A: Basic Multi Type F: Free joint multi Electric Standard (Volts / Freq. / Phase) 6: 220-240V~ / 50Hz / 1Ø...
Dimensions Dimensions 1. Indoor Unit • Model: SQ/SR/ST chassis Installation plate Capacity SQ Ch. 7K/9K SR Ch. ST Ch. 18K/24K 1080 • Model: SP 1 chassis Hanger Hole Fix Hole Pipe Hole Capacity SP1 Ch. 9K/12K Service Manual 17...
Page 18
Dimensions 2. Outdoor Unit 2-1 A2UC146FA0, A2UH146FA0 Gas side 3-way valve Liquid side 2-way valve MODEL A2UC146FA0, A2UH146FA0 543.6 11.4 72.5 74.5 18 Free Joint Multi Air Conditioner...
Page 19
Dimensions 2-2. A2UC186FA0, A2UH186FA0 Gas side 3-Way valve Liquid side 2-Way valve MODEL A2UC186FA0, A2UH186FA0 64.5 Service Manual 19...
Page 20
Dimensions 2-3 A3UC216FA0, A3UH216FA0 Gas side 3-way valve Liquid side 2-way valve MODEL A3UC216FA0, A3UH216FA0 64.5 20 Free Joint Multi Air Conditioner...
Page 21
Dimensions 2-4 A4UC306FA0, A4UH306FA0 Gas side 3-way valve Liquid side 2-way valve MODEL A4UC306FA0, A4UH306FA0 1038 1035 64.5 Service Manual 21...
Refrigeration Cycle Diagram Refrigeration Cycle Diagram 1. A2UH146FA0 Indoor Side Outdoor Side 4- WAY Valve COMP 2. A2UC146FA0 Indoor Side Outdoor Side COMP Capillary Solenoid Valve L.E.V 3-Way Valve 2-Way Valve 22 Free Joint Multi Air Conditioner...
Page 23
Refrigeration Cycle Diagram 3. A2UH186FA0 Indoor Side Outdoor Side 4- WAYValve COMP A COMP B 4. A2UC186FA0 Indoor Side Outdoor Side COMP A COMP B Capillary Solenoid Valve L.E.V 3-Way Valve 2-Way Valve Service Manual 23...
Page 24
Refrigeration Cycle Diagram 5. A3UH216FA0 Indoor Side Outdoor Side 4- WAY Valve COMP A COMP B 6. A3UC216FA0 Indoor Side Outdoor Side COMP A COMP B Capillary Solenoid Valve L.E.V 3-Way Valve 2-Way Valve 24 Free Joint Multi Air Conditioner...
Page 25
Refrigeration Cycle Diagram 7. A4UH306FA0 Indoor Side Outdoor Side 4- WAY Valve COMP A COMP B 8. A4UC306FA0 Indoor Side Outdoor Side COMP A COMP B Capillary Solenoid Valve L.E.V 3-Way Valve 2-Way Valve Service Manual 25...
Electronic Control Device Electronic Control Device Indoor Unit AMNC076LQL0, AMNC096LQL0, AMNC126LRL0, AMNC186LTL0, AMNC246LTL0, AMNH076LQL0, AMNH096LQL0, AMNH126LRL0, AMNH186LTL0, AMNH246LTL0, AMNH096LQA0, AMNH246LQA0 • MAIN P.C.B DC ASM • MAIN P.C.B AC ASM Service Manual 29...
Functions Functions Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature • Room temperature sensor. (THERMISTOR) Room temperature control • Maintains the room temperature in accordance with the Setting Temp. Starting Current Control • Indoor fan is delayed for 5 sec at the starting. Time Delay Safety Control •...
Functions Remote Controller Operation ON/OFF Operation Mode Selection Cooling Operation Mode.( Auto Operation Mode.( (Cooling (Heating Healthy Dehumidification Operation Mode.( Heating Operation Mode.( model only) model only) Fan Speed Selection (Low) (Med) (High) (CHAOS) Room, Temperature Display : (High: 39°C LOW : 11°C) Temperature Setting Down to 18°C...
Page 37
Functions Signal Receptor Receives the signals from the remote controller.(Signal receiving sound: two short beeps or one long beep.) Operation Indication Lamps On/Off : Lights up during the system operation. Sleep Mode : Lights up during Sleep Mode Auto operation. Timer : Lights up during Timer operation.
Page 38
Functions Remote Control Operation The Remote Controller transmits the signals to the system. START/STOP BUTTON Operation starts when this button is pressed and stops when the button is pressed again. OPERATION MODE SELECTION BUTTON Used to select the operation mode. (Cooling Only) Signal transmitter (Heat Pump)
Operation Details Operation Details Main Unit Function 1) C/O Model Operation Indicator • On while in appliance operation, off while in appliance pause • Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on) Sleep Timer Indicator •...
Page 40
Operation Details • While in compressor off, the indoor fan repeats low airflow speed and pause. • While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidifica- tion operation and 4-min compressor off repeat. Compressor ON Temp.
Page 41
Operation Details Fuzzy Operation (C/O Model) • According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on. Compressor ON Temp Setting Temp + 0.5°C Compressor OFF Temp...
Page 42
Operation Details 2) Fuzzy Operation for Dehumidification • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Operation Details Off-Timer Operation • When the set time is reached after the time is input by the remote control, the appliance stops operating. • The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached. •...
Operation Details Jet Cool Mode Operation (C/O Model) • If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates. • In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation. •...
Page 45
Operation Details Remote Control Operation Mode • When the remote control is selected by the slide switch on the main unit, the appliance operates according to the input by the remote control. Protection of the evaporator pipe from frosting • If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool- ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor evaporator pipe from frosting.
2-way, 3-way Valve 2-way, 3-way Valve 2-way Valve (Liquid Side) 3-way Valve (Gas Side) Valve cap Hexagonal wrench Open position (4mm) Closed position Flare nut Flare nut Open position Closed position piping piping Service Service connection connection port cap port To outdoor unit To outdoor unit Works...
Page 47
2-way, 3-way Valve (1) Pumping down Liquid side Indoor unit Outdoor unit Close 2-Way valve Gas side Open 3-Way valve Liquid side Indoor unit Close 2-Way valve Gas side Open 3-Way valve manifold gauge Low- handle Hi- handle (CLOSE) (CLOSE) Procedure •...
Page 48
2-way, 3-way Valve (2) Evacuation (All amount of refrigerant leaked) Liquid side Indoor unit Outdoor unit Open 2-Way valve Gas side Open 3-Way valve Liquid side Indoor unit Open 2-Way valve Gas side Open 3-Way valve manifold gauge Vacuum pump Low- handle Hi- handle...
Page 49
2-way, 3-way Valve (3) Gas Charging (After Evacuation) Liquid side Indoor unit Outdoor unit Open 2-Way valve Gas side Open 3-Way valve Liquid side Indoor unit Open 2-Way valve Gas side Open 3-Way valve manifold gauge Charging cylinder Low-handle Hi- handle (OPEN) Check valve (OPEN)
Cycle Troubleshooting Guide Cycle Troubleshooting Guide Trouble analysis 1. Check temperature difference between intake and discharge air, and operating current. Temp. difference : approx. 0°C All amount of refrigerant leaked out. Current : less than 80% of Check refrigeration cycle. rated current Temp.
Page 51
Cycle Troubleshooting Guide Comp basic step. Free joint outdoor unit has two compressor (TPS: Twin power system) Step Step 1 Step 2 Step 3 Outdoor Operation Mode COMP 40%(B)only COMP 60%(A)only COMP 100%(A+B) together 18k(Max. 19k) Cooling Qs<=7k Qs<=12k 12k<Qs Heating Qs<=9k 12k<Qs...
Electronic Parts Troubleshooting Guide Electronic Parts Troubleshooting Guide 1. The Outdoor Unit does not operate at all Does the Operating LED of indoor unit blink Refer to the self-diagnosis function. when Operation’s ON? Is the Connection between CN-Power of indoor Check the connecting state of connector unit and terminal block? Indoor...
Page 53
Electronic Parts Troubleshooting Guide 2. The product is not operate with the remote controller. Turn on Main Power While the compressor has been stopped, the compressor does not operate owing to the delaying function for 3 minutes after stopped. When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is not controlled by the remote controller.
Page 54
Electronic Parts Troubleshooting Guide 3. When cooling does not operate Turn on Main Power Operate "Cooling Mode( )" by setting the desired temperature of the remote controller is less than one of the indoor temperature by 1°C at least. When in Air Circulation Mode, Compressor/Outdoor Fan is stopped. Check the sensor for indoor temperature is attached as close as to be effected by the temperature of Heat Exchanger(EVA).
Page 55
Electronic Parts Troubleshooting Guide 4. When Heating does not operate Turn ON Main Power Operate “Heating Mode( )” by setting the desired temperature of the remote control is higher than one of the indoor temperature by 2°C at least. In heating Mode, the indoor fan operates in case the pipe temperature is higher than 28°C.
Page 56
Electronic Parts Troubleshooting Guide 5. When indoor Fan does not operate Turn off Main power Check the connection of CN-FAN or CN-MOTOR Check the Fan Motor Check the Fuse(AC250V/T2A) Check the related circuit of indoor Fan Motor. • The pin of Micom, and the part for driving SSR •...
Page 57
Electronic Parts Troubleshooting Guide 6. When Vertical Louver does not operate • Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor. • If the regular torque is detected when rotating the Vertical Louver with hands Normal •...
Disassembly of the parts (Indoor unit) Disassembly of the parts (Indoor unit) 2. To remove the Control Box. 1. SQ/SR/ST Chassis • Remove securing screws. • Pull the control box out from the chassis carefully. Warning : Disconnect the unit from power supply before making any checks.
Page 59
Disassembly of the parts (Indoor unit) • Unhook the tab on the right inside of the chassis 2. SP1 Chassis at the same time, slightly pull the evaporator toward you until the tab is clear of the slot. Warning : Disconnect the unit from power supply before making any checks.
Page 60
Disassembly of the parts (Indoor unit) 3. To remove the Evaporator. 5. To remove the Motor. - Remove 4 screws securing the evaporator. - Remove the securing bolt from the motor shaft. - Pull the evaporator out from the chassis carefully. - Pull the fan out from the motor shaft.