Site Requirement Guidelines
Figure 1-52
Typical DC Power Cable Lug
.25 in +/- .04 in
(6.35 mm +/- 1.016 mm)
(16 mm +/- 0.508 mm)
0.48 in +/- .04 in
(12.192 mm +/- 1.016 mm)
0.08 in +/- .01 in
(2.032 mm +/- 0.254 mm)
(31.75 mm +/- 1.016 mm)
•
•
The DC power trays and power modules for the Cisco ASR 9000 Series Routers are identical, so the
Note
examples shown in
To avoid shock hazard, be sure to apply shrink wrap tubing around the wire entry area of the lug.
Caution
Cisco ASR 9000 Series Aggregation Services Router Hardware Installation Guide
1-48
0.63 in +/- .02 in
0.27 in +/- .02 in
(6.858 mm +/- .508 mm)
90 degrees +/- 5 degrees
1.25 in +/- .04 in
1.66 in (42.164 mm )
Figure 1-53
shows typical DC power source cable connections for a version 1 single DC power
module, in this case, a module installed in slot M2 of the power tray.
Figure 1-54
shows typical DC power source cable connections for a version 2 single DC power
module, in this case, a module installed in slot M3 of the power tray.
Figure 1-53
0.22 in
(5.588 mm)
0.31 in
(7.874 mm)
Beveled wire entry
0.81 in +/- .04 in
(20.574 mm +/- 1.016 mm)
and
Figure 1-54
apply to all of these routers.
Chapter 1
Preparing for Installation
1.16 in
(29.464 mm)