hit counter script

Honeywell ADEMCO VISTA-40 Installation And Setup Manual page 49

2-partitioned security system
Hide thumbs Also See for ADEMCO VISTA-40:
Table of Contents

Advertisement

FIELD
TITLE and DATA ENTRIES
Ignore Expansion Zone Tamper
*24
0 = disable (tamper detection)
1 = enable (no tamper detection)
Burglary Trigger for Response
*25
Type 8
0 = disable
1 = enable
Intelligent Test Report
*26
0 = disable
1 = enable
Test Report Interval
*27
Enter 001-199 for the test report interval in
hours.
Enter 000 for test reporting.
Power-Up in Previous State
*28
0 = disable
1 = enable
Quick Arm (partition-specific)
*29
0 = disable
1 = enable
TouchTone or Rotary Dial
*30
0 = disable
1 = enable
If you select TouchTone, make sure the subscriber has requested and is paying for TouchTone service. Note that
whether or not TouchTone dialing for call placement is permitted, communication by the use of DTMF signaling
(ADEMCO High Speed) will still take place. See field 1*33 for TouchTone w/Rotary backup
PABX Access Code
*31
Enter 00-09; B-F (11-15)
Primary Subscriber's Account
*32
Number (partition-specific)
Enter 00-09; B-F (11-15)
EXPLANATION
If disabled, the system monitors the tampers on expansion zones.
NOTE: Only applicable to certain polling loop sensors with tamper
switches or 5800 Series transmitters.
Must be 0 for UL installations.
If enabled, allows triggering of Output 3 (pin 7) of the J7 header to
include zone response type 8 (24-hr. auxiliary).
If enabled, no test report is sent if any other type of report was sent since
the last test report.
If disabled, test reports are sent at the set intervals, regardless of
whether or not any other report has been sent.
Must be 0 for UL applications.
If a test report is desired, enter a test code in field *81 and *82. Set first
test report time in field *83.
Maximum Test report interval is 024 for UL installations.
If enabled, the system, upon power-up, reverts to its status prior to a
complete power loss.
If disabled, the system always powers up in a disarmed state.
NOTE: Neither authority level 0 nor 5 can be used to disarm the system
if the control powers up armed.
Must be 1 for UL applications.
If enabled, allows arming of the burglary system in AWAY, STAY,
INSTANT, or MAXIMUM mode by using the [#] key instead of the user
code.
NOTES:
When armed, the system reports closing as User 0 if Open/Close reporting
for User #2 (typically a Master level user) was enabled for a given
partition.
If Quick Arm is used, the Installer Code and Authority Level 5 codes
cannot disarm the system.
Select the dialing method for the system
This field is used to enter up to four 2-digit numbers representing the
prefix needed to obtain an outside telco line. If not required, enter
nothing and proceed to next field.
Enter a 3- or 4-digit (depending on report format) primary subscriber
account number. Each number requires a 2-digit entry so as to allow
entry of hexadecimal digits (B-F). If a 3-digit account number is to be
used, enter data only in the first 3 locations, and enter * in the fourth
location.
Section 5 – Data Field Descriptions
5-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents