Infrared Flame Detector The C7015A Flame Detector includes a lead sulfide photocell that is sensitive to the infrared radiation emitted by the combustion offuels such as natural gas, oil, and coal. Particularily suitable for combination or dual-fuel applications. When installed properly, can supervise the pilot flame and/or the main burner flame.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1. Your local Honeywell Residential and Building Controls Division Sales Office (check white pages of phone directory). 2. Residential and Building Controls Division Customer Satisfaction Honeywell Inc., 1885 Douglas Drive North...
C7015A leadwires are connected. The stickerprohibits routing any other wiring through the junction box. RRPLACFMENT PARTS: 104662D Lead Sulfide Photocells Fig. l-Mounting dimensions of C7015A infrared Flame Detector and accessories, in in. [mm]. 106061 HEAT BLOCK ‘COLLAR. 3/4 - 14 NPSM...
2. All wiring must be NBC Class 1 (line voltage). 3. Use the C7015A only with Honeywell lead sulfide photocells (part no. 104662D) and flame signal amplifiers specified, (see Table 6).
C7015A is mounted. FIELD OF VIEW A lead sulfide photocell, like other photocells, views an area rather than a point. It is unable to pinpoint pilot flame locationaseasilyasaflamerod.Ifthedetectoristoproveonly jlame, it must view only a part of...
C7015A INSTALLATION INSTALLING AN ORIFICE PLATE AnorificeplatewithahexagonalorificediameterofO.125 in. [3.2 mm] is available for the C7915A Infrared Flame Detector. The orifice can be mounted in front of the cell in the adapter seal-off or in a standard 314 in. coupling. (Refer to Fig.
Refer to Figs. 2 and 3 for methods of reducing the ama of hot refractory sighted. Fig. 4--C7015A infrared Flame Detector aimed at side wall of combustion chamber. ‘, I __----- Fig.
SIGHT PIPE TEE MOUNTING THE DETECTOR PIPE Before mounting the C7015A , install the lead sulfide photocell (if not installed already). Unscrew the bushing from the cap, plu cell mount, and screw the bushing back into the cap (Fig. 8). The bushing also includes a focu&n g lens to concenuate available radiation on the photocell face.
194°F [90” C] if used with a flame safeguard Honeywell specification no. R1298020 or equivalent for the FOCUSING LENS I F leadwire. (This wire is rated up to 400” F [204” Cl for continuous duty. It is tested for operation up to 600 volts and breakdown up to 7500 volts.) For the other leadwire, use...
FLEXIBLE CABLE (MECHANICALLY SUPPORT TO MINIMIZE MOVEMENT) GROUNDlNG STRAP, 1 1 BROWN WIRE AND 1 WHITE WIRE FROM THE C7015A. CONNECT TO FLAME SAFEGUARD CONTROL’S SUBBASE, COLOR NOT IMPORTANT, KEEP WIRES AS SHORT AS POSSIBLE. AND TWIST THEM. AFLEXIBLE To FLAME SA...
RED CONNECTOR El 208 TABLE 6-FLAME SIGNAL Minimum Acceptable Steady Current (microamp) 2.25 ADJUSTMENTS AND CHECKOUT PROBES ECS 7700 CHASSIS MODULE FOOTMOUNT Maximum Minimum Expected Acceptable Steady Voltage Current (microamp) (Vb) 1.25 1.25 C7015A E2512A Maximum Expected Voltage (Vdc) 4.98 60-2306-5...
Page 12
C7015A ADJUSTMENTS AND CHECKOUT PILOT TURNDOWN TEST Ifthedetectorisusedtoproveapilotflamebeforethemain fuel valve( can be opened, perform a Pilot Turndown Test before welding the sight pipe into position. Follow the procedures in the instructions for the appropriate flame safeguard control, and the burner manufacturer instructions.
Troubleshooting in the instructions for the appropri- ate flame safeguard control. EQUIPMENT REQUIRED 1. Voltmeter(HoneywellW136Aorequivalent)withOto 300 Vat scale. 2. Microammeter (Honeywell W136A or equivalent) with 0 to 25 microampdc range. 3. W136ACableConnector,partno. 196146, or 117053 Meter Connector Plug or equivalent (required for some meters).
2. Open the master switch to disconnect power before removing or installing the detector. 3. If the C7015A is disassembled for any reason (e.g., to replace the lead sulfide cell or bushing with focusing lens), you must perform the Ad- justments and Checkout, page 11.
Table 6 -Flame Signal ... Figures Fig. 1 -Mounting dimensions of C7015A Infrared Flame Detector and accessories, in in. [mm]..3 Fig. 2 -Methods of reducing C7015A Infrared Flame Detector field-of-view ... 5 Fig. 3 -Using orifice plate to restrict detector field-of-view to intersection of pilot and main flame, or to small area of hot refractory ...