4–38
Using Intelligent Input Terminals
The 4-quadrant operation mode for torque
limiting (B040=00) is illustrated in the figure
to the right. The instantaneous torque depends
on inverter activity (acceleration, constant
speed, or deceleration), as well as the load.
These factors determine the operating quadrant
at any particular time. The parameters in B041,
B042, B043 and B044 determine the amount of
torque limiting that the inverter applies.
The terminal selection mode (B040=01) uses two intelligent inputs [TRQ1] and [TRQ2] for the
binary-encoded selection of one of the four torque limit parameters B041, B042, B043 and
B044.
Opt.
Symbol
Function Name
Code
40
TL
Torque limit enable
41
TRQ1
Torque limit select 1
42
TRQ2
Torque limit select 2
C001, C002, C003, C004,
Valid for inputs:
C005, C006, C007, C008
B040, B041, B042, B043,
Required
B044
settings:
Notes:
• Both the 4-quadrant mode and terminal
switching mode of torque limiting use input
[TL] for enable/disable.
• Inputs TRQ1 and TRQ2 apply only to
terminal switching mode.
Intelligent
Torque limit
Inputs
parameter
TRQ2
TRQ1
OFF
OFF
B041
OFF
ON
B042
ON
OFF
B043
ON
ON
B044
• When using the torque limit function at low
speed, also use the overload restriction
feature.
Torque
Reverse-regenerating
B042
RV
Reverse-driving
B043
Input
Description
State
ON
Enables torque limiting
OFF
Disables torque limiting
0 / 1
Torque limit select, Bit 1 (LSB)
0 / 1
Torque limit select, Bit 2 (MSB)
Examples: (Require input configuration—
see page 3–47. Jumper position shown is
for –xFU/-xFR models; for –xFE models,
see page 4–12.)
TH
FW
CM1
8
P24
PLC
CM1
7
TRQ2
TH
FW
CM1
8
P24
PLC
CM1
7
See I/O specs on page 4–9.
B40=00
+
Forward-driving
B041
FW
Forward-regenerating
B044
TL
5
3
1
6
4
2
TL
TRQ1
5
3
1
6
4
2