hit counter script

Toshiba L5232 Instruction Manual page 117

Electromagnetic flowmeter converter
Table of Contents

Advertisement

Changing the fixed output function
The following is an example to change the fixed output function from Fixed value output OFF to
ON and then go on to set the current output value and the pulse output value. To change the current
output value or pulse output value independently, select the following function:
Fixed current output value
Fixed pulse output value
Switch operation
N1: FIXED OUT
N1: FIXED OUT
N1: FIXED OUT
N2: FIX. CURR.
N2: FIX. CURR.
N2: FIX. CURR.
N3: FIX. PULSE
N3: FIX. PULSE
N3: FIX. PULSE
Note. If a value outside of the settable range is tried to set, the upper limit or lower limit value of the settable
range will be forcibly set.
Display example
Select N1: FIXED OUT from the setting item selection menu.
The currently set fixed value output On/Off setting appears.
2:OFF
The cursor appears.
2:OFF
Select the fixed value output: ON.
1:ON
The display blinks and the set value is displayed for
conformation.
Press
10.0 mA
disappears and then the current output set value can be
changed.
Move the cursor to the desired digit to change.
10.0 mA
Change the number of the digit.
To change other digit, press
20.0 mA
the cursor to the desired digit and change the number there.
The display blinks and the set value is displayed for
conformation.
Press
100 PPS
disappears and then the pulse output set value can be changed.
The display blinks and the set value is displayed for
conformation.
Press
100 PPS
disappears and the display returns to the condition that the
setting value is displayed.
Returns to the menu of setting item selection.
- 116 -
N2: FIX CURR
N3: FIX PULSE
Description
again to write the data. The cursor
MENU/ENT
again to write the data. The cursor
MENU/ENT
again to write the data. Then the cursor
MENU/ENT
6F8A0917
under this condition to move

Advertisement

Table of Contents
loading

Table of Contents