Summary of Contents for Honeywell Pneumatic Controls

  • Page 1 Pneumatic Controls Manual Catalog, Cross-Reference, Engineering Guide...
  • Page 2 Honeywell Technical Support: 888-516-9347 Honeywell Customer Web-site: customer.honeywell.com Technical data can be accessed via: customer.honeywell.com/Pneumatics customer.honeywell.com 70-6925...
  • Page 3: Table Of Contents

    Table of Contents Humidistats and Thermostats HP970 Pneumatic Humidistat ........... TP971 Pneumatic Day/Night Thermostat ......HP972 Pneumatic Humidistat ........... TP972 Pneumatic Heating/Cooling Thermostat ....Humidistat Cover Assemblies ........... TP973 Pneumatic Thermostat ......... Humidistat Accessories ............ TP975 Pneumatic Diffuser Thermostat ......Replacement Parts ............
  • Page 4 Table of Contents Gauges for Pneumatics ............................113 Pneumatic Accessories ............................114 Pneumatic Controls Engineering Guide ......................123 Snap Acting Relay ............141 Introduction ............... 125 Definitions ................. 125 Lockout Relay ............. 141 Abbreviations ..............126 High-Pressure Selector Relay ........142 Symbols ................126 Low-Pressure Selector Relay ........
  • Page 5 VP531C......75-7251EF For more information on any of the products listed in this catalog, you can also use our web site at http:// customer.honeywell.com. The technical literature that is listed above with each model number is also available on that site.
  • Page 6 Thermostat 23 Pneumatic Fittings 122 CP980 Cross Reference 32 Cross Reference CP980 32 Limit Control 148 – Pneumatic Products 159 Load Analyzer Relay 56 Lockout Relay 141 Low-Pressure Selector Relay 142 Maintenance Kit 121 Manual Positioning Switch 146 customer.honeywell.com 70-6925...
  • Page 7 Subject Index Manual Switch 69 Relay 140 Control 149 Accessories 62 Miniature Pressure Regulator 116 Averaging 61 Minimum Position Switch 69 Capacity 58 Electric-Pneumatic 52 Hesitation 62 Nozzle-Flapper Assembly 127 High-Pressure Selector Relay 142 Load Analyzer 142 Lockout 141 Offset 125 Low-Pressure Selector 142 Positive Positioning 143 Ratio 59...
  • Page 8 Remote Bulb 5 Velocity Control Accessories 33 Replacement Parts 22 Velocity Control Replacement Parts 33 Three-pipe 11 Velocity Sensor 136 Two-pipe 6 Three-Way Mixing Valve Piping 147 Three-way Valve 98 Water Valve 96 Throttling Range Adjustment 129 Sequencing 99 customer.honeywell.com 70-6925...
  • Page 9 Humidistats and Thermostats HP970 Pneumatic Humidistat ..........................2 HP972 Pneumatic Humidistat ..........................3 Humidistat Cover Assemblies ..........................4 Humidistat Accessories ............................4 Replacement Parts ............................... 4 LP907 Airstream Insertion Pneumatic Thermostat ................... 5 LP916 Pneumatic Thermostat ..........................6 TP9600 Pneumatic Thermostat ........................... 8 TP970 Pneumatic Thermostat ..........................
  • Page 10: Hp970 Pneumatic Humidistat

    Maximum Storage Temperature: -30 to +150 F (-34 to +66 C) and HP972B Maximum Operating Pressure: 25 psi (170 kPa) 14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell & competitive pneumatic stats to TP970, TP971A, TP972, TP973, Accessories: TP974, TP9600 family; HP970, HP971 and HP972 14002362-001 Duct Sampling Chamber 14002374-004 Restrictor Block Assembly,.005 in., For TP970A-D;...
  • Page 11: Hp972 Pneumatic Humidistat

    14002430-001 Thermostat Guard 14002496-003 Nylon element assembly, with Spring 14002362-001 Duct Sampling Chamber 14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell & 14004406-124 Humidistat Cover assembly Satin Chrome with setpoint competitive pneumatic stats to TP970, TP971A, TP972, TP973, display and Honeywell logo for vertical mounting, scale range 15 to TP974, TP9600 family;...
  • Page 12: Humidistat Cover Assemblies

    Product Number Scale Range (% RH) Description Used With 14004406-124 15 to 75% RH Humidistat Cover assembly Satin Chrome with setpoint display and Honeywell logo for HP970; HP972 vertical mounting, scale range 15 to 75% RH 14004406-224 15 to 75% RH Humidistat Cover assembly Satin Chrome with setpoint display and Honeywell logo for HP970;...
  • Page 13: Lp907 Airstream Insertion Pneumatic Thermostat

    Thermostats LP907 Airstream Insertion Pneumatic Thermostat One-pipe, single setpoint, pneumatic thermostat used to provide proportional control of pneumatic valves and damper actuators in heating and air conditioning systems. Commonly used as discharge controllers for unit ventilators. • Rod and tube insertion sensing element. •...
  • Page 14: Lp916 Pneumatic Thermostat

    Typical LP916B Fan Coil Application, Heating/Cooling with Seasonal Changeover FILTER DISCHARGE AIR LP916B RETURN AIR SUM/WIN M5415 Typical LP916A Duct Mounted Heating Application COIL N.O. CW IN SUMMER N.O. BULB HW IN WINTER LP916A FILTER DISCHARGE SUPPLY RETURN AIR M5416 M5417 customer.honeywell.com 70-6925...
  • Page 15 Thermostats Application Type: Unit Ventilator Maximum Operating Pressure: 25 psi (170 kPa) Dimensions, Approximate: 4 3/4 in. high x 3 3/4 in. wide x 3 in. deep Accessories: (121 mm high x 95 mm wide x 76 mm deep) 107324A Capillary Holder Assembly for duct insertion, 8 3/8 in. long Airflow Usage: 0.022 scfm (10.4 mL/s) with 0.007 in.
  • Page 16: Tp9600 Pneumatic Thermostat

    14002913-001 .005 in. Blue Filter Restriction Assembly; Inlet: 1/4 in., 14002053-001 Back Plate Assembly Outlets: 1/4 in. and 5/32 in.; Order in Quantities of 10 14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell & 14002362-001 Duct Sampling Chamber competitive pneumatic stats to TP970, TP971A, TP972, TP973, 14002913-004 TP974, TP9600 family;...
  • Page 17: Tp970 Pneumatic Thermostat

    14003192-001 Wallplate adapter kit. Adapts HP970 or TP970 series and HP972B stats to HP900 and TP900 flush mounted and TP910 series flush or 14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell & surface mounted installations competitive pneumatic stats to TP970, TP971A, TP972, TP973, 14004447-001 Setpoint Cam Assembly for TP970A1004, A1012, TP974, TP9600 family;...
  • Page 18 **A Tradeline Kit includes a TP970 Series thermostat with either a Satin Chrome or Beige Universal Cover, Windows (horizontal (F), vertical (F) and blank) for new installations or to convert newer, small size Honeywell or competitor thermostat, not requiring a wall plate adapter.
  • Page 19: Tp971 Pneumatic Day/Night Thermostat

    Operating Temperature: 100 F maximum and HP972B Storage Temperature: 150 F maximum (66 C maximum) 14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell & Remote Bulb: No competitive pneumatic stats to TP970, TP971A, TP972, TP973, Setpoint: Day/Night TP974, TP9600 family;...
  • Page 20 **A Tradeline Kit includes a TP970 Series thermostat with either a Satin Chrome or Beige Universal Cover, Windows (horizontal (F), vertical (F) and blank) for new installations or to convert newer, small size Honeywell or competitor thermostat, not requiring a wall plate adapter.
  • Page 21: Tp972 Pneumatic Heating/Cooling Thermostat

    A1127 and HP972B 14004447-002 Setpoint Cam Assembly for TP970B1002, B1010, 14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell & B1028, B1036, B2002, B2010, B2028, B2036; TP970D; competitive pneumatic stats to TP970, TP971A, TP972, TP973, TP972A1002, A1010, A1028, A1044, A2002, A2010, A2028, A2044;...
  • Page 22 **A Tradeline Kit includes a TP970 Series thermostat with either a Satin Chrome or Beige Universal Cover, Windows (horizontal (F), vertical (F) and blank) for new installations or to convert newer, small size Honeywell or competitor thermostat, not requiring a wall plate adapter.
  • Page 23: Tp973 Pneumatic Thermostat

    14002053-001 Back Plate Assembly 14004447-001 Setpoint Cam Assembly for TP970A1004, A1012, 14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell & A1020, A1038, A1046, A1053, A1095, A2004, A2012, A2020, A2038, competitive pneumatic stats to TP970, TP971A, TP972, TP973, A2053, A2095;...
  • Page 24 **A Tradeline Kit includes a TP970 Series thermostat with either a Satin Chrome or Beige Universal Cover, Windows (horizontal (F), vertical (F) and blank) for new installations or to convert newer, small size Honeywell or competitor thermostat, not requiring a wall plate adapter.
  • Page 25: Tp975 Pneumatic Diffuser Thermostat

    Thermostats TP975 Pneumatic Diffuser Thermostat One-pipe, single temperature, low-capacity pneumatic thermostat used to provide proportional control of pneumatic valves and mixing boxes in heating and air conditioning systems. It mounts in a slot or light troffer diffuser or a return air grill. •...
  • Page 26: Pneumatic Thermostat Accessories

    TP9600 Family; HP970 Family 14002362-001 Duct Sampling Chamber TP970; TP971; TP972; TP973; TP9600 Family; HP970 Family 14002373-001 Switch over Springs 16 To 21 Psi, TP972; TP971 14002390-001 Bag assembly of screws TP970; TP971; TP972; TP973; TP9600 Family; HP970 Family customer.honeywell.com 70-6925...
  • Page 27 Description Used With 14002430-001 Thermostat Guard TP970; TP971; TP972; TP973; TP9600 Family; HP970 Family 14002573-002 Modernization Kit to convert 3 pipe Honeywell TP911C TP971C & competitive three pipe pneumatic thermostats to TP971C 14002636-001 Base for 14002362-001 Sampling Chamber 14002362-001 14002913-001 0.005 in.
  • Page 28 Stand-Off Ring for surface or flush mounting TP970; TP971; TP972; TP973; TP9600 Family; HP970 Family C8404 14004505-001 Twin elbow connector TP970; TP971; TP972; TP973; TP9600 Family; HP970 Family 14004558-001 Six inch branch tube-spring assembly TP970; TP971; TP972; TP973; TP9600 Family; HP970 Family customer.honeywell.com 70-6925...
  • Page 29 Knob and scale plate assembly with screws LP916 316016M Knob, large scale plate and hanger assembly with LP916 screws 43176655-004 Case TP937, TP938 AK3863 Honeywell Thermostat Tool Kit, TP970/TP900 HP970, HP972, TP970 AK3970 Cover for Aspirator Boxes 14002424-002 and 14002424-002; 14002424-003 14002424-003 70-6925...
  • Page 30: Pneumatic Thermostat Replacement Parts

    14002424-001 (14002421-001), 4 clips (14002422-001), 4 rivets (305835) 14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell & TP970; TP9600; TP972; HP970; competitive pneumatic stats to TP970, TP971A, TP972, HP971; TP971A; HP972; TP973; TP974 TP973, TP974, TP9600 family; HP970, HP971 and...
  • Page 31: Tp9600 Series Standard Covers

    Fahrenheit scale (60 to 90 F) Taupe Thermostat Cover Kit with thermometer and setpoint TP9600 display visible and Honeywell logo for vertical mounting. 14004910-004 Taupe Thermostat Cover with setpoint and thermometer concealed with Honeywell logo, for TP9600 vertical mounting 70-6925...
  • Page 32: Tp970 Series Standard Covers

    See Specification TP970; TP972; Thermostat Cover Kit with Thermometer Display Data sheet, Form No. TP971; TP973 and setpoint display and Honeywell logo for 77-1003 for details vertical mounting. Open setpoint slot. 14004406-111 Fahrenheit scale (60 to 90 F) Satin Chrome See Specification TP970;...
  • Page 33 40 50 60 70 M18964 14004406-123 Satin Chrome Thermostat Cover Kit with setpoint See Specification TP970; TP972; display and Honeywell logo for vertical mounting Data sheet, Form No. TP971; TP973 with Warmer/Cooler Scale. Open Setpoint slot. 77-1003 for details Cooler...
  • Page 34 Fahrenheit scale (60 to 90F), Satin chrome See Specification TP970; TP972; thermostat cover kit with thermometer display Data sheet, Form No. TP971; TP973 and Honeywell logo for vertical mounting. Closed 77-1003 for details Setpoint slot. 14004406-511 Fahrenheit scale (60 to 90F), Satin Chrome See Specification TP970;...
  • Page 35 TP971; TP973 and Honeywell logo for horizontal mounting. 77-1003 for details Open Setpoint slot. M13901 14004407-300 Beige Cover Kit with Honeywell logo for vertical See Specification TP970; TP972; mounting. Closed Setpoint slot. Data sheet, Form No. TP971; TP973; 77-1003 for details HP970;...
  • Page 36 TP971; TP973; Setpoint slot. HP970; HP972 M18967 14004878-910 Thermostat Cover Kit - Premier White includes — TP970; TP972; cover, setpoint insert cover and 6 window inserts TP971; TP973 for 60 to 90 F scale for vertical and horizontal mounting. customer.honeywell.com 70-6925...
  • Page 37: Controllers

    Controllers RP7517 Electronic-Pneumatic Transducer ......................30 CP980 Velocitrol Velocity Sensor/Controller ....................31 CP980C,D,E, and F Cross-Reference Table ....................... 32 Pneumatic Velocity Control Accessories and Replacement Parts ..............33 LP920 Remote Bulb Temperature Controllers ....................34 RP920 Pneumatic Controller ..........................35 Pneumatic Temperature Controller Accessories ....................
  • Page 38: Rp7517 Electronic-Pneumatic Transducer

    Electronic Pneumatic Transducer with direct Without cover, external for 14 to 22 gage 0.1 mA max external action and 2 to 10 Vdc at 0.1 mA max input transformer required, 24 wire transformer signal. External transformer required. Vac, 50/60 Hz, (3 wire) customer.honeywell.com 70-6925...
  • Page 39: Cp980 Velocitrol Velocity Sensor/Controller

    Velocity Sensors/Controllers CP980 Velocitrol Velocity Sensor/Controller An ultra-sensitive air velocity sensor and pneumatic controller, control pneumatic damper actuators in heating and air conditioning systems to provide constant air velocity in the duct regardless of the static pressure. • State-of-the-art design provides reliable operation. •...
  • Page 40: Cp980C,D,E, And F Cross-Reference Table

    Velocity Sensors/Controllers CP980C,D,E, and F Cross-Reference Table Replaces Honeywell Current Order Interim Matched Number Velocity Range Original Set Less Matched Set (Less Orifice) Orifice Order No. ft/min (m/s) Orifice Set Orifice (Less Orifice) (Includes Orifice) CP980C1065 None 500 (2.5) None —...
  • Page 41: Pneumatic Velocity Control Accessories And Replacement Parts

    Velocity Sensors/Controllers Pneumatic Velocity Control Accessories and Replacement Parts Product Number Description Used With 14003469-001 Replacement Diaphragm RP980 14003514-001 Sensor for CP980E Velocitrol Velocity Control CP980E 14003617-002 Velocitrol Supply Module “B” CP980; RP980 14003642-002 Orifice Green, Velocity Range 750 ft/min (3.8 m/s) CP980 14003642-003 Orifice White, Velocity Range 1500 ft/min (7.6 m/s)
  • Page 42: Lp920 Remote Bulb Temperature Controllers

    Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell two-pipe pneumatic temperature controller. • Fahrenheit or Celsius scales for all adjustments.
  • Page 43: Rp920 Pneumatic Controller

    (P) or proportional plus integral (P+I) control of temperature, humidity, pressure, or dewpoint for heating and air conditioning systems. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell controllers. • Proportional plus integral control option minimizes offset. •...
  • Page 44: Temperature Controllers

    Acting 8.5 psi (59 kPa) BLP (does signal maximum is signal maximum is control point pneumatic not include sensor usage): Mainline Pressure Mainline Pressure adjustment controller 0.046 scfm (21.7 mL/s) minus 1/2 psi minus 7 kPa capability. customer.honeywell.com 70-6925...
  • Page 45: Pneumatic Temperature Controller Accessories

    Temperature Controllers Pneumatic Temperature Controller Accessories Product Number Description Used With 14000786-001 Receiver Gauge, 25 F-125 F scale, 1 1/2 in. diameter, 1/8 in. NPT connection RP920; 14000786-002 Receiver Gauge, -5 to 55 C scale, 1 1/2 in. diameter, 1/8 in. NPT connection RP920;...
  • Page 46: Pp901; Pp902 Pressure Reducing Valves

    Models also available including a sub-micron filter assembly and pressure gauges. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman and older Honeywell pressure reducing valves. • Built-in adjustable safety relief valve for limiting downstream pressure.
  • Page 47: Pressure Controllers

    Pressure Controllers Application Type: Pressure Reducing 804191E 2-1/2 in. diameter, panel-mounted Pneumatic Pressure Connection Size: Inlet and out air: 1/4 in. NPT (female) Air gage: 1/8 Indicating Gauge (0 to 160 psi), 1/8 in. NPT connection, +/-3% in. NPT (female) accuracy Mounting: Bracket furnished Replacement Parts:...
  • Page 48: Pp903 Pneumatic Differential Pressuretrol

    Replacement devices are available for Johnson, Powers, Robertshaw, and older Honeywell pneumatic pressure controllers. •...
  • Page 49: Pp904 Static Pressure Regulators

    One- or two-pipe, direct- or reverse-acting, low- or high-capacity controller used with pneumatic actuators to regulate static or differential pressure in central fan installations. Replacement devices are available for Johnson, Powers, Robertshaw, Barber- Colman, and older Honeywell devices. • Adjustable setpoint and throttling range (Zero and span). •...
  • Page 50: Pp905 Static Pressure Sensor

    RP908/RP920 Controllers to provide control of duct static, velocity, or differential pressure in airflow applications. Replacement devices available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Three-diaphragm design minimizes calibration shift with static pressure changes in velocity pressure applications.
  • Page 51: Pp97 Pneumatic Pressure Control

    PP97 Pneumatic Pressure Control One-pipe, pressure operated device that provides proportional control of pneumatic valves to control steam, air, noncorrosive gas, or noncorrosive liquid pressure. Replacement devices are available for Johnson, Powers, Robertshaw, and older Honeywell pneumatic pressure controllers. • Easily accessible adjustments.
  • Page 52: Uec24014 Differential Pressure Switch

    Filter cartridge kit for PP902C and PP902D. PP902C,D 14004205-002 Filter Station Assembly for PP901, PP902A or B PP901; PP902A,B 14004238-001 Static Pressure Duct Head for 1/4 in., 6 mm diameter Plastic Tubing PP904 301298B Outdoor Static Pressure Head PP904 customer.honeywell.com 70-6925...
  • Page 53: Sensors

    Sensors HP971 Pneumatic Humidity Sensor ........................46 LP914 Pneumatic Temperature Sensor ......................47 LP915 Pneumatic Temperature Sensor ......................48 TP974 Pneumatic Temperature Sensor ......................49 Pneumatic Sensor Accessories ......................... 49 Pneumatic Sensor Replacement Parts ......................49...
  • Page 54: Hp971 Pneumatic Humidity Sensor

    Mounted in Duct Sampling Chamber to 75% RH range Separately HP971A1024 1 or 2 15 to 85% RH Vertical or Horizontal Wall Mounting or Pneumatic Humidity Sensor, 15 Order Cover Mounted in Duct Sampling Chamber to 85% RH range Separately customer.honeywell.com 70-6925...
  • Page 55: Lp914 Pneumatic Temperature Sensor

    Temperature Sensors LP914 Pneumatic Temperature Sensor One-pipe, direct-acting temperature sensor used with RP908/ RP920 Controllers to provide proportional control of pneumatic valve or damper actuators. Rod and tube insertion element for duct, well, or through-the-wall mounting. • Corrosion resistant. • Continuous temperature indication available by using receiver gage.
  • Page 56: Lp915 Pneumatic Temperature Sensor

    Duct mount LP915A1051 Liquid-filled 8 7/8 ft 2.7m 0 F to 200 F -18 C to +93 C Duct mount LP915A1077 Liquid-filled 18 1/2 ft 5.6m 25 F to 125 F -4 C to +52 C Duct mount customer.honeywell.com 70-6925...
  • Page 57: Tp974 Pneumatic Temperature Sensor

    Temperature Sensors TP974 Pneumatic Temperature Sensor One- or two-pipe direct-acting temperature sensor used with RP908/RP920 Controllers to provide proportional control of pneumatic valve and damper actuators. • Plug-in air connections. • High efficiency air filter. • Bimetal element. • Continuous temperature indication available by using receiver gage. TP974A Typical Piping Application Type: Temperature Sensor Dimensions, Approximate: 3 1/4 in.
  • Page 58 70-6925...
  • Page 59: Relays

    Relays RP418, RP818 Electric/Pneumatic Relay ......................52 RP470 Pneumatic Selector Relay ........................53 RP471 Snap-Acting Pneumatic Relay ........................ 54 RP670 Pneumatic Switching Relay ........................55 RP913 Pneumatic Load Analyzer ........................56 RP922 Pneumatic Potentiometer ........................57 RP970 Pneumatic Capacity Relay ........................58 RP971 Pneumatic Ratio Relay ..........................
  • Page 60: Rp418, Rp818 Electric/Pneumatic Relay

    Electrically operated pneumatic switches used to interlock an electrical system and a pneumatic control system. Replacement devices are available for Johnson, Powers, Robertshaw, Barber- Colman, and older Honeywell devices. • Usable as a diverting relay, a selector relay, or a stop and bleed relay.
  • Page 61: Rp470 Pneumatic Selector Relay

    Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Uses diaphragm-logic technology. •...
  • Page 62: Rp471 Snap-Acting Pneumatic Relay

    (two-position) pressure change. It can also divert a supply line to one of two branches. Replacement device is available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Manually adjustable switching pressure.
  • Page 63: Rp670 Pneumatic Switching Relay

    Stop, On-Off-Auto and other multiple condition systems where control sequence is changed as conditions change. Replacement devices are available for Johnson, Powers, Robertshaw, Barber- Colman, and older Honeywell devices. • Available with either single-pole, double-throw (SPDT) or double- pole, double-throw (DPDT) switching action.
  • Page 64: Rp913 Pneumatic Load Analyzer

    PLUG PORT H OR L WHEN NOT USED. C4483 Product Number Operation Mounting Description RP913A1008 Selects highest and/or lowest branch pressure input Wall or In-line or panel Wall, In-Line or Panel Mounted Load Analyzer Relay, to operate final control elements 7 input customer.honeywell.com 70-6925...
  • Page 65: Rp922 Pneumatic Potentiometer

    A three-port pneumatic potentiometer can sum two input pressures, average two input pressures, be an adjustable flow restriction, or be an adjustable pressure supply. Replacement devices are available for Johnson, Powers, Robertshaw, Barber- Colman, and older Honeywell devices. • High efficiency integral filters for all ports. •...
  • Page 66: Rp970 Pneumatic Capacity Relay

    Temperature Range: 0 F to 140 F (-18 C to +60 C) Maximum Safe Operating Pressure: 30 psi (205 kPa) Accessories: TO ADDITIONAL ACTUATORS 14003203-003 Conversion Kit to convert Johnson, Powers, OR LONG TRANSMISSION LINE Robertshaw, Barber Coleman and older Honeywell switches C4479-1 Input Operating Pressure Product Number Operation...
  • Page 67: Rp971 Pneumatic Ratio Relay

    Output Span: 3 to 13 psi (21 to 90 kPa) ALL DAMPER ACTUATOR Accessories: SPRING RANGES 14003203-003 Conversion Kit to convert Johnson, Powers, 3-13 PSI Robertshaw, Barber Coleman and older Honeywell switches (20-90 kPa) 801629T Clip for surface mounting C4478-1 Pilot Input Span Product Number Operation...
  • Page 68: Rp972 Pneumatic Reversing Relay

    Temperature Range: 0 F to 140 F (-18 C to +60 C) N.C. THERMOSTAT Maximum Safe Operating Pressure: 30 psi (205 kPa) C4477 Accessories: 14003203-003 Conversion Kit to convert Johnson, Powers, Robertshaw, Barber Coleman and older Honeywell switches Product Number Operation Description Includes RP972A1006 Output varies inversely with input with an Wall, In-line or panel mounted Pneumatic 14003030-001, 1 1/2 in.
  • Page 69: Rp973 Pneumatic Averaging Relay

    The pneumatic averaging relay provides an output pressure equal to the average of two input pressures. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • In-line, wall or panel mounted.
  • Page 70: Rp975 Pneumatic Hesitation Relay

    OR FACE AND BYPASS DAMPER Maximum Safe Operating Pressure: 30 psi (205 kPa) Replacement Parts: 0.005 IN. RESTRICTION 14003203-003 Conversion Kit to convert Johnson, Powers, Robertshaw, Barber Coleman and older Honeywell switches RP975A RP470B ISOLATE PILOT WITH RP470B PIPED AS...
  • Page 71: Switches

    Switches CLEPAS Air Pressure Switch ..........................64 P643 Pneumatic/Electric Switch ......................... 65 P658 Pneumatic/Electric Switch ......................... 66 SP470 Pneumatic Diverting Switches ........................ 68 SP970 Pneumatic Manual or Minimum Position Switches ................69 Pneumatic Switch Replacement Parts ....................... 69 SP970 Operation ..............................70...
  • Page 72: Clepas Air Pressure Switch

    Pneumatic Airflow Differential Pressure Switch, 0.15 to 12.0 in w.c. 0.037 to 2.99 kPa Low Setpoint Range CLEPAS2200 Vertical Mount 0.15 to 12.0 in w.c. 0.037 to 2.99 kPa On/Off Pneumatic Airflow Differential Pressure Switch, High Setpoint Range customer.honeywell.com 70-6925...
  • Page 73: P643 Pneumatic/Electric Switch

    Used to convert a pneumatic signal from a controller to an electrical switching action to provide start and stop control of equipment such as fans and pumps. Replacement devices available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell pneumatic/electric switches. Adjustable setpoint. • Adjustable differential. •...
  • Page 74: P658 Pneumatic/Electric Switch

    (SPDT) to provide start and stop control of equipment such as fans and pumps. Replacement devices available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell pneumatic/ electric switches. • Models available for surface or panel mounting.
  • Page 75 Switches P658E Dimensions in inches (millimeters) P658 Typical Piping 2-7/8 (73) 1-3/4 1-1/4 (44) (32) CONTROLLER BRANCH LINE TO OTHER CONTROLLED DEVICES 3-5/16 (84) TO CONTROL SIDE OF FAN MOTOR STARTER M5436 Air Connections: Barb fitting for 1/4 in. (6 mm) O.D. plastic tubing Operating Humidity Range (% RH): 5 to 95% RH, 80 F (27C) max 15/64 wet bulb...
  • Page 76: Sp470 Pneumatic Diverting Switches

    Commonly applied on Day-Night, Summer- Winter, On-Off-Auto, or Start-Stop functions. Replacement kits are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell switches. • Available in two-position or three-position devices. •...
  • Page 77: Sp970 Pneumatic Manual Or Minimum Position Switches

    Replacement kits are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell switches. • Two spans available as shipped. Six spans with breakaway stops on knob.
  • Page 78: Sp970 Operation

    C. PILOT BUILDING BRANCH ABOVE A. BUILDING TO MINIMUM SETTING MINIMUM SETTING BRANCH BRANCH SP970C SP970C PILOT PILOT MAIN MAIN C4298A PILOT PILOT BRANCH BRANCH VENT MAIN VENT MAIN D. BALANCED AGAINST PILOT B. BALANCED AT MINIMUM SETTING C4300A customer.honeywell.com 70-6925...
  • Page 79 Damper and Valve Actuators Pneumatic Damper Actuator Torque Ratings ....................72 MP516 Pneumatic Unit Ventilator Damper Actuator ..................73 MP909D Pneumatic Damper Actuator ........................ 74 MP909E,H Pneumatic Damper Actuators ......................76 MP913 Pneumatic Variable Volume Damper Actuator ..................79 MP918A,B Pneumatic Damper Actuators ......................80 MP920 Pneumatic Damper Actuator ........................
  • Page 80: Actuators

    Torque with actuator shaft extended. The midstroke is significant only for modulating service and is based on the premise that an input pressure change no greater than 1.5 psi (10 kPa) should cause the actuator to reposition the damper. customer.honeywell.com 70-6925...
  • Page 81: Mp516 Pneumatic Unit Ventilator Damper Actuator

    Used to control the damper on unit ventilators. Can be adapted to various unit ventilator control cycles. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell unit ventilator damper actuators. • Constructed of strong zinc die castings.
  • Page 82: Mp909D Pneumatic Damper Actuator

    Used for pneumatic proportional control of variable volume terminal units and small damper. Available in various operating ranges for either individual or sequence operation with other actuators. Replacement devices are available for Johnson, Powers, Robertshaw, and older Honeywell actuator models. • Rugged ribbed aluminum body. •...
  • Page 83 Damper Actuator Diaphragm Effective Area Spring Range Stroke Product Number Air Connections sq in. sq cm (psi) (kPa) (inch) (mm) Includes MP909D1201 Barbed fitting for 3/32 3 sq in. 19.4 sq cm 3 psi to 21 kPa to 2.4 in. 61 mm Actuator only.
  • Page 84: Mp909E,H Pneumatic Damper Actuators

    The MP909E has an optional adjustable stroke feature.; The MP909H includes a positive positioner. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell actuator models. • Rolling diaphragm operated. •...
  • Page 85 Damper Actuator 26025B Damper crank arm for 3/8 in. (9.5 mm) diameter axle. 312867C Damper Crank Arm for 1/2 in. (12.7mm) diameter axle. Elongated slot for linkage connection. Slot scaled for 40-50-60-75-90 Elongated slot for linkage connection. Slot scaled for 45-60-75-90 degrees.
  • Page 86 N.C. Trunnion Main 1/4 in. barb, 10 psi span 69 kPa span mounting, positive Branch 1/4 in. barb. (5 psi spring (34 kPa positioner Actuator: included) spring combination 5/32 included) in. and 1/4 in. barb customer.honeywell.com 70-6925...
  • Page 87: Mp913 Pneumatic Variable Volume Damper Actuator

    Damper Actuator MP913 Pneumatic Variable Volume Damper Actuator Provides proportional control of variable volume dampers in small high velocity mixing boxes. Replacement devices are available for Johnson and Robertshaw devices. Suitable for direct replacement only, do not attempt to replace larger damper actuators with this unit.
  • Page 88: Mp918A,B Pneumatic Damper Actuators

    Used for proportional control of medium- to large-size dampers in HVAC systems. The MP918A,B are rolling diaphragm, piston-type actuators. The MP918A has a positive positioner. Replacement devices are available for Johnson, Powers, Robertshaw, Barber- Colman, and older Honeywell actuator models. • Rolling diaphragm operated. •...
  • Page 89 Damper Actuator Maximum Temperature Operating Range Pressure Spring Range Product Number Connections (psi) (kPa) (psi) (kPa) Includes MP918A1024 5/32 in. push-on -20 F to -29 C to 25 psi 172 kPa Positive Positive positioner 14004062-001 - External barb (Pilot), 1/4 +158 F +70 C positioner 10 psi...
  • Page 90: Mp920 Pneumatic Damper Actuator

    24.8 sq in. 160 sq cm 7.25 psi to 13 psi 50 kPa to 90 kPa 6 in. 150 mm Actuator only. No Bracket. Order positive positioner, mounting and connecting hardware separately. See Installation Instructions form no. 95-6053 customer.honeywell.com 70-6925...
  • Page 91: Pneumatic Damper Actuator Parts And Accessories

    Damper Actuator Pneumatic Damper Actuator Parts and Accessories Product Number Description Used With 14000716-001 Internal, Normally Closed, Motor Mounting Kit with Right Drive MP909E,H Ear, For MP909E and MP918. 14001213-001 MP904A and B Diaphragm MP904A,B 14002061-001 Damper Linkage Kit w/ Template MP909E,F 14002850-001 Angle Bracket 5 3/8 in, 137 mm, long, 5 in, 127 mm, wide...
  • Page 92 MP909 - Clevis, Clevis Pin and Cotter Pin Assembly MP909 314503 MP909C Replacement Diaphragm MP909C 315321 Crankarm Balljoint (with 1/4 in male threads), fits 5/16 in. MP516; MP909D,E,H; diameter pushrod MP913 315321G Crankarm and Linkage MP909A,D 315439/0062 Clevis MP909D customer.honeywell.com 70-6925...
  • Page 93 Damper Actuator Product Number Description Used With 315781 Motor shaft balljoint with 3/8 - 16 UNC female threads, fits 5/ MP909D,E,H; MP913 16 inch diameter pushrods. 315781 M11503 315782 Balljoint (9/16 in.-18 UNC) accepts 5/16 in. Pushrod MP920B AK3557 Short Clevis Bag Assembly for 3/8-16 threaded rod MP920B AK3557 M11509...
  • Page 94: Mp953C,D Pneumatic Coil Valve Actuators

    Pneumatic actuators provide proportional control of steam or hot or cold liquids in HVAC systems by operating V5011, V5013, and VGF valve assemblies. Replacement devices are available for older Honeywell actuators. • Rolling diaphragm for long life and low hysteresis.
  • Page 95: Valve Actuator

    Valve Actuator Spring Range Stroke Actuator Diameter Product Number Action Force (psi) (kPa) (in.) (inch) (mm) Includes — MP953D1107 Reverse Acting Medium 8 psi to 13 psi 55 kPa to 90 kPa 7 1/8 in. 3/4 in. 19 mm MP953D1131 Reverse Acting Medium 4 psi to 11 psi...
  • Page 96: Mp953E, F Pneumatic Coil Valve Actuators

    Pneumatic actuators provide proportional control of steam or hot or cold liquids in HVAC systems by operating V5011, V5013, and VGF valve assemblies. Replacement devices are available for older Honeywell actuators. • Rolling diaphragm for long life and low hysteresis.
  • Page 97 Valve Actuator Spring Range Stroke Actuator Diameter Product Number Action Force (psi) (kPa) (in.) (inch) (mm) Includes 311851-062 Stem Extension MP953E1384 Direct Acting Medium 4 psi to 11 psi 28 kPa to 76 kPa 8 in. 3/4 in. 19 mm Assembly and Positive Positioner with 10 psi range MP953E1400...
  • Page 98: Mp958 Pneumatic Valve Actuators

    Valve Actuator MP958 Pneumatic Valve Actuators The MP958 Pneumatic Valve Actuator is direct-acting and used only with Honeywell V5852A2xx, V5862A2xx, V5853A2xx, and V5863A2xx Terminal Unit Valves to control hot and/or chilled water. Dimensions in inches (millimeters) Actuator Type: Valve Action: Direct Acting Fail Safe Mode: Spring Return Air Connections: Barbed fitting for 1/4 in.
  • Page 99 Valve Actuator Close-off ratings SPRING RANGE IN PSI (kPa) CLOSEOFF RATINGS FOR MP958A ACTUATOR AND IRC VALVES 8 - 11 3 - 10 2 - 5 (55 - 76) (21 - 69) (14 - 35) 12 (83) 11 (76) 6 (41) 13 (90) 12 (83) 7 (48)
  • Page 100: Pneumatic Valve Actuator Parts And Accessories

    Stem Retainer for 13 in. diameter MP953A,C,E (Latches on Stem Button) MP953A,C,E (13 in.) 315020 Cup for MP953C,E (13 inch diameter) MP593C,E (13 in.) 316059A MP953B, D and F (Reverse Acting) Yoke Assembly for Support Assembly- with helicoil insert MP953B,D,F customer.honeywell.com 70-6925...
  • Page 101: Replacement Parts

    Valves VP512 Unit Vent Pneumatic Control Valve ......................94 VP513 Pneumatic Water Valve ..........................96 VP519 Two-Position Three-Way Air Valve ......................98 VP522 Pneumatic Sequencing Water Valve ...................... 99 VP525C Pneumatic Radiator Valve ........................101 VP526 Three-Way High Pressure Water Valve ....................103 VP527 Pneumatic Water Valve ..........................
  • Page 102: Vp512 Unit Vent Pneumatic Control Valve

    Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Equal percentage, high lift throttling guide provides accurate control over wide load variations.
  • Page 103 Valves Close-off Ratings at various Branchline Pressures 8 (55) 11 (76) 9 (62) 12 (83) 10 (69) 13 (90) 11 (76) 14 (97) 12 (83) 15 (103) 13 (90) 16 (110) 14 (97) 17 (117) 15 (103) (896) (69) (138) (207) (276) (345)
  • Page 104: Vp513 Pneumatic Water Valve

    Single-seated, straight-through, pneumatic valves used for proportional control of unit air conditioners using hot and/or chilled water. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Available in normally-open (A models) or normally-closed models (B models).
  • Page 105 Valves End Connection Size Capacity Close-off Spring Range Ratings at Branchline Product Number (inch) (mm) Body Pattern Valve Action (Cv) (Kv) Pressure (psi) (kPa) VP513A1048 O.D.: 7/8 in.; O.D.: 22.2 mm; Two-way, Proportional 2.5 Cv 2.16 Kv 79 psid (545 kPa) 3 psi to 21 kPa to Nominal: 3/4 in.
  • Page 106: Vp519 Two-Position Three-Way Air Valve

    VP519 Two-Position Three-Way Air Valve Two-position, three-way, pneumatic air valve used to control main airflow in large Day-Night or Summer-Winter pneumatic control systems. Replacement device is available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Spring-loaded, self-adjusting Teflon™ cone packing. •...
  • Page 107: Vp522 Pneumatic Sequencing Water Valve

    VP522 Pneumatic Sequencing Water Valve Three-pipe, sequencing, pneumatically operated water valve for controlling both hot and cold water flow in fan-coil and induction units. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Corrosion resistant. •...
  • Page 108 O.D.: 7/8 in.; O.D.: 22.2 mm; Three-way Diverting/ Port A: 4 Cv, Port A: 3.5 Kv, 15 psid at Adjustable Adjustable Nominal: Nominal: Diverting, Sequencing Port B: 3.5 Cv Port B: 3.0 Kv 13 psi 3/4 in. 19.1 mm Sequencing customer.honeywell.com 70-6925...
  • Page 109: Vp525C Pneumatic Radiator Valve

    Replacement devices are available for Johnson, Powers, Robertshaw, Barber- Colman, and older Honeywell devices. • Available in several capacities and spring ranges for various application requirements.
  • Page 110 1/2 in. 12.7 mm NPT- Angle 3 Cv 2.59 Kv 55 psid (379 kPa) at 3 psi to 21 kPa to Replacement for 2-5 psi spring is Male union 20 psi (138 kPa) 10 psi 69 kPa VP525A1127 and packed in box VP525A1135 customer.honeywell.com 70-6925...
  • Page 111: Vp526 Three-Way High Pressure Water Valve

    Three-way pneumatic mixing valve provides proportional control of hot and/or cold water in unit air conditioners and fan coil systems. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Small size permits installation where space is limited.
  • Page 112 76 kPa VP526A1118 O.D.: 1/2 in.; O.D.: 12.7 mm; 1.6 Cv 1.38 Kv 58 psid at 0 psi 50 psid at 18 psi 8 psi to 55 kPa to Nominal: 3/8 in. Nominal: 9.5 mm 11 psi 76 kPa customer.honeywell.com 70-6925...
  • Page 113: Vp527 Pneumatic Water Valve

    Normally open, single-seated, high pressure valve provides proportional control of hot and/or cold water in unit air conditioners and fan coil units. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Small size permits installation where space is limited. •...
  • Page 114 Nominal: 3/8 in. Nominal: 9.5 mm VP527A1075 O.D.: 1/2 in.; O.D.: 12.7 mm; 1.6 Cv 1.38 Kv 45 psid at 8 psi 2 psi to 5 psi 14 kPa to 34 kPa Nominal: 3/8 in. Nominal: 9.5 mm customer.honeywell.com 70-6925...
  • Page 115: Vp531C Pneumatic Terminal Unit Valve

    Normally-open, single-seated valve provides proportional control of steam or hot or cold water in terminal units. Replacement devices are available for Johnson, Powers, Robertshaw, Barber- Colman, and older Honeywell devices. • Available in several capacities and spring ranges for various application requirements.
  • Page 116 12.7 mm 2.3 Cv 1.99 Kv 70 psid at 20 psi 2 psi to 14 kPa to Replacement for 3-10 psi (with 2 to 5 psi 5 psi 34 kPa VP531A1020 and spring is spring) VP531A1038 packed in customer.honeywell.com 70-6925...
  • Page 117: Pneumatic Valve Accessories

    Valves Pneumatic Valve Accessories Product Number Description Used With 14002864-001 Valve rebuild kit for 1/2 to 3/4 in valves with Cv of 4 or less VP512 14003102-001 Replacement top assembly VP526; VP525; VP527; VP531 14003115-001 Valve rebuild kit for 1/2 in. valves with 2 Cv or less. Not for Solder Bodies. VP525A 14003116-001 Valve rebuild kit for 3/4 in.
  • Page 118: Pneumatic Valve Replacement Parts

    Disc for VP513A Valves VP513A 313744A Actuator Replacement Assembly for the VP519 Valve VP519C 314482 Stainless Steel Stem for 1/4 inch VP517A Valves VP522A; VP517A 314526 Orange Spring with Blue stripe, 3 to 10 psi, 1/2 in. stroke VP517A; VP513A; 312817T customer.honeywell.com 70-6925...
  • Page 119 Valves Product Number Description Used With 315800A O-Ring for VP513B, VP525, VP527 or VP531 Valves VP513B; VP525; VP527; VP531 315911/0021 Cup with keyhole for VP525, VP526, VP527, VP531 VP526A; VP527A; VP525A,C; VP531A,C 315913/0041 Orange Spring, 3 to 10 psi for VP525, VP526, VP527, VP531 VP526A;...
  • Page 120 70-6925...
  • Page 121: Gauges For Pneumatics

    Gauges and Accessories Gauges for Pneumatics Product Number Description 2-1/2 in. diameter, panel mount Pneumatic Receiver gauge (-40 to 160 F), +/- 2% accuracy. Replaces 14506495-001(gauge) + 14004904-001 14505846-001 2-1/2 in. diameter, panel mount Pneumatic Receiver gauge (0 to 200 F), +/- 2% accuracy. Replaces 4506495-001(gauge) + 14004904-002 14505846-002 2-1/2 in.
  • Page 122: Pneumatic Accessories

    1 1/4 in. Bonnet for V5011/V5013 V5011; V5013 14004596-004 Pneumatic indicator - 1 7/8 in. +/- 1/16 in. X 5/8 in. +/- 1/32 in. Red =energized color, black de-energized color — 14004695-002 ISD Central relay panel — 14501547-001 customer.honeywell.com 70-6925...
  • Page 123: Resistor Assembly

    Gauges and Accessories Product Number Description Used With Resistor Assembly PPK, End of Line Resistor, 1.91K Ohms Single Zone Fire Alarm Panels — 14501600-001 Resistor Assembly PPK, End of Line Resistor, 1.91K Ohms Single Zone Fire Alarm Panels — 14501600-002 Resistor Assembly PPK, End of Line Resistor, 1.91K Ohms Single Zone Fire Alarm Panels —...
  • Page 124: Miniature Pressure Regulator

    Pneumatic Fitting - 1/2 in. Plastic Ferrule (white) for use with plastic tubing and standard CCT1573 compression fittings, Pneumatic Fitting - 1/4 in. Brass Insert for Plastic Tubing, CCT1575 Pneumatic Fitting - 3/8 in. Brass Insert for Plastic Tubing, CCT1576 Pneumatic Fitting - 1/2 in. Brass Insert for Plastic Tubing, CCT1577 customer.honeywell.com 70-6925...
  • Page 125 Gauges and Accessories Product Number Description Pneumatic Fitting - 1/4 in.x1/8 in. FPT 90 Barbed Female Street Ells, CCT1589B Pneumatic Fitting - 1/4 in. Barbed x 1/8 in. NPT Male Adapter, Taped, CCT1590BT Pneumatic Fitting - 1/4 in. Barbed x 1/8 in. FPT Female Adapter, CCT1594B Pneumatic Fitting - 1/4 in.
  • Page 126 Pneumatic Fitting - 1/4 in. barbed x 1/4 in. Compression Adapter, CCT1635B Pneumatic Fitting - 5/32 in. barbed x 5/32 in. barbed x 5/32 in. barbed (brass) Straight Tee, CCT1637B Pneumatic Fitting - 1/4 in. Tubing Plug, CCT1640 customer.honeywell.com 70-6925...
  • Page 127 Gauges and Accessories Product Number Description Pneumatic Fitting - 5/32 in. barbed x 5/32 in. Brass barbed 90 Elbow, CCT1641 Pneumatic Fitting - 1/4 in. barbed x 1/4 in. barbed 90 Elbow, CCT1642 Pneumatic Fitting - 1/4 in. barbed x 5/32 in. barbed 90 Elbow CCT1643 90 degree brass elbow CCT1650...
  • Page 128 Valve Seat Removal Wrench, 2 1/8 in., for V5011 and V5013 (2 in. Valves) CCT947 Valve Seat Removal Wrench, 2 5/8 in. for V5011 and V5013 (2-1/2 in. Valves) CCT948 Valve Seat Removal Wrench, 3 1/8 in. for V5011 and V5013 (3 in. Valves) CCT949 Plastic Tube Holder CCT950 customer.honeywell.com 70-6925...
  • Page 129: Calibration Training Kit

    Gauges and Accessories Product Number Description Plastic Tube Fitting Push,. CCT951 Thermometer Calibration Tool for Pneumatic Thermostats (TP970, TP971, TP972, TP973, CCT970 TP9600 series). NOTE: The thermometer on thermostats made after 1988 may also be adjusted using a 1/8 in. allen wrench. Calibration Training Kit DSP3356 Separator Drain.
  • Page 130: Calibration Kit

    Gauges and Accessories Product Number Description Pneumatic Fittings Kit - Includes an assortment of fittings most often required for MJK100 replacement or repair of pneumatic devices. Pneumatic Calibration Kit with two 0-30 psi gauges MQP800 Static Pressure Regulator P246A1009 customer.honeywell.com 70-6925...
  • Page 131: Pneumatic Controls Engineering Guide

    Pneumatic Controls Engineering Guide Table of Contents Introduction..........................125 Definitions..........................125 Abbreviations..........................126 Symbols..........................126 Basic Pneumatic Control System..........................126 General ........................126 Air Supply and Operation ..................127 Restrictor ........................ 127 Nozzle-Flapper Assembly ..................127 Pilot Bleed System ....................127 Signal Amplifier ......................
  • Page 132 Start-Stop Control Sequence .................. 153 Supply Fan Control Sequence ................155 Return Fan Control Sequence ................155 Warm-Up/Heating Coil Control Sequence .............. 156 Mixing Damper Control Sequence ................157 Discharge Air Temperature Control Sequence ............157 Off/Failure Mode Control Sequence ................ 157 customer.honeywell.com 70-6925...
  • Page 133: Introduction

    Pneumatic control systems use compressed air to operate actuators, sensors, relays, and other control equipment. Differential: A term that applies to two-position devices. The Pneumatic controls differ from other control systems in several range through which the controlled variable must pass in ways with some distinct advantages: order to move the final control element from one to the other of its two possible positions.
  • Page 134: Abbreviations

    For example, a system designed to control the flow of water through a coil requires a control valve. The type of valve, however, depends on whether the water is intended for customer.honeywell.com 70-6925...
  • Page 135: Air Supply And Operation

    (day/night) systems and for systems designed to change from direct to reverse acting (heating/cooling), the PRV switches NOZZLE SPRING between two pressures, such as 13 and 18 psi. The maximum safe air pressure for most pneumatic controls is 25 psi. RESTRICTOR BRANCH AIR SUPPLY C1084...
  • Page 136: Signal Amplifier

    Feed and Bleed System temperature falls, the bimetal warps in the other direction (Fig. 6C). The “feed and bleed” (sometimes called “non bleed”) system of controlling branchline pressure is more complicated than the nozzle-flapper assembly but theoretically uses less air. The customer.honeywell.com 70-6925...
  • Page 137: Throttling Range Adjustment

    Basic Pneumatic Control System On a rise in temperature, the brass tube expands and draws the rod with it. The rod pulls on the flapper spring which pulls the flapper closed to the nozzle. The flapper movement decreases the air-bleed rate, which increases branchline pressure. A.
  • Page 138: Relays And Switches

    50 percent of the time, with up to twelve contaminated inlet air can cause excessive wear on piston motor starts per hour. rings. The intake filter is usually located in the equipment room with the compressor, but it may be located outdoors if clean customer.honeywell.com 70-6925...
  • Page 139: Air Drying Techniques

    Air Supply Equipment outdoor air is available. After the air is compressed, cooling and A typical summer minimum dew point application is a cold air settling actions in the tank condense some of the excess plenum. Figure 13 shows a 50F plenum application along with moisture and allow fallout of the larger oil droplets generated by winter requirements for a year-round composite.
  • Page 140: Pressure Reducing Valve Station

    The filter, high-pressure gage, high pressure relief valve, pressure reducing valve (PRV), and low-pressure gage are usually located together at one point in the system and may be mounted directly on the compressor. The most important elements are the air filter and the PRV. customer.honeywell.com 70-6925...
  • Page 141: Thermostats

    Thermostats Air Filter TWO-PRESSURE REDUCING VALVE A two-pressure reducing valve is typically set to pass 13 or 18 The air filter (Fig. 16) removes solid particulate matter and oil psi to the control system, as switched by a pilot pressure. The aerosols or mist from the control air.
  • Page 142: Controllers

    The sensing element in a humidistat is usually a band condition, thus providing modulating operation of the controlled of moisture-sensitive nylon. The nylon expands and contracts device. with changes in the relative humidity of the air. customer.honeywell.com 70-6925...
  • Page 143: Pressure Controllers

    Sensor-Controller Systems The humidistat can be used in a one-pipe or two-pipe On a decrease in static pressure, or if the static pressure sensor configuration and is available as either a bleed-type humidistat is piped for reverse action (high- and low-pressure pickups or a two-pipe capacity humidistat using a capacity amplifier.
  • Page 144: Pneumatic Sensors

    It is used in air terminal units and other air handling systems. Reverse and direct-acting models are available for normally closed and normally open dampers. customer.honeywell.com 70-6925...
  • Page 145: Actuators And Final Control Elements

    Actuators and Final Control Elements The velocity sensor measures actual velocity and does not require the conversion of velocity pressure to velocity. Although the sensor is typically used in duct air velocity applications, it can accurately sense velocities as low as 100 feet per minute. Flow-limiting orifices inserted into the sensor sampling tube can measure velocity ranges up to 3,500 feet per minute.
  • Page 146: Actuators

    F1, allowing forces F2 and F3 to push the diaphragm the diaphragm chamber, the compressed-spring pressure upward and move the valve stem toward the open position. moves the diaphragm up and the valve stem moves toward the closed position. customer.honeywell.com 70-6925...
  • Page 147 Actuators and Final Control Elements In a double-seated valve (Fig. 29), the controlled agent flows between the two seats. This placement balances the inlet BRANCH pressures between the two discs of the plug assembly and LINE reduces the actuator force needed to position the plug assembly.
  • Page 148: Dampers

    PILOT SIGNAL BELOW PILOT SIGNAL ABOVE RELAY SETPOINT RELAY SETPOINT PORTS: P= PILOT C= COMMON O= NORMALLY CONNECTED OPPOSED PARALLEL X= NORMALLY DISCONNECTED BLADES BLADES C2344 C2604 Fig. 34. Relay Port Connections. Fig. 32. Parallel- and Opposed-Blade Dampers. customer.honeywell.com 70-6925...
  • Page 149: Snap Acting Relay

    Relays and Switches Switching Relay Snap Acting Relay A switching relay requires a two-position pilot signal and is The snap acting relay is a spdt switch that provides two position available with either single-pole, double-throw (spdt) or double- switching action from a modulating signal and has an adjustable pole, double-throw (dpdt) switching action.
  • Page 150: High-Pressure Selector Relay

    The relay transmits the highest pressure signal from the thermostat in the warmest zone to a normally closed cooling valve. customer.honeywell.com 70-6925...
  • Page 151: Capacity Relay

    Relays and Switches Capacity Relay Positive-Positioning Relay The capacity relay is a direct-acting relay that isolates an input The positive-positioning relay (Fig. 44) mounts directly on a and repeats the input pressure with a higher capacity output. valve or damper actuator. The relay positions the valve or Figure 42 shows a capacity relay enabling a single bleed type damper precisely according to the branchline pressure from a thermostat to operate multiple damper actuators quickly by...
  • Page 152: Ratio Relay

    RATIO RELAY 2 6-9 PSI MIXING TO CONTROLLED DAMPERS DEVICE 3–13 PSI C2372 RATIO RELAY 3 9-12 PSI Fig. 48. Pneumatic Potentiometer as Adjustable Airflow Restrictor. COOLING VALVE 3–13 PSI C2370 Fig. 46. Ratio Relays in Sequencing Control Application. customer.honeywell.com 70-6925...
  • Page 153: Hesitation Relay

    Relays and Switches Hesitation Relay Electric-Pneumatic Relay The electric-pneumatic (E/P) relay is a two-position, three-way The hesitation relay is used with a pneumatic actuator in unit air valve. Depending on the piping connections to the ports, the ventilator applications. The output pressure goes to minimum relay performs the same functions as a simple diverting relay.
  • Page 154: Electronic-Pneumatic Transducer

    A manual positioning switch is used to position a remote valve or damper or change the setpoint of a controller. The switch takes input air from a controller and passes a preset, constant, minimum air pressure to the branch regardless of the controller customer.honeywell.com 70-6925...
  • Page 155: Pneumatic Control Combinations

    Pneumatic Control Combinations output (e.g., to provide an adjustable minimum position of an outdoor air damper). Branchline pressure from the controller to other devices connected to the controller is not affected. THERMOSTAT Figure 56 shows the switch functioning as a minimum positioning switch.
  • Page 156: Sequence Control

    8 to 13 psi spring range. Although this method lessens Fig. 61. High-Limit Control (Heating Application). precise positioning, it is usually acceptable in systems with lower pressure differentials across the valve or damper and on smaller valves and dampers. customer.honeywell.com 70-6925...
  • Page 157: Manual Switch Control

    Pneumatic Control Combinations Bleed-type, low-limit controllers can be used with pilot-bleed thermostats (Fig. 62). A restrictor installed between the DAMPER thermostat and the low-limit controller, allows the low limit ACTUATOR controller to bleed the branchline and open the valve. The MANUAL restrictor allows the limit controller to bleed air from the valve POSITIONING...
  • Page 158: Compensated Control System

    C N.C. N.O. SET 7-9 PSI SET 12-14 PSI SENSOR IN N.C. DAMPER CONDENSER CONTROLLER ACTUATOR WATER B M S C2361 DA CONTROLLER C2367 Fig. 68. Simple E/P Relay Combination. Fig. 71. Two-Speed Fan Operated by P/E Relays. customer.honeywell.com 70-6925...
  • Page 159: Pneumatic Recycling Control

    Pneumatic Control Combinations Voltage is applied to the common contact of Relay 1 from the Figure 72 shows a pneumatic-electric system that recycles normally closed contact of Relay 2. When the controller equipment when power fails. branchline pressure rises to 9 psi, the cooling tower fan is started on low speed by Relay 1 which makes common to TO LOAD SIDE WIRED TO START...
  • Page 160: Pneumatic Centralization

    This HVAC system, they are usually connected with 1/4 inch plastic panel contains pneumatic controls and may be local to the tubing. When there are many lines at extended lengths, smaller...
  • Page 161: Pneumatic Control System Example

    Pneumatic Control System Example PNEUMATIC CONTROL SYSTEM — 35,000 cfm. — 4,000 cfm outside air. EXAMPLE — 3,000 cfm exhaust air. — Variable speed drives. — Hot water coil for morning warm-up and to prevent discharge The following is an example of a typical air handling system air from getting too cold in winter.
  • Page 162 SMOKE HIGH STATIC DETECTOR TEMPERATURE PRESSURE SUPPLY RETURN THERMOSTAT CUTOUT NIGHT 'STAT X1-2 X2-2 X1-3 X2-3 FIRE EXHAUST 120 VOLT CONTROL CIRCUIT EARLY START CLOCK TIME CLOCKS OCCUPANCY CLOCK INTERVAL TIMER (AFTER HOURS) M10303 Fig. 75. Start-Stop Control. customer.honeywell.com 70-6925...
  • Page 163: Supply Fan Control Sequence

    Pneumatic Control System Example Supply Fan Control Sequence Return Fan Control Sequence Any time the Supply Fan (Fig. 76) runs, the pressure controller Static Pressure Controller PC (Fig. 77) controls the return fan with the greatest demand, Static Pressure Controller PC1 or variable speed drive to maintain space static pressure.
  • Page 164: Warm-Up/Heating Coil Control Sequence

    FROM TO COOLING TS-1 COOLING CONTROLS CONTROLS SR-1 3-8 PSI N.O. SR-3 B S M TC-2 SR-2 COOLING SIGNAL TO OPEN CONTROLS ALL INTERIOR VAV BOX DAMPERS AND START HOT WATER PUMP M10301 Fig. 78. Heating Coil Control. customer.honeywell.com 70-6925...
  • Page 165: Mixing Damper Control Sequence

    Pneumatic Control System Example Mixing Damper Control Sequence NOTE: These dampers can control in sequence also, but uni- son control positions the damper blades better for mix- Any time the AHU (Fig. 79) runs in the occupied mode with ing which is helpful during freezing periods. If the Electric-Pneumatic Relay 1EP energized, Outside Air airflow outside air is provided from an outside air shaft with an Controller P-F modulates the outside air damper toward open...
  • Page 166 70-6925...
  • Page 167: Pneumatic Product Cross Reference

    Pneumatic Product Cross Reference Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS POWERS/LANDIS & GYR NO REPLACEMENT NONE POWERS/LANDIS & GYR RP470A1003 FUNCTIONAL POWERS/LANDIS & GYR RP970A1008 FUNCTIONAL POWERS/LANDIS & GYR RP972A1006 FUNCTIONAL 2212 ROBERTSHAW NO REPLACEMENT NONE 2213...
  • Page 168: Pneumatic Product Cross Reference

    NO REPLACEMENT NONE 24799 NONE NONE 221256 NONE NONE 221257 NONE NONE 221257 NONE NONE 221618 NO REPLACEMENT NONE 230345 HONEYWELL CCT2193 DIRECT 310535 NONE NONE 310540 HONEYWELL NO REPLACEMENT NONE 310541 NO REPLACEMENT NONE 310565 NONE NONE 310588 NONE...
  • Page 169 TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS 314462 NO REPLACEMENT NONE 314483 NONE NONE 314485 NO REPLACEMENT NONE 314667 HONEYWELL NO REPLACEMENT NONE 314706 NO REPLACEMENT NONE 314810 NONE NONE 314811 NONE NONE 314959 HONEYWELL 314959A FUNCTIONAL 315005...
  • Page 170 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS 14002061-007 HONEYWELL 14002061-006 FUNCTIONAL 14002062-005 HONEYWELL NO REPLACEMENT NONE 14002066-001 HONEYWELL NO REPLACEMENT NONE 14002095-001 NONE NONE 14002424-002 NO REPLACEMENT NONE 14002424-003 NO REPLACEMENT NONE 14002465-171 HONEYWELL...
  • Page 171 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS 14003700-002 HONEYWELL 315321N FUNCTIONAL 14003700-004 HONEYWELL 315781 WITH FUNCTIONAL 14003700-004 HONEYWELL 315321 WITH FUNCTIONAL 14003700-004 HONEYWELL 14003640-001 WITH FUNCTIONAL 14003700-004 HONEYWELL 26025B FUNCTIONAL 14003820-001 HONEYWELL 315321 WITH...
  • Page 172 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS 14004459-002 NONE NONE 14004509-001 HONEYWELL 14004210-001 FUNCTIONAL 14004533-002 NONE NONE 14004559-001 HONEYWELL 14004558-001 FUNCTIONAL 14004559-001 HONEYWELL 14004558-002 FUNCTIONAL 14004599-004 NO REPLACEMENT NONE 14004625-002 NONE NONE 14004625-011 NO REPLACEMENT...
  • Page 173 TP971A2102 FUNCTIONAL 2216-536 ROBERTSHAW TP971A2102 FUNCTIONAL 2218-132 ROBERTSHAW TP972A2192 FUNCTIONAL 2218-133 ROBERTSHAW TP972A2200 FUNCTIONAL 2218-134 ROBERTSHAW TP972A2002 FUNCTIONAL 2218-142 ROBERTSHAW TP972A2192 FUNCTIONAL 2218-301 ROBERTSHAW TP972A2077 FUNCTIONAL 221846A HONEYWELL NO REPLACEMENT NONE 2218-512 ROBERTSHAW TP972A2192 FUNCTIONAL 2218-532 ROBERTSHAW TP972A2077 FUNCTIONAL 70-6925...
  • Page 174 MP909D1201 FUNCTIONAL 2472-140 ROBERTSHAW MP909D1219 FUNCTIONAL 2473-010 ROBERTSHAW MP909E1018 FUNCTIONAL 2473-020 ROBERTSHAW MP909E1083 FUNCTIONAL 2473-030 ROBERTSHAW MP909E1034 FUNCTIONAL 2473-110 ROBERTSHAW MP909E1018 FUNCTIONAL 2473-120 ROBERTSHAW MP909E1083 FUNCTIONAL 2473-140 ROBERTSHAW MP909E1174 FUNCTIONAL 2474-160 ROBERTSHAW MP909H1331 FUNCTIONAL 2474-160 ROBERTSHAW MP918A1024 FUNCTIONAL customer.honeywell.com 70-6925...
  • Page 175 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS 2560-001 ROBERTSHAW VP519C1006 FUNCTIONAL 2561-002 ROBERTSHAW VP527A1067 FUNCTIONAL 2561-004 ROBERTSHAW VP527A1075 FUNCTIONAL 2561-013 ROBERTSHAW VP513B1053 FUNCTIONAL 2563-002 ROBERTSHAW VP526A1118 FUNCTIONAL 2563-003 ROBERTSHAW VP526A1092 FUNCTIONAL 2563-005 ROBERTSHAW VP526A1050 FUNCTIONAL 2563-006 ROBERTSHAW...
  • Page 176 MP953C1000 FUNCTIONAL 2567-019 ROBERTSHAW V5011H1028 WITH FUNCTIONAL 2567-019 ROBERTSHAW MP953C1018 FUNCTIONAL 2567-020 ROBERTSHAW V5011H1028 WITH FUNCTIONAL 2567-020 ROBERTSHAW MP953E1327 FUNCTIONAL 2567-021 ROBERTSHAW V5011H1036 WITH FUNCTIONAL 2567-021 ROBERTSHAW MP953C1000 FUNCTIONAL 2567-023 ROBERTSHAW V5011H1036 WITH FUNCTIONAL 2567-023 ROBERTSHAW MP953C1018 FUNCTIONAL customer.honeywell.com 70-6925...
  • Page 177 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS 2567-024 ROBERTSHAW V5011H1036 WITH FUNCTIONAL 2567-024 ROBERTSHAW MP953E1327 FUNCTIONAL 2567-025 ROBERTSHAW V5011H1044 WITH FUNCTIONAL 2567-025 ROBERTSHAW MP953C1000 FUNCTIONAL 2567-027 ROBERTSHAW V5011H1044 WITH FUNCTIONAL 2567-027 ROBERTSHAW MP953C1018 FUNCTIONAL 2567-028 ROBERTSHAW V5011H1044...
  • Page 178 VP525A1192 FUNCTIONAL 2581-005 ROBERTSHAW VP525A1135 FUNCTIONAL 2581-006 ROBERTSHAW VP525A1127 FUNCTIONAL 2581-008 ROBERTSHAW VP525A1168 FUNCTIONAL 2581-009 ROBERTSHAW VP525A1226 FUNCTIONAL 2581-010 ROBERTSHAW VP525A1218 FUNCTIONAL 2582-002 ROBERTSHAW VP527A1059 FUNCTIONAL 2582-004 ROBERTSHAW VP527A1059 FUNCTIONAL 2582-006 ROBERTSHAW VP527A1075 FUNCTIONAL 2582-008 ROBERTSHAW VP527A1067 FUNCTIONAL customer.honeywell.com 70-6925...
  • Page 179 MIRCOSWITCH 14002695-006 FUNCTIONAL 311094B HOLDER IS PART OF 14002863-001 MERCHANDISE ASSEMBLY 311936A NONE NONE 311993A NONE NONE 313220/0062 NO REPLACEMENT NONE 313824D HONEYWELL NO REPLACEMENT NONE 314249D HONEYWELL 309389J FUNCTIONAL 314615/0034 NONE NONE 31-4854 FEDDERS T6031F1010 FUNCTIONAL 314959A NO REPLACEMENT...
  • Page 180 POWERS/LANDIS & GYR PP902C1009 FUNCTIONAL 908-049 POWERS/LANDIS & GYR PP902D1007 FUNCTIONAL A4000 JOHNSON CONTROLS PP902D1007 FUNCTIONAL A4000-127 JOHNSON CONTROLS PP902C1009 FUNCTIONAL A404A HONEYWELL P658A1013 FUNCTIONAL A421-100 JOHNSON CONTROLS AK3470B WITH FUNCTIONAL A421-100 JOHNSON CONTROLS AK3485D FUNCTIONAL AK40401 BARBER COLMAN RP670A1001 FUNCTIONAL...
  • Page 181 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS AK40603 BARBER COLMAN RP970A1008 FUNCTIONAL AK40603 BARBER COLMAN RP970A1016 FUNCTIONAL AK40605 BARBER COLMAN SP970A1005 FUNCTIONAL AK40613 BARBER COLMAN RP972A1006 FUNCTIONAL AK40613 BARBER COLMAN RP972A1030 FUNCTIONAL AK50401 BARBER COLMAN RP670A1001 FUNCTIONAL AK50401...
  • Page 182 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS POWERS/LANDIS & GYR P658A1013 FUNCTIONAL AP910A1700 HONEYWELL TP970A2053 FUNCTIONAL AP910A1718 HONEYWELL TP970A2053 FUNCTIONAL C101 JOHNSON CONTROLS RP471A1002 FUNCTIONAL C101 JOHNSON CONTROLS RP471A1010 FUNCTIONAL C104 JOHNSON CONTROLS RP973A1002...
  • Page 183 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS CCT2511 NONE NONE CCT2654C NONE NONE CCT3428 NONE NONE CCT3863 HONEYWELL AK3863 DIRECT CCT729 HONEYWELL CCT729A DIRECT CCT800 HONEYWELL MQP800 DIRECT CCT811B NONE NONE CCT817D NONE NONE...
  • Page 184 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS CP980F1001 HONEYWELL CP980F1068 WITH DIRECT CP980F1001 HONEYWELL 14003642-002 DIRECT CP980F1019 HONEYWELL CP980F1068 WITH DIRECT CP980F1019 HONEYWELL 14003642-001 DIRECT CP980F1027 HONEYWELL CP980F1068 WITH DIRECT CP980F1027 HONEYWELL 14003642-003 DIRECT...
  • Page 185 H5100 JOHNSON CONTROLS HP971A1008 FUNCTIONAL HDREMOTE POWERS/LANDIS & GYR LP916A1134 FUNCTIONAL HK18 BARBER COLMAN HP970B1007 FUNCTIONAL HKS5033 BARBER COLMAN HP971A1024 FUNCTIONAL HO9000A HONEYWELL HP970A1009 FUNCTIONAL HO9000B HONEYWELL HP970B1007 FUNCTIONAL HP2234 ROBERTSHAW HP973A1006 FUNCTIONAL HP900A HONEYWELL HP970A1009 FUNCTIONAL HP900B HONEYWELL HP970B1007...
  • Page 186 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS LO95A HONEYWELL NO REPLACEMENT NONE LO95B HONEYWELL NO REPLACEMENT NONE LO95C HONEYWELL NO REPLACEMENT NONE LO97A HONEYWELL NO REPLACEMENT NONE JOHNSON CONTROLS L4069A1078 FUNCTIONAL JOHNSON CONTROLS L4069A1060...
  • Page 187 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS LP916C1106 MIRCOSWITCH LP916C1023 FUNCTIONAL LP920A HONEYWELL NO REPLACEMENT NONE LP920B HONEYWELL NO REPLACEMENT NONE LP920B1003 MIRCOSWITCH LP920A1005 FUNCTIONAL LP920B1011 MIRCOSWITCH LP920A1013 FUNCTIONAL LP920B1029 MIRCOSWITCH LP920A1021 FUNCTIONAL LP92D...
  • Page 188 BARBER COLMAN MP918A1024 FUNCTIONAL MK4-7121 BARBER COLMAN MP918A1024 FUNCTIONAL MK7101 BARBER COLMAN MP918B1063 FUNCTIONAL MK7121 BARBER COLMAN MP918B1089 FUNCTIONAL MO516A HONEYWELL NO REPLACEMENT NONE MO900C HONEYWELL NO REPLACEMENT NONE MO904A HONEYWELL NO REPLACEMENT NONE MO904B HONEYWELL NO REPLACEMENT NONE MO906...
  • Page 189 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS MP904B1093 HONEYWELL MP918B1071 FUNCTIONAL Internal normally closed only MP904B1101 HONEYWELL MP918B1097 FUNCTIONAL Internal normally closed only MP904B1101 HONEYWELL MP918B1089 FUNCTIONAL External Only MP904B1119 HONEYWELL MP918B1014 FUNCTIONAL MP904B1127...
  • Page 190 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS HONEYWELL FUNCTIONAL For unitary applications, consult technical MP909C1310 MP918B1063 support. MP909C1336 HONEYWELL MP918B1063 FUNCTIONAL HONEYWELL FUNCTIONAL For unitary applications, consult technical MP909C1344 MP918B1089 support. HONEYWELL For unitary applications, consult technical...
  • Page 191 FUNCTIONAL P340-122 ROBERTSHAW RP920B1023 FUNCTIONAL JOHNSON CONTROLS CLEPAS2100 FUNCTIONAL P5215 JOHNSON CONTROLS PP905B1008 FUNCTIONAL P5217 JOHNSON CONTROLS PP905B1008 FUNCTIONAL P643A HONEYWELL NO REPLACEMENT NONE P658A HONEYWELL NO REPLACEMENT NONE P658A1005 HONEYWELL P658A1013 DIRECT P658A1021 HONEYWELL P658A1013 DIRECT P658A1039 HONEYWELL P658A1005...
  • Page 192 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS PO903A3X HONEYWELL NO REPLACEMENT NONE PO91 HONEYWELL NO REPLACEMENT NONE PO97 HONEYWELL NO REPLACEMENT NONE PO97A19X HONEYWELL NO REPLACEMENT NONE PO97A2X HONEYWELL NO REPLACEMENT NONE PO97A3X HONEYWELL...
  • Page 193 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS R3030 JOHNSON CONTROLS RP972A1006 FUNCTIONAL R3030 JOHNSON CONTROLS RP972A1030 FUNCTIONAL R317 JOHNSON CONTROLS PP92B1019 FUNCTIONAL R3180-1 JOHNSON CONTROLS CP981A1001 FUNCTIONAL R3180-1 JOHNSON CONTROLS CP981B1009 FUNCTIONAL R4000 JOHNSON CONTROLS SP970A1005 FUNCTIONAL R416...
  • Page 194 RP913A1008 FUNCTIONAL RL243SW POWERS/LANDIS & GYR RP471A1002 FUNCTIONAL RL782HP POWERS/LANDIS & GYR RP470A1003 FUNCTIONAL RL782HP POWERS/LANDIS & GYR RP913A1008 FUNCTIONAL RO403A HONEYWELL NO REPLACEMENT NONE RO403E HONEYWELL NO REPLACEMENT NONE RO46 HONEYWELL NO REPLACEMENT NONE RO47 HONEYWELL NO REPLACEMENT NONE...
  • Page 195 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS RP404A HONEYWELL NO REPLACEMENT NONE RP405A HONEYWELL NO REPLACEMENT NONE RP407A HONEYWELL NO REPLACEMENT NONE RP409A HONEYWELL CLEPAS2100 FUNCTIONAL RP40A00000000 ITT GENERAL CONTROLS NO REPLACEMENT NONE RP412A...
  • Page 196 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS RP818A1004 HONEYWELL NO REPLACEMENT NONE RP818A1012 HONEYWELL NO REPLACEMENT NONE RP818B HONEYWELL NO REPLACEMENT NONE RP818B1010 HONEYWELL NO REPLACEMENT NONE RP818C HONEYWELL NO REPLACEMENT NONE RP904A HONEYWELL...
  • Page 197 SP470B1008 FUNCTIONAL ROBERTSHAW SP470A1000 FUNCTIONAL ROBERTSHAW SP470B1008 FUNCTIONAL SP306XX BARBER COLMAN SP955A1046 FUNCTIONAL SP310XX BARBER COLMAN SP955A1046 FUNCTIONAL SP400 HONEYWELL NO REPLACEMENT NONE SP401A HONEYWELL NO REPLACEMENT NONE SP470A HONEYWELL NO REPLACEMENT NONE SP470A1026 HONEYWELL SP470A1000 FUNCTIONAL SP470A1034 HONEYWELL SP470A1018...
  • Page 198 POWERS/LANDIS & GYR TP970B2077 FUNCTIONAL ROBERTSHAW TP971A2029 FUNCTIONAL T23-301 ROBERTSHAW TP971A2102 FUNCTIONAL T23-3011 ROBERTSHAW TP971A2102 FUNCTIONAL ROBERTSHAW TP971A2029 FUNCTIONAL ROBERTSHAW TP971B2019 FUNCTIONAL ROBERTSHAW TP971A2029 FUNCTIONAL ROBERTSHAW TP971B2019 FUNCTIONAL ROBERTSHAW TP971A2029 FUNCTIONAL ROBERTSHAW TP971B2019 FUNCTIONAL T27-301 ROBERTSHAW TP971A2102 FUNCTIONAL customer.honeywell.com 70-6925...
  • Page 199 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS T27-3011 ROBERTSHAW TP971A2102 FUNCTIONAL T3100-2 JOHNSON CONTROLS LP916A1134 FUNCTIONAL T3100-3 JOHNSON CONTROLS LP916C1098 FUNCTIONAL T32-301 ROBERTSHAW TP972A2192 FUNCTIONAL T32-3011 ROBERTSHAW TP972A2192 FUNCTIONAL T32-501 ROBERTSHAW TP972A2192 FUNCTIONAL ROBERTSHAW TP972A2176 FUNCTIONAL T3300...
  • Page 200 JOHNSON CONTROLS RP920A1033 FUNCTIONAL T53-101 ROBERTSHAW TP974A2000 FUNCTIONAL T5312-1 JOHNSON CONTROLS RP920A1033 FUNCTIONAL T5800-1 JOHNSON CONTROLS RP920A1033 FUNCTIONAL T5800-1 JOHNSON CONTROLS RP920A1058 FUNCTIONAL T5800-2 JOHNSON CONTROLS RP920C1039 FUNCTIONAL T5800-3 JOHNSON CONTROLS RP920B1031 FUNCTIONAL T5800-3 JOHNSON CONTROLS RP920B1056 FUNCTIONAL customer.honeywell.com 70-6925...
  • Page 201 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS T5800-4 JOHNSON CONTROLS RP920D1029 FUNCTIONAL T8000-1 JOHNSON CONTROLS LP920A1039 FUNCTIONAL T8000-3 JOHNSON CONTROLS LP920A1039 FUNCTIONAL T8000-4 JOHNSON CONTROLS LP920A1005 FUNCTIONAL T8000-6 JOHNSON CONTROLS LP920A1005 FUNCTIONAL T8020 JOHNSON CONTROLS LP920A1013 FUNCTIONAL T9001-1...
  • Page 202 POWERS/LANDIS & GYR LP920A1005 FUNCTIONAL TH361D POWERS/LANDIS & GYR LP920A1021 FUNCTIONAL TH832D POWERS/LANDIS & GYR TP970A2004 FUNCTIONAL TH832DN POWERS/LANDIS & GYR TP971A2086 FUNCTIONAL TINVI800767 HONEYWELL 315781 WITH FUNCTIONAL TINVI800767 HONEYWELL 315321 WITH FUNCTIONAL TINVI800767 HONEYWELL 26026D FUNCTIONAL TK1001 BARBER COLMAN NO REPLACEMENT...
  • Page 203 BARBER COLMAN LP914A1052 FUNCTIONAL TKS9014 BARBER COLMAN LP914A1003 FUNCTIONAL TKS9014 BARBER COLMAN LP914A1243 FUNCTIONAL TKS9033 BARBER COLMAN LP914A1268 FUNCTIONAL TO300A1005 HONEYWELL NO REPLACEMENT NONE TO300A1013 HONEYWELL NO REPLACEMENT NONE TO300A1047 HONEYWELL NO REPLACEMENT NONE TO300A1054 HONEYWELL NO REPLACEMENT NONE TO300A1X-3X...
  • Page 204 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TO410A1028 HONEYWELL TP970A WITH FUNCTIONAL TO410A1028 HONEYWELL RP471A FUNCTIONAL TO410A1X-3X HONEYWELL TP970A WITH FUNCTIONAL TO410A1X-3X HONEYWELL RP471A FUNCTIONAL TO410B1000 HONEYWELL TP970A WITH FUNCTIONAL TO410B1000 HONEYWELL RP471A FUNCTIONAL...
  • Page 205 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TO900A3X HONEYWELL TP970A2053 FUNCTIONAL TO900A3X HONEYWELL TP970B2036 FUNCTIONAL TO900A49X HONEYWELL TP970A2020 NONE TO900A49X HONEYWELL TP970B2010 NONE TO900A4X HONEYWELL TP970A2053 FUNCTIONAL TO900A4X HONEYWELL TP970B2036 FUNCTIONAL TO900A50X HONEYWELL NO REPLACEMENT...
  • Page 206 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TO900A72X HONEYWELL TP970A2053 FUNCTIONAL TO900A72X HONEYWELL TP970B2036 FUNCTIONAL TO900A73X HONEYWELL TP970A2053 FUNCTIONAL TO900A73X HONEYWELL TP970B2036 FUNCTIONAL TO900A74X HONEYWELL TP970A2053 FUNCTIONAL TO900A74X HONEYWELL TP970B2036 FUNCTIONAL TO900A75X HONEYWELL TP970A2053...
  • Page 207 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TO900AX20X HONEYWELL TP970A2095 FUNCTIONAL TO900AX21X HONEYWELL TP970A2095 FUNCTIONAL TO900AX22X HONEYWELL TP970A2095 FUNCTIONAL TO900AX23X HONEYWELL TP970A2095 FUNCTIONAL TO900AX25X HONEYWELL TP970A2053 FUNCTIONAL TO900AX25X HONEYWELL TP970B2036 FUNCTIONAL TO900AX28X HONEYWELL TP970A2053...
  • Page 208 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TO900BX16X HONEYWELL TP971A2003 FUNCTIONAL TO900BX16X HONEYWELL TP970B2002 FUNCTIONAL TO900BX17X HONEYWELL TP971A2003 FUNCTIONAL TO900BX17X HONEYWELL TP970B2002 FUNCTIONAL TO900BX6X HONEYWELL TP971A2003 FUNCTIONAL TO900BX6X HONEYWELL TP970B2002 FUNCTIONAL TO900BX7X HONEYWELL TP971A2003...
  • Page 209 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TO900D19X HONEYWELL TP972A2044 FUNCTIONAL TO900D1X HONEYWELL TP972A2044 FUNCTIONAL TO900D20X HONEYWELL TP972A2044 FUNCTIONAL TO900D2X HONEYWELL TP972A2044 FUNCTIONAL TO900D3X HONEYWELL TP972A2044 FUNCTIONAL TO900D8X HONEYWELL TP972A2044 FUNCTIONAL TO900DX14X HONEYWELL TP972A2044...
  • Page 210 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TO9037X HONEYWELL TP970A2053 FUNCTIONAL TO9037X HONEYWELL TP970B2036 FUNCTIONAL TO9038X HONEYWELL TP970A2053 FUNCTIONAL TO9038X HONEYWELL TP970B2036 FUNCTIONAL TO903A HONEYWELL NO REPLACEMENT NONE TO903A1X HONEYWELL TP970A2053 FUNCTIONAL TO903A1X HONEYWELL...
  • Page 211 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TO910A24X HONEYWELL TP970A2053 FUNCTIONAL TO910A2X HONEYWELL TP970A2053 FUNCTIONAL TO910A3X HONEYWELL TP970A2053 FUNCTIONAL TO910A4X HONEYWELL TP970A2095 FUNCTIONAL TO910A5X HONEYWELL TP970A2053 FUNCTIONAL TO910A6X HONEYWELL TP970A2053 FUNCTIONAL TO910A7X HONEYWELL TP970A2053...
  • Page 212 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TO93A2X2 HONEYWELL TP970A2004 FUNCTIONAL TO93A2X2 HONEYWELL TP970A2038 FUNCTIONAL TO93A3X HONEYWELL TP970A2004 FUNCTIONAL TO93A3X HONEYWELL TP970A2038 FUNCTIONAL TO93AX4X-X17X HONEYWELL TP970A2004 FUNCTIONAL TO93AX4X-X17X HONEYWELL TP970A2038 FUNCTIONAL TO93B HONEYWELL NO REPLACEMENT...
  • Page 213 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TP900A1116 HONEYWELL NO REPLACEMENT NONE TP900A1124 HONEYWELL NO REPLACEMENT NONE TP900A1132 HONEYWELL NO REPLACEMENT NONE TP900A1140 HONEYWELL NO REPLACEMENT NONE TP900A1157 HONEYWELL NO REPLACEMENT NONE TP900A1165 HONEYWELL...
  • Page 214 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TP903A1006 HONEYWELL TP970A2053 FUNCTIONAL TP903A1006 HONEYWELL TP970B2036 FUNCTIONAL TP903A1014 HONEYWELL TP970A2053 FUNCTIONAL TP903A1014 HONEYWELL TP970B2036 FUNCTIONAL TP903A1022 HONEYWELL TP970A2053 FUNCTIONAL TP903A1022 HONEYWELL TP970B2036 FUNCTIONAL TP903A1030 HONEYWELL TP970A2053...
  • Page 215 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TP910A1536 HONEYWELL TP970A2053 FUNCTIONAL TP910A1544 HONEYWELL TP970A2053 FUNCTIONAL TP910A1577 HONEYWELL TP970A2053 FUNCTIONAL TP910A1585 HONEYWELL TP970A2053 FUNCTIONAL TP910A1593 HONEYWELL TP970A2053 FUNCTIONAL TP910A1601 HONEYWELL TP970A2053 FUNCTIONAL TP910A1619 HONEYWELL TP970A2053...
  • Page 216 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TP911A1055 HONEYWELL TP971A2045 FUNCTIONAL TP911A1063 HONEYWELL TP971A2045 FUNCTIONAL TP911A1089 HONEYWELL TP971A2045 FUNCTIONAL TP911A1105 HONEYWELL TP971A2045 FUNCTIONAL TP911A1113 HONEYWELL TP971A2045 FUNCTIONAL TP911A1121 HONEYWELL TP971A2045 FUNCTIONAL TP911A1139 HONEYWELL TP971A2045...
  • Page 217 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TP954A1046 HONEYWELL NO REPLACEMENT NONE TP954A1053 HONEYWELL TP954A1517 FUNCTIONAL TP954A1103 HONEYWELL TP954A1442 FUNCTIONAL TP954A1111 HONEYWELL TP954A1491 FUNCTIONAL TP954A1186 HONEYWELL NO REPLACEMENT NONE TP954A1285 HONEYWELL NO REPLACEMENT NONE...
  • Page 218 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TP970B1069 HONEYWELL TP970B2069 DIRECT TP970B1077 HONEYWELL TP970B2077 DIRECT TP970B2028 HONEYWELL TP970B2002 WITH DIRECT TP970B2028 HONEYWELL 14004406-111 WITH DIRECT TP970B2028 HONEYWELL 14002573-001 DIRECT TP970B2036 HONEYWELL TP970B2002 WITH DIRECT...
  • Page 219 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TP971A2169 HONEYWELL TP971A2191 FUNCTIONAL TP971A2209 HONEYWELL TP971A2003 WITH DIRECT TP971A2209 HONEYWELL 14004878-910 WITH DIRECT TP971A2209 HONEYWELL 14002373-001 DIRECT TP971A2217 HONEYWELL TP971A2003 WITH DIRECT TP971A2217 HONEYWELL 14004878-910 WITH...
  • Page 220 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TP972A2135 MIRCOSWITCH TP972A2010 FUNCTIONAL TP972A2168 HONEYWELL TP972A2002 WITH FUNCTIONAL TP972A2168 HONEYWELL 14002373-001 FUNCTIONAL TP972A2176 HONEYWELL NO REPLACEMENT NONE TP972A2200 MIRCOSWITCH TP972A2226 WITH FUNCTIONAL TP972A2200 MIRCOSWITCH 14004401-002 FUNCTIONAL...
  • Page 221 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TP973B2189 HONEYWELL TP973B2066 WITH DIRECT TP973B2189 HONEYWELL 14004878-910 DIRECT TP974A HONEYWELL NO REPLACEMENT NONE TP974A1000 HONEYWELL TP974A2000 DIRECT TP975A HONEYWELL NO REPLACEMENT NONE TP975B HONEYWELL NO REPLACEMENT...
  • Page 222 VP531A1053 FUNCTIONAL V8000-16108 ROBERTSHAW VP525A1200 FUNCTIONAL V8000-16111 ROBERTSHAW VP525A1192 FUNCTIONAL V8100-04108 ROBERTSHAW VP525A1135 FUNCTIONAL V8100-04111 ROBERTSHAW VP525A1127 FUNCTIONAL V8100-15111 ROBERTSHAW VP525A1168 FUNCTIONAL V8100-16108 ROBERTSHAW VP525A1226 FUNCTIONAL V8100-16111 ROBERTSHAW VP525A1218 FUNCTIONAL V8200-01108 ROBERTSHAW VP527A1059 FUNCTIONAL V8200-02108 ROBERTSHAW VP527A1059 FUNCTIONAL customer.honeywell.com 70-6925...
  • Page 223 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS V8200-03108 ROBERTSHAW VP527A1075 FUNCTIONAL V8200-05108 ROBERTSHAW VP527A1067 FUNCTIONAL V8300-03108 ROBERTSHAW VP526A1027 FUNCTIONAL VK1114-201-3-4 BARBER COLMAN VP525A1135 FUNCTIONAL VK1114-201-3-5 BARBER COLMAN VP525A1226 FUNCTIONAL VK1114-211-3-3 BARBER COLMAN VP525A1085 FUNCTIONAL VK1114-211-3-4 BARBER COLMAN VP525A1127...
  • Page 224 VK9332-203-4-4 BARBER COLMAN VP522A1047 FUNCTIONAL VK9332-313-4-2 BARBER COLMAN VP522B1003 FUNCTIONAL VK9332-313-4-3 BARBER COLMAN VP522B1011 FUNCTIONAL VK9332-313-4-4 BARBER COLMAN VP522B1029 FUNCTIONAL VO500A HONEYWELL VP525 FUNCTIONAL VO500A HONEYWELL VP513A FUNCTIONAL VO501A HONEYWELL VP525A FUNCTIONAL VO501A HONEYWELL VP513A FUNCTIONAL VO502C HONEYWELL NO REPLACEMENT...
  • Page 225 Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS VO54F HONEYWELL NO REPLACEMENT NONE VO55A HONEYWELL NO REPLACEMENT NONE VO55B HONEYWELL NO REPLACEMENT NONE VO55C HONEYWELL NO REPLACEMENT NONE VO56A HONEYWELL NO REPLACEMENT NONE VO56B HONEYWELL...
  • Page 226 WITH FUNCTIONAL VP525A1226 MIRCOSWITCH 316027/0042 FUNCTIONAL VP525A1408 MIRCOSWITCH VP525C1008 FUNCTIONAL VP525A1416 MIRCOSWITCH VP525C1016 DIRECT VP525C9001 VP525C FUNCTIONAL VP526A HONEYWELL NO REPLACEMENT NONE VP526A9061 NONE NONE VP527A HONEYWELL NO REPLACEMENT NONE VP531A HONEYWELL NO REPLACEMENT NONE VP531A1004 MIRCOSWITCH VP531C1000 DIRECT VP531A1012...
  • Page 227: Warranty

    WARRANTY POLICY Honeywell warrants the products in this catalog (except those parts designated on Honeywell's price lists as not covered by this warranty) to be free from defects due to workmanship or materials, under normal use and service, for the following warranty periods. Honeywell VisionPRO®, Commercial VisionPRO™, FocusPRO®, PRO 4000, PRO 3000, LineVolt™...
  • Page 228 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422-3992 Toronto, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark Printed in U.S.A. on recycled © 2007 Honeywell International Inc. paper containing at least 10% 70-6925 12-07 post-consumer paper fibers.