VP531C......75-7251EF For more information on any of the products listed in this catalog, you can also use our web site at http:// customer.honeywell.com. The technical literature that is listed above with each model number is also available on that site.
Maximum Storage Temperature: -30 to +150 F (-34 to +66 C) and HP972B Maximum Operating Pressure: 25 psi (170 kPa) 14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell & competitive pneumatic stats to TP970, TP971A, TP972, TP973, Accessories: TP974, TP9600 family; HP970, HP971 and HP972 14002362-001 Duct Sampling Chamber 14002374-004 Restrictor Block Assembly,.005 in., For TP970A-D;...
14002430-001 Thermostat Guard 14002496-003 Nylon element assembly, with Spring 14002362-001 Duct Sampling Chamber 14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell & 14004406-124 Humidistat Cover assembly Satin Chrome with setpoint competitive pneumatic stats to TP970, TP971A, TP972, TP973, display and Honeywell logo for vertical mounting, scale range 15 to TP974, TP9600 family;...
Product Number Scale Range (% RH) Description Used With 14004406-124 15 to 75% RH Humidistat Cover assembly Satin Chrome with setpoint display and Honeywell logo for HP970; HP972 vertical mounting, scale range 15 to 75% RH 14004406-224 15 to 75% RH Humidistat Cover assembly Satin Chrome with setpoint display and Honeywell logo for HP970;...
Thermostats LP907 Airstream Insertion Pneumatic Thermostat One-pipe, single setpoint, pneumatic thermostat used to provide proportional control of pneumatic valves and damper actuators in heating and air conditioning systems. Commonly used as discharge controllers for unit ventilators. • Rod and tube insertion sensing element. •...
Typical LP916B Fan Coil Application, Heating/Cooling with Seasonal Changeover FILTER DISCHARGE AIR LP916B RETURN AIR SUM/WIN M5415 Typical LP916A Duct Mounted Heating Application COIL N.O. CW IN SUMMER N.O. BULB HW IN WINTER LP916A FILTER DISCHARGE SUPPLY RETURN AIR M5416 M5417 customer.honeywell.com 70-6925...
Page 15
Thermostats Application Type: Unit Ventilator Maximum Operating Pressure: 25 psi (170 kPa) Dimensions, Approximate: 4 3/4 in. high x 3 3/4 in. wide x 3 in. deep Accessories: (121 mm high x 95 mm wide x 76 mm deep) 107324A Capillary Holder Assembly for duct insertion, 8 3/8 in. long Airflow Usage: 0.022 scfm (10.4 mL/s) with 0.007 in.
14002913-001 .005 in. Blue Filter Restriction Assembly; Inlet: 1/4 in., 14002053-001 Back Plate Assembly Outlets: 1/4 in. and 5/32 in.; Order in Quantities of 10 14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell & 14002362-001 Duct Sampling Chamber competitive pneumatic stats to TP970, TP971A, TP972, TP973, 14002913-004 TP974, TP9600 family;...
14003192-001 Wallplate adapter kit. Adapts HP970 or TP970 series and HP972B stats to HP900 and TP900 flush mounted and TP910 series flush or 14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell & surface mounted installations competitive pneumatic stats to TP970, TP971A, TP972, TP973, 14004447-001 Setpoint Cam Assembly for TP970A1004, A1012, TP974, TP9600 family;...
Page 18
**A Tradeline Kit includes a TP970 Series thermostat with either a Satin Chrome or Beige Universal Cover, Windows (horizontal (F), vertical (F) and blank) for new installations or to convert newer, small size Honeywell or competitor thermostat, not requiring a wall plate adapter.
Operating Temperature: 100 F maximum and HP972B Storage Temperature: 150 F maximum (66 C maximum) 14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell & Remote Bulb: No competitive pneumatic stats to TP970, TP971A, TP972, TP973, Setpoint: Day/Night TP974, TP9600 family;...
Page 20
**A Tradeline Kit includes a TP970 Series thermostat with either a Satin Chrome or Beige Universal Cover, Windows (horizontal (F), vertical (F) and blank) for new installations or to convert newer, small size Honeywell or competitor thermostat, not requiring a wall plate adapter.
A1127 and HP972B 14004447-002 Setpoint Cam Assembly for TP970B1002, B1010, 14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell & B1028, B1036, B2002, B2010, B2028, B2036; TP970D; competitive pneumatic stats to TP970, TP971A, TP972, TP973, TP972A1002, A1010, A1028, A1044, A2002, A2010, A2028, A2044;...
Page 22
**A Tradeline Kit includes a TP970 Series thermostat with either a Satin Chrome or Beige Universal Cover, Windows (horizontal (F), vertical (F) and blank) for new installations or to convert newer, small size Honeywell or competitor thermostat, not requiring a wall plate adapter.
14002053-001 Back Plate Assembly 14004447-001 Setpoint Cam Assembly for TP970A1004, A1012, 14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell & A1020, A1038, A1046, A1053, A1095, A2004, A2012, A2020, A2038, competitive pneumatic stats to TP970, TP971A, TP972, TP973, A2053, A2095;...
Page 24
**A Tradeline Kit includes a TP970 Series thermostat with either a Satin Chrome or Beige Universal Cover, Windows (horizontal (F), vertical (F) and blank) for new installations or to convert newer, small size Honeywell or competitor thermostat, not requiring a wall plate adapter.
Thermostats TP975 Pneumatic Diffuser Thermostat One-pipe, single temperature, low-capacity pneumatic thermostat used to provide proportional control of pneumatic valves and mixing boxes in heating and air conditioning systems. It mounts in a slot or light troffer diffuser or a return air grill. •...
TP9600 Family; HP970 Family 14002362-001 Duct Sampling Chamber TP970; TP971; TP972; TP973; TP9600 Family; HP970 Family 14002373-001 Switch over Springs 16 To 21 Psi, TP972; TP971 14002390-001 Bag assembly of screws TP970; TP971; TP972; TP973; TP9600 Family; HP970 Family customer.honeywell.com 70-6925...
Page 27
Description Used With 14002430-001 Thermostat Guard TP970; TP971; TP972; TP973; TP9600 Family; HP970 Family 14002573-002 Modernization Kit to convert 3 pipe Honeywell TP911C TP971C & competitive three pipe pneumatic thermostats to TP971C 14002636-001 Base for 14002362-001 Sampling Chamber 14002362-001 14002913-001 0.005 in.
Page 28
Stand-Off Ring for surface or flush mounting TP970; TP971; TP972; TP973; TP9600 Family; HP970 Family C8404 14004505-001 Twin elbow connector TP970; TP971; TP972; TP973; TP9600 Family; HP970 Family 14004558-001 Six inch branch tube-spring assembly TP970; TP971; TP972; TP973; TP9600 Family; HP970 Family customer.honeywell.com 70-6925...
Page 29
Knob and scale plate assembly with screws LP916 316016M Knob, large scale plate and hanger assembly with LP916 screws 43176655-004 Case TP937, TP938 AK3863 Honeywell Thermostat Tool Kit, TP970/TP900 HP970, HP972, TP970 AK3970 Cover for Aspirator Boxes 14002424-002 and 14002424-002; 14002424-003 14002424-003 70-6925...
Fahrenheit scale (60 to 90 F) Taupe Thermostat Cover Kit with thermometer and setpoint TP9600 display visible and Honeywell logo for vertical mounting. 14004910-004 Taupe Thermostat Cover with setpoint and thermometer concealed with Honeywell logo, for TP9600 vertical mounting 70-6925...
See Specification TP970; TP972; Thermostat Cover Kit with Thermometer Display Data sheet, Form No. TP971; TP973 and setpoint display and Honeywell logo for 77-1003 for details vertical mounting. Open setpoint slot. 14004406-111 Fahrenheit scale (60 to 90 F) Satin Chrome See Specification TP970;...
Page 33
40 50 60 70 M18964 14004406-123 Satin Chrome Thermostat Cover Kit with setpoint See Specification TP970; TP972; display and Honeywell logo for vertical mounting Data sheet, Form No. TP971; TP973 with Warmer/Cooler Scale. Open Setpoint slot. 77-1003 for details Cooler...
Page 34
Fahrenheit scale (60 to 90F), Satin chrome See Specification TP970; TP972; thermostat cover kit with thermometer display Data sheet, Form No. TP971; TP973 and Honeywell logo for vertical mounting. Closed 77-1003 for details Setpoint slot. 14004406-511 Fahrenheit scale (60 to 90F), Satin Chrome See Specification TP970;...
Page 35
TP971; TP973 and Honeywell logo for horizontal mounting. 77-1003 for details Open Setpoint slot. M13901 14004407-300 Beige Cover Kit with Honeywell logo for vertical See Specification TP970; TP972; mounting. Closed Setpoint slot. Data sheet, Form No. TP971; TP973; 77-1003 for details HP970;...
Page 36
TP971; TP973; Setpoint slot. HP970; HP972 M18967 14004878-910 Thermostat Cover Kit - Premier White includes — TP970; TP972; cover, setpoint insert cover and 6 window inserts TP971; TP973 for 60 to 90 F scale for vertical and horizontal mounting. customer.honeywell.com 70-6925...
Electronic Pneumatic Transducer with direct Without cover, external for 14 to 22 gage 0.1 mA max external action and 2 to 10 Vdc at 0.1 mA max input transformer required, 24 wire transformer signal. External transformer required. Vac, 50/60 Hz, (3 wire) customer.honeywell.com 70-6925...
Velocity Sensors/Controllers CP980 Velocitrol Velocity Sensor/Controller An ultra-sensitive air velocity sensor and pneumatic controller, control pneumatic damper actuators in heating and air conditioning systems to provide constant air velocity in the duct regardless of the static pressure. • State-of-the-art design provides reliable operation. •...
Velocity Sensors/Controllers CP980C,D,E, and F Cross-Reference Table Replaces Honeywell Current Order Interim Matched Number Velocity Range Original Set Less Matched Set (Less Orifice) Orifice Order No. ft/min (m/s) Orifice Set Orifice (Less Orifice) (Includes Orifice) CP980C1065 None 500 (2.5) None —...
Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell two-pipe pneumatic temperature controller. • Fahrenheit or Celsius scales for all adjustments.
(P) or proportional plus integral (P+I) control of temperature, humidity, pressure, or dewpoint for heating and air conditioning systems. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell controllers. • Proportional plus integral control option minimizes offset. •...
Acting 8.5 psi (59 kPa) BLP (does signal maximum is signal maximum is control point pneumatic not include sensor usage): Mainline Pressure Mainline Pressure adjustment controller 0.046 scfm (21.7 mL/s) minus 1/2 psi minus 7 kPa capability. customer.honeywell.com 70-6925...
Temperature Controllers Pneumatic Temperature Controller Accessories Product Number Description Used With 14000786-001 Receiver Gauge, 25 F-125 F scale, 1 1/2 in. diameter, 1/8 in. NPT connection RP920; 14000786-002 Receiver Gauge, -5 to 55 C scale, 1 1/2 in. diameter, 1/8 in. NPT connection RP920;...
Models also available including a sub-micron filter assembly and pressure gauges. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman and older Honeywell pressure reducing valves. • Built-in adjustable safety relief valve for limiting downstream pressure.
One- or two-pipe, direct- or reverse-acting, low- or high-capacity controller used with pneumatic actuators to regulate static or differential pressure in central fan installations. Replacement devices are available for Johnson, Powers, Robertshaw, Barber- Colman, and older Honeywell devices. • Adjustable setpoint and throttling range (Zero and span). •...
RP908/RP920 Controllers to provide control of duct static, velocity, or differential pressure in airflow applications. Replacement devices available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Three-diaphragm design minimizes calibration shift with static pressure changes in velocity pressure applications.
PP97 Pneumatic Pressure Control One-pipe, pressure operated device that provides proportional control of pneumatic valves to control steam, air, noncorrosive gas, or noncorrosive liquid pressure. Replacement devices are available for Johnson, Powers, Robertshaw, and older Honeywell pneumatic pressure controllers. • Easily accessible adjustments.
Filter cartridge kit for PP902C and PP902D. PP902C,D 14004205-002 Filter Station Assembly for PP901, PP902A or B PP901; PP902A,B 14004238-001 Static Pressure Duct Head for 1/4 in., 6 mm diameter Plastic Tubing PP904 301298B Outdoor Static Pressure Head PP904 customer.honeywell.com 70-6925...
Mounted in Duct Sampling Chamber to 75% RH range Separately HP971A1024 1 or 2 15 to 85% RH Vertical or Horizontal Wall Mounting or Pneumatic Humidity Sensor, 15 Order Cover Mounted in Duct Sampling Chamber to 85% RH range Separately customer.honeywell.com 70-6925...
Temperature Sensors LP914 Pneumatic Temperature Sensor One-pipe, direct-acting temperature sensor used with RP908/ RP920 Controllers to provide proportional control of pneumatic valve or damper actuators. Rod and tube insertion element for duct, well, or through-the-wall mounting. • Corrosion resistant. • Continuous temperature indication available by using receiver gage.
Duct mount LP915A1051 Liquid-filled 8 7/8 ft 2.7m 0 F to 200 F -18 C to +93 C Duct mount LP915A1077 Liquid-filled 18 1/2 ft 5.6m 25 F to 125 F -4 C to +52 C Duct mount customer.honeywell.com 70-6925...
Temperature Sensors TP974 Pneumatic Temperature Sensor One- or two-pipe direct-acting temperature sensor used with RP908/RP920 Controllers to provide proportional control of pneumatic valve and damper actuators. • Plug-in air connections. • High efficiency air filter. • Bimetal element. • Continuous temperature indication available by using receiver gage. TP974A Typical Piping Application Type: Temperature Sensor Dimensions, Approximate: 3 1/4 in.
Electrically operated pneumatic switches used to interlock an electrical system and a pneumatic control system. Replacement devices are available for Johnson, Powers, Robertshaw, Barber- Colman, and older Honeywell devices. • Usable as a diverting relay, a selector relay, or a stop and bleed relay.
(two-position) pressure change. It can also divert a supply line to one of two branches. Replacement device is available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Manually adjustable switching pressure.
Stop, On-Off-Auto and other multiple condition systems where control sequence is changed as conditions change. Replacement devices are available for Johnson, Powers, Robertshaw, Barber- Colman, and older Honeywell devices. • Available with either single-pole, double-throw (SPDT) or double- pole, double-throw (DPDT) switching action.
PLUG PORT H OR L WHEN NOT USED. C4483 Product Number Operation Mounting Description RP913A1008 Selects highest and/or lowest branch pressure input Wall or In-line or panel Wall, In-Line or Panel Mounted Load Analyzer Relay, to operate final control elements 7 input customer.honeywell.com 70-6925...
A three-port pneumatic potentiometer can sum two input pressures, average two input pressures, be an adjustable flow restriction, or be an adjustable pressure supply. Replacement devices are available for Johnson, Powers, Robertshaw, Barber- Colman, and older Honeywell devices. • High efficiency integral filters for all ports. •...
Temperature Range: 0 F to 140 F (-18 C to +60 C) Maximum Safe Operating Pressure: 30 psi (205 kPa) Accessories: TO ADDITIONAL ACTUATORS 14003203-003 Conversion Kit to convert Johnson, Powers, OR LONG TRANSMISSION LINE Robertshaw, Barber Coleman and older Honeywell switches C4479-1 Input Operating Pressure Product Number Operation...
Temperature Range: 0 F to 140 F (-18 C to +60 C) N.C. THERMOSTAT Maximum Safe Operating Pressure: 30 psi (205 kPa) C4477 Accessories: 14003203-003 Conversion Kit to convert Johnson, Powers, Robertshaw, Barber Coleman and older Honeywell switches Product Number Operation Description Includes RP972A1006 Output varies inversely with input with an Wall, In-line or panel mounted Pneumatic 14003030-001, 1 1/2 in.
The pneumatic averaging relay provides an output pressure equal to the average of two input pressures. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • In-line, wall or panel mounted.
OR FACE AND BYPASS DAMPER Maximum Safe Operating Pressure: 30 psi (205 kPa) Replacement Parts: 0.005 IN. RESTRICTION 14003203-003 Conversion Kit to convert Johnson, Powers, Robertshaw, Barber Coleman and older Honeywell switches RP975A RP470B ISOLATE PILOT WITH RP470B PIPED AS...
Pneumatic Airflow Differential Pressure Switch, 0.15 to 12.0 in w.c. 0.037 to 2.99 kPa Low Setpoint Range CLEPAS2200 Vertical Mount 0.15 to 12.0 in w.c. 0.037 to 2.99 kPa On/Off Pneumatic Airflow Differential Pressure Switch, High Setpoint Range customer.honeywell.com 70-6925...
Used to convert a pneumatic signal from a controller to an electrical switching action to provide start and stop control of equipment such as fans and pumps. Replacement devices available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell pneumatic/electric switches. Adjustable setpoint. • Adjustable differential. •...
(SPDT) to provide start and stop control of equipment such as fans and pumps. Replacement devices available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell pneumatic/ electric switches. • Models available for surface or panel mounting.
Page 75
Switches P658E Dimensions in inches (millimeters) P658 Typical Piping 2-7/8 (73) 1-3/4 1-1/4 (44) (32) CONTROLLER BRANCH LINE TO OTHER CONTROLLED DEVICES 3-5/16 (84) TO CONTROL SIDE OF FAN MOTOR STARTER M5436 Air Connections: Barb fitting for 1/4 in. (6 mm) O.D. plastic tubing Operating Humidity Range (% RH): 5 to 95% RH, 80 F (27C) max 15/64 wet bulb...
Commonly applied on Day-Night, Summer- Winter, On-Off-Auto, or Start-Stop functions. Replacement kits are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell switches. • Available in two-position or three-position devices. •...
Replacement kits are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell switches. • Two spans available as shipped. Six spans with breakaway stops on knob.
C. PILOT BUILDING BRANCH ABOVE A. BUILDING TO MINIMUM SETTING MINIMUM SETTING BRANCH BRANCH SP970C SP970C PILOT PILOT MAIN MAIN C4298A PILOT PILOT BRANCH BRANCH VENT MAIN VENT MAIN D. BALANCED AGAINST PILOT B. BALANCED AT MINIMUM SETTING C4300A customer.honeywell.com 70-6925...
Torque with actuator shaft extended. The midstroke is significant only for modulating service and is based on the premise that an input pressure change no greater than 1.5 psi (10 kPa) should cause the actuator to reposition the damper. customer.honeywell.com 70-6925...
Used to control the damper on unit ventilators. Can be adapted to various unit ventilator control cycles. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell unit ventilator damper actuators. • Constructed of strong zinc die castings.
Used for pneumatic proportional control of variable volume terminal units and small damper. Available in various operating ranges for either individual or sequence operation with other actuators. Replacement devices are available for Johnson, Powers, Robertshaw, and older Honeywell actuator models. • Rugged ribbed aluminum body. •...
Page 83
Damper Actuator Diaphragm Effective Area Spring Range Stroke Product Number Air Connections sq in. sq cm (psi) (kPa) (inch) (mm) Includes MP909D1201 Barbed fitting for 3/32 3 sq in. 19.4 sq cm 3 psi to 21 kPa to 2.4 in. 61 mm Actuator only.
The MP909E has an optional adjustable stroke feature.; The MP909H includes a positive positioner. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell actuator models. • Rolling diaphragm operated. •...
Page 85
Damper Actuator 26025B Damper crank arm for 3/8 in. (9.5 mm) diameter axle. 312867C Damper Crank Arm for 1/2 in. (12.7mm) diameter axle. Elongated slot for linkage connection. Slot scaled for 40-50-60-75-90 Elongated slot for linkage connection. Slot scaled for 45-60-75-90 degrees.
Page 86
N.C. Trunnion Main 1/4 in. barb, 10 psi span 69 kPa span mounting, positive Branch 1/4 in. barb. (5 psi spring (34 kPa positioner Actuator: included) spring combination 5/32 included) in. and 1/4 in. barb customer.honeywell.com 70-6925...
Damper Actuator MP913 Pneumatic Variable Volume Damper Actuator Provides proportional control of variable volume dampers in small high velocity mixing boxes. Replacement devices are available for Johnson and Robertshaw devices. Suitable for direct replacement only, do not attempt to replace larger damper actuators with this unit.
Used for proportional control of medium- to large-size dampers in HVAC systems. The MP918A,B are rolling diaphragm, piston-type actuators. The MP918A has a positive positioner. Replacement devices are available for Johnson, Powers, Robertshaw, Barber- Colman, and older Honeywell actuator models. • Rolling diaphragm operated. •...
Page 89
Damper Actuator Maximum Temperature Operating Range Pressure Spring Range Product Number Connections (psi) (kPa) (psi) (kPa) Includes MP918A1024 5/32 in. push-on -20 F to -29 C to 25 psi 172 kPa Positive Positive positioner 14004062-001 - External barb (Pilot), 1/4 +158 F +70 C positioner 10 psi...
24.8 sq in. 160 sq cm 7.25 psi to 13 psi 50 kPa to 90 kPa 6 in. 150 mm Actuator only. No Bracket. Order positive positioner, mounting and connecting hardware separately. See Installation Instructions form no. 95-6053 customer.honeywell.com 70-6925...
Damper Actuator Pneumatic Damper Actuator Parts and Accessories Product Number Description Used With 14000716-001 Internal, Normally Closed, Motor Mounting Kit with Right Drive MP909E,H Ear, For MP909E and MP918. 14001213-001 MP904A and B Diaphragm MP904A,B 14002061-001 Damper Linkage Kit w/ Template MP909E,F 14002850-001 Angle Bracket 5 3/8 in, 137 mm, long, 5 in, 127 mm, wide...
Page 92
MP909 - Clevis, Clevis Pin and Cotter Pin Assembly MP909 314503 MP909C Replacement Diaphragm MP909C 315321 Crankarm Balljoint (with 1/4 in male threads), fits 5/16 in. MP516; MP909D,E,H; diameter pushrod MP913 315321G Crankarm and Linkage MP909A,D 315439/0062 Clevis MP909D customer.honeywell.com 70-6925...
Page 93
Damper Actuator Product Number Description Used With 315781 Motor shaft balljoint with 3/8 - 16 UNC female threads, fits 5/ MP909D,E,H; MP913 16 inch diameter pushrods. 315781 M11503 315782 Balljoint (9/16 in.-18 UNC) accepts 5/16 in. Pushrod MP920B AK3557 Short Clevis Bag Assembly for 3/8-16 threaded rod MP920B AK3557 M11509...
Pneumatic actuators provide proportional control of steam or hot or cold liquids in HVAC systems by operating V5011, V5013, and VGF valve assemblies. Replacement devices are available for older Honeywell actuators. • Rolling diaphragm for long life and low hysteresis.
Valve Actuator Spring Range Stroke Actuator Diameter Product Number Action Force (psi) (kPa) (in.) (inch) (mm) Includes — MP953D1107 Reverse Acting Medium 8 psi to 13 psi 55 kPa to 90 kPa 7 1/8 in. 3/4 in. 19 mm MP953D1131 Reverse Acting Medium 4 psi to 11 psi...
Pneumatic actuators provide proportional control of steam or hot or cold liquids in HVAC systems by operating V5011, V5013, and VGF valve assemblies. Replacement devices are available for older Honeywell actuators. • Rolling diaphragm for long life and low hysteresis.
Page 97
Valve Actuator Spring Range Stroke Actuator Diameter Product Number Action Force (psi) (kPa) (in.) (inch) (mm) Includes 311851-062 Stem Extension MP953E1384 Direct Acting Medium 4 psi to 11 psi 28 kPa to 76 kPa 8 in. 3/4 in. 19 mm Assembly and Positive Positioner with 10 psi range MP953E1400...
Valve Actuator MP958 Pneumatic Valve Actuators The MP958 Pneumatic Valve Actuator is direct-acting and used only with Honeywell V5852A2xx, V5862A2xx, V5853A2xx, and V5863A2xx Terminal Unit Valves to control hot and/or chilled water. Dimensions in inches (millimeters) Actuator Type: Valve Action: Direct Acting Fail Safe Mode: Spring Return Air Connections: Barbed fitting for 1/4 in.
Page 99
Valve Actuator Close-off ratings SPRING RANGE IN PSI (kPa) CLOSEOFF RATINGS FOR MP958A ACTUATOR AND IRC VALVES 8 - 11 3 - 10 2 - 5 (55 - 76) (21 - 69) (14 - 35) 12 (83) 11 (76) 6 (41) 13 (90) 12 (83) 7 (48)
Stem Retainer for 13 in. diameter MP953A,C,E (Latches on Stem Button) MP953A,C,E (13 in.) 315020 Cup for MP953C,E (13 inch diameter) MP593C,E (13 in.) 316059A MP953B, D and F (Reverse Acting) Yoke Assembly for Support Assembly- with helicoil insert MP953B,D,F customer.honeywell.com 70-6925...
Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Equal percentage, high lift throttling guide provides accurate control over wide load variations.
Single-seated, straight-through, pneumatic valves used for proportional control of unit air conditioners using hot and/or chilled water. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Available in normally-open (A models) or normally-closed models (B models).
Page 105
Valves End Connection Size Capacity Close-off Spring Range Ratings at Branchline Product Number (inch) (mm) Body Pattern Valve Action (Cv) (Kv) Pressure (psi) (kPa) VP513A1048 O.D.: 7/8 in.; O.D.: 22.2 mm; Two-way, Proportional 2.5 Cv 2.16 Kv 79 psid (545 kPa) 3 psi to 21 kPa to Nominal: 3/4 in.
VP519 Two-Position Three-Way Air Valve Two-position, three-way, pneumatic air valve used to control main airflow in large Day-Night or Summer-Winter pneumatic control systems. Replacement device is available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Spring-loaded, self-adjusting Teflon™ cone packing. •...
VP522 Pneumatic Sequencing Water Valve Three-pipe, sequencing, pneumatically operated water valve for controlling both hot and cold water flow in fan-coil and induction units. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Corrosion resistant. •...
Page 108
O.D.: 7/8 in.; O.D.: 22.2 mm; Three-way Diverting/ Port A: 4 Cv, Port A: 3.5 Kv, 15 psid at Adjustable Adjustable Nominal: Nominal: Diverting, Sequencing Port B: 3.5 Cv Port B: 3.0 Kv 13 psi 3/4 in. 19.1 mm Sequencing customer.honeywell.com 70-6925...
Replacement devices are available for Johnson, Powers, Robertshaw, Barber- Colman, and older Honeywell devices. • Available in several capacities and spring ranges for various application requirements.
Page 110
1/2 in. 12.7 mm NPT- Angle 3 Cv 2.59 Kv 55 psid (379 kPa) at 3 psi to 21 kPa to Replacement for 2-5 psi spring is Male union 20 psi (138 kPa) 10 psi 69 kPa VP525A1127 and packed in box VP525A1135 customer.honeywell.com 70-6925...
Three-way pneumatic mixing valve provides proportional control of hot and/or cold water in unit air conditioners and fan coil systems. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Small size permits installation where space is limited.
Page 112
76 kPa VP526A1118 O.D.: 1/2 in.; O.D.: 12.7 mm; 1.6 Cv 1.38 Kv 58 psid at 0 psi 50 psid at 18 psi 8 psi to 55 kPa to Nominal: 3/8 in. Nominal: 9.5 mm 11 psi 76 kPa customer.honeywell.com 70-6925...
Normally open, single-seated, high pressure valve provides proportional control of hot and/or cold water in unit air conditioners and fan coil units. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices. • Small size permits installation where space is limited. •...
Page 114
Nominal: 3/8 in. Nominal: 9.5 mm VP527A1075 O.D.: 1/2 in.; O.D.: 12.7 mm; 1.6 Cv 1.38 Kv 45 psid at 8 psi 2 psi to 5 psi 14 kPa to 34 kPa Nominal: 3/8 in. Nominal: 9.5 mm customer.honeywell.com 70-6925...
Normally-open, single-seated valve provides proportional control of steam or hot or cold water in terminal units. Replacement devices are available for Johnson, Powers, Robertshaw, Barber- Colman, and older Honeywell devices. • Available in several capacities and spring ranges for various application requirements.
Page 116
12.7 mm 2.3 Cv 1.99 Kv 70 psid at 20 psi 2 psi to 14 kPa to Replacement for 3-10 psi (with 2 to 5 psi 5 psi 34 kPa VP531A1020 and spring is spring) VP531A1038 packed in customer.honeywell.com 70-6925...
Valves Pneumatic Valve Accessories Product Number Description Used With 14002864-001 Valve rebuild kit for 1/2 to 3/4 in valves with Cv of 4 or less VP512 14003102-001 Replacement top assembly VP526; VP525; VP527; VP531 14003115-001 Valve rebuild kit for 1/2 in. valves with 2 Cv or less. Not for Solder Bodies. VP525A 14003116-001 Valve rebuild kit for 3/4 in.
Disc for VP513A Valves VP513A 313744A Actuator Replacement Assembly for the VP519 Valve VP519C 314482 Stainless Steel Stem for 1/4 inch VP517A Valves VP522A; VP517A 314526 Orange Spring with Blue stripe, 3 to 10 psi, 1/2 in. stroke VP517A; VP513A; 312817T customer.honeywell.com 70-6925...
Page 119
Valves Product Number Description Used With 315800A O-Ring for VP513B, VP525, VP527 or VP531 Valves VP513B; VP525; VP527; VP531 315911/0021 Cup with keyhole for VP525, VP526, VP527, VP531 VP526A; VP527A; VP525A,C; VP531A,C 315913/0041 Orange Spring, 3 to 10 psi for VP525, VP526, VP527, VP531 VP526A;...
1 1/4 in. Bonnet for V5011/V5013 V5011; V5013 14004596-004 Pneumatic indicator - 1 7/8 in. +/- 1/16 in. X 5/8 in. +/- 1/32 in. Red =energized color, black de-energized color — 14004695-002 ISD Central relay panel — 14501547-001 customer.honeywell.com 70-6925...
Gauges and Accessories Product Number Description Used With Resistor Assembly PPK, End of Line Resistor, 1.91K Ohms Single Zone Fire Alarm Panels — 14501600-001 Resistor Assembly PPK, End of Line Resistor, 1.91K Ohms Single Zone Fire Alarm Panels — 14501600-002 Resistor Assembly PPK, End of Line Resistor, 1.91K Ohms Single Zone Fire Alarm Panels —...
Pneumatic Fitting - 1/2 in. Plastic Ferrule (white) for use with plastic tubing and standard CCT1573 compression fittings, Pneumatic Fitting - 1/4 in. Brass Insert for Plastic Tubing, CCT1575 Pneumatic Fitting - 3/8 in. Brass Insert for Plastic Tubing, CCT1576 Pneumatic Fitting - 1/2 in. Brass Insert for Plastic Tubing, CCT1577 customer.honeywell.com 70-6925...
Page 125
Gauges and Accessories Product Number Description Pneumatic Fitting - 1/4 in.x1/8 in. FPT 90 Barbed Female Street Ells, CCT1589B Pneumatic Fitting - 1/4 in. Barbed x 1/8 in. NPT Male Adapter, Taped, CCT1590BT Pneumatic Fitting - 1/4 in. Barbed x 1/8 in. FPT Female Adapter, CCT1594B Pneumatic Fitting - 1/4 in.
Page 126
Pneumatic Fitting - 1/4 in. barbed x 1/4 in. Compression Adapter, CCT1635B Pneumatic Fitting - 5/32 in. barbed x 5/32 in. barbed x 5/32 in. barbed (brass) Straight Tee, CCT1637B Pneumatic Fitting - 1/4 in. Tubing Plug, CCT1640 customer.honeywell.com 70-6925...
Page 127
Gauges and Accessories Product Number Description Pneumatic Fitting - 5/32 in. barbed x 5/32 in. Brass barbed 90 Elbow, CCT1641 Pneumatic Fitting - 1/4 in. barbed x 1/4 in. barbed 90 Elbow, CCT1642 Pneumatic Fitting - 1/4 in. barbed x 5/32 in. barbed 90 Elbow CCT1643 90 degree brass elbow CCT1650...
Page 128
Valve Seat Removal Wrench, 2 1/8 in., for V5011 and V5013 (2 in. Valves) CCT947 Valve Seat Removal Wrench, 2 5/8 in. for V5011 and V5013 (2-1/2 in. Valves) CCT948 Valve Seat Removal Wrench, 3 1/8 in. for V5011 and V5013 (3 in. Valves) CCT949 Plastic Tube Holder CCT950 customer.honeywell.com 70-6925...
Gauges and Accessories Product Number Description Plastic Tube Fitting Push,. CCT951 Thermometer Calibration Tool for Pneumatic Thermostats (TP970, TP971, TP972, TP973, CCT970 TP9600 series). NOTE: The thermometer on thermostats made after 1988 may also be adjusted using a 1/8 in. allen wrench. Calibration Training Kit DSP3356 Separator Drain.
Gauges and Accessories Product Number Description Pneumatic Fittings Kit - Includes an assortment of fittings most often required for MJK100 replacement or repair of pneumatic devices. Pneumatic Calibration Kit with two 0-30 psi gauges MQP800 Static Pressure Regulator P246A1009 customer.honeywell.com 70-6925...
Pneumatic Controls Engineering Guide Table of Contents Introduction..........................125 Definitions..........................125 Abbreviations..........................126 Symbols..........................126 Basic Pneumatic Control System..........................126 General ........................126 Air Supply and Operation ..................127 Restrictor ........................ 127 Nozzle-Flapper Assembly ..................127 Pilot Bleed System ....................127 Signal Amplifier ......................
Page 132
Start-Stop Control Sequence .................. 153 Supply Fan Control Sequence ................155 Return Fan Control Sequence ................155 Warm-Up/Heating Coil Control Sequence .............. 156 Mixing Damper Control Sequence ................157 Discharge Air Temperature Control Sequence ............157 Off/Failure Mode Control Sequence ................ 157 customer.honeywell.com 70-6925...
Pneumatic control systems use compressed air to operate actuators, sensors, relays, and other control equipment. Differential: A term that applies to two-position devices. The Pneumatic controls differ from other control systems in several range through which the controlled variable must pass in ways with some distinct advantages: order to move the final control element from one to the other of its two possible positions.
For example, a system designed to control the flow of water through a coil requires a control valve. The type of valve, however, depends on whether the water is intended for customer.honeywell.com 70-6925...
(day/night) systems and for systems designed to change from direct to reverse acting (heating/cooling), the PRV switches NOZZLE SPRING between two pressures, such as 13 and 18 psi. The maximum safe air pressure for most pneumatic controls is 25 psi. RESTRICTOR BRANCH AIR SUPPLY C1084...
Feed and Bleed System temperature falls, the bimetal warps in the other direction (Fig. 6C). The “feed and bleed” (sometimes called “non bleed”) system of controlling branchline pressure is more complicated than the nozzle-flapper assembly but theoretically uses less air. The customer.honeywell.com 70-6925...
Basic Pneumatic Control System On a rise in temperature, the brass tube expands and draws the rod with it. The rod pulls on the flapper spring which pulls the flapper closed to the nozzle. The flapper movement decreases the air-bleed rate, which increases branchline pressure. A.
50 percent of the time, with up to twelve contaminated inlet air can cause excessive wear on piston motor starts per hour. rings. The intake filter is usually located in the equipment room with the compressor, but it may be located outdoors if clean customer.honeywell.com 70-6925...
Air Supply Equipment outdoor air is available. After the air is compressed, cooling and A typical summer minimum dew point application is a cold air settling actions in the tank condense some of the excess plenum. Figure 13 shows a 50F plenum application along with moisture and allow fallout of the larger oil droplets generated by winter requirements for a year-round composite.
The filter, high-pressure gage, high pressure relief valve, pressure reducing valve (PRV), and low-pressure gage are usually located together at one point in the system and may be mounted directly on the compressor. The most important elements are the air filter and the PRV. customer.honeywell.com 70-6925...
Thermostats Air Filter TWO-PRESSURE REDUCING VALVE A two-pressure reducing valve is typically set to pass 13 or 18 The air filter (Fig. 16) removes solid particulate matter and oil psi to the control system, as switched by a pilot pressure. The aerosols or mist from the control air.
The sensing element in a humidistat is usually a band condition, thus providing modulating operation of the controlled of moisture-sensitive nylon. The nylon expands and contracts device. with changes in the relative humidity of the air. customer.honeywell.com 70-6925...
Sensor-Controller Systems The humidistat can be used in a one-pipe or two-pipe On a decrease in static pressure, or if the static pressure sensor configuration and is available as either a bleed-type humidistat is piped for reverse action (high- and low-pressure pickups or a two-pipe capacity humidistat using a capacity amplifier.
It is used in air terminal units and other air handling systems. Reverse and direct-acting models are available for normally closed and normally open dampers. customer.honeywell.com 70-6925...
Actuators and Final Control Elements The velocity sensor measures actual velocity and does not require the conversion of velocity pressure to velocity. Although the sensor is typically used in duct air velocity applications, it can accurately sense velocities as low as 100 feet per minute. Flow-limiting orifices inserted into the sensor sampling tube can measure velocity ranges up to 3,500 feet per minute.
F1, allowing forces F2 and F3 to push the diaphragm the diaphragm chamber, the compressed-spring pressure upward and move the valve stem toward the open position. moves the diaphragm up and the valve stem moves toward the closed position. customer.honeywell.com 70-6925...
Page 147
Actuators and Final Control Elements In a double-seated valve (Fig. 29), the controlled agent flows between the two seats. This placement balances the inlet BRANCH pressures between the two discs of the plug assembly and LINE reduces the actuator force needed to position the plug assembly.
PILOT SIGNAL BELOW PILOT SIGNAL ABOVE RELAY SETPOINT RELAY SETPOINT PORTS: P= PILOT C= COMMON O= NORMALLY CONNECTED OPPOSED PARALLEL X= NORMALLY DISCONNECTED BLADES BLADES C2344 C2604 Fig. 34. Relay Port Connections. Fig. 32. Parallel- and Opposed-Blade Dampers. customer.honeywell.com 70-6925...
Relays and Switches Switching Relay Snap Acting Relay A switching relay requires a two-position pilot signal and is The snap acting relay is a spdt switch that provides two position available with either single-pole, double-throw (spdt) or double- switching action from a modulating signal and has an adjustable pole, double-throw (dpdt) switching action.
The relay transmits the highest pressure signal from the thermostat in the warmest zone to a normally closed cooling valve. customer.honeywell.com 70-6925...
Relays and Switches Capacity Relay Positive-Positioning Relay The capacity relay is a direct-acting relay that isolates an input The positive-positioning relay (Fig. 44) mounts directly on a and repeats the input pressure with a higher capacity output. valve or damper actuator. The relay positions the valve or Figure 42 shows a capacity relay enabling a single bleed type damper precisely according to the branchline pressure from a thermostat to operate multiple damper actuators quickly by...
Relays and Switches Hesitation Relay Electric-Pneumatic Relay The electric-pneumatic (E/P) relay is a two-position, three-way The hesitation relay is used with a pneumatic actuator in unit air valve. Depending on the piping connections to the ports, the ventilator applications. The output pressure goes to minimum relay performs the same functions as a simple diverting relay.
A manual positioning switch is used to position a remote valve or damper or change the setpoint of a controller. The switch takes input air from a controller and passes a preset, constant, minimum air pressure to the branch regardless of the controller customer.honeywell.com 70-6925...
Pneumatic Control Combinations output (e.g., to provide an adjustable minimum position of an outdoor air damper). Branchline pressure from the controller to other devices connected to the controller is not affected. THERMOSTAT Figure 56 shows the switch functioning as a minimum positioning switch.
8 to 13 psi spring range. Although this method lessens Fig. 61. High-Limit Control (Heating Application). precise positioning, it is usually acceptable in systems with lower pressure differentials across the valve or damper and on smaller valves and dampers. customer.honeywell.com 70-6925...
Pneumatic Control Combinations Bleed-type, low-limit controllers can be used with pilot-bleed thermostats (Fig. 62). A restrictor installed between the DAMPER thermostat and the low-limit controller, allows the low limit ACTUATOR controller to bleed the branchline and open the valve. The MANUAL restrictor allows the limit controller to bleed air from the valve POSITIONING...
C N.C. N.O. SET 7-9 PSI SET 12-14 PSI SENSOR IN N.C. DAMPER CONDENSER CONTROLLER ACTUATOR WATER B M S C2361 DA CONTROLLER C2367 Fig. 68. Simple E/P Relay Combination. Fig. 71. Two-Speed Fan Operated by P/E Relays. customer.honeywell.com 70-6925...
Pneumatic Control Combinations Voltage is applied to the common contact of Relay 1 from the Figure 72 shows a pneumatic-electric system that recycles normally closed contact of Relay 2. When the controller equipment when power fails. branchline pressure rises to 9 psi, the cooling tower fan is started on low speed by Relay 1 which makes common to TO LOAD SIDE WIRED TO START...
This HVAC system, they are usually connected with 1/4 inch plastic panel contains pneumatic controls and may be local to the tubing. When there are many lines at extended lengths, smaller...
Pneumatic Control System Example PNEUMATIC CONTROL SYSTEM — 35,000 cfm. — 4,000 cfm outside air. EXAMPLE — 3,000 cfm exhaust air. — Variable speed drives. — Hot water coil for morning warm-up and to prevent discharge The following is an example of a typical air handling system air from getting too cold in winter.
Page 162
SMOKE HIGH STATIC DETECTOR TEMPERATURE PRESSURE SUPPLY RETURN THERMOSTAT CUTOUT NIGHT 'STAT X1-2 X2-2 X1-3 X2-3 FIRE EXHAUST 120 VOLT CONTROL CIRCUIT EARLY START CLOCK TIME CLOCKS OCCUPANCY CLOCK INTERVAL TIMER (AFTER HOURS) M10303 Fig. 75. Start-Stop Control. customer.honeywell.com 70-6925...
Pneumatic Control System Example Supply Fan Control Sequence Return Fan Control Sequence Any time the Supply Fan (Fig. 76) runs, the pressure controller Static Pressure Controller PC (Fig. 77) controls the return fan with the greatest demand, Static Pressure Controller PC1 or variable speed drive to maintain space static pressure.
FROM TO COOLING TS-1 COOLING CONTROLS CONTROLS SR-1 3-8 PSI N.O. SR-3 B S M TC-2 SR-2 COOLING SIGNAL TO OPEN CONTROLS ALL INTERIOR VAV BOX DAMPERS AND START HOT WATER PUMP M10301 Fig. 78. Heating Coil Control. customer.honeywell.com 70-6925...
Pneumatic Control System Example Mixing Damper Control Sequence NOTE: These dampers can control in sequence also, but uni- son control positions the damper blades better for mix- Any time the AHU (Fig. 79) runs in the occupied mode with ing which is helpful during freezing periods. If the Electric-Pneumatic Relay 1EP energized, Outside Air airflow outside air is provided from an outside air shaft with an Controller P-F modulates the outside air damper toward open...
Page 182
Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS POWERS/LANDIS & GYR P658A1013 FUNCTIONAL AP910A1700 HONEYWELL TP970A2053 FUNCTIONAL AP910A1718 HONEYWELL TP970A2053 FUNCTIONAL C101 JOHNSON CONTROLS RP471A1002 FUNCTIONAL C101 JOHNSON CONTROLS RP471A1010 FUNCTIONAL C104 JOHNSON CONTROLS RP973A1002...
Page 183
Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS CCT2511 NONE NONE CCT2654C NONE NONE CCT3428 NONE NONE CCT3863 HONEYWELL AK3863 DIRECT CCT729 HONEYWELL CCT729A DIRECT CCT800 HONEYWELL MQP800 DIRECT CCT811B NONE NONE CCT817D NONE NONE...
Page 184
Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS CP980F1001 HONEYWELL CP980F1068 WITH DIRECT CP980F1001 HONEYWELL 14003642-002 DIRECT CP980F1019 HONEYWELL CP980F1068 WITH DIRECT CP980F1019 HONEYWELL 14003642-001 DIRECT CP980F1027 HONEYWELL CP980F1068 WITH DIRECT CP980F1027 HONEYWELL 14003642-003 DIRECT...
Page 186
Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS LO95A HONEYWELL NO REPLACEMENT NONE LO95B HONEYWELL NO REPLACEMENT NONE LO95C HONEYWELL NO REPLACEMENT NONE LO97A HONEYWELL NO REPLACEMENT NONE JOHNSON CONTROLS L4069A1078 FUNCTIONAL JOHNSON CONTROLS L4069A1060...
Page 187
Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS LP916C1106 MIRCOSWITCH LP916C1023 FUNCTIONAL LP920A HONEYWELL NO REPLACEMENT NONE LP920B HONEYWELL NO REPLACEMENT NONE LP920B1003 MIRCOSWITCH LP920A1005 FUNCTIONAL LP920B1011 MIRCOSWITCH LP920A1013 FUNCTIONAL LP920B1029 MIRCOSWITCH LP920A1021 FUNCTIONAL LP92D...
Page 195
Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS RP404A HONEYWELL NO REPLACEMENT NONE RP405A HONEYWELL NO REPLACEMENT NONE RP407A HONEYWELL NO REPLACEMENT NONE RP409A HONEYWELL CLEPAS2100 FUNCTIONAL RP40A00000000 ITT GENERAL CONTROLS NO REPLACEMENT NONE RP412A...
Page 196
Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS RP818A1004 HONEYWELL NO REPLACEMENT NONE RP818A1012 HONEYWELL NO REPLACEMENT NONE RP818B HONEYWELL NO REPLACEMENT NONE RP818B1010 HONEYWELL NO REPLACEMENT NONE RP818C HONEYWELL NO REPLACEMENT NONE RP904A HONEYWELL...
Page 217
Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TP954A1046 HONEYWELL NO REPLACEMENT NONE TP954A1053 HONEYWELL TP954A1517 FUNCTIONAL TP954A1103 HONEYWELL TP954A1442 FUNCTIONAL TP954A1111 HONEYWELL TP954A1491 FUNCTIONAL TP954A1186 HONEYWELL NO REPLACEMENT NONE TP954A1285 HONEYWELL NO REPLACEMENT NONE...
Page 218
Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TP970B1069 HONEYWELL TP970B2069 DIRECT TP970B1077 HONEYWELL TP970B2077 DIRECT TP970B2028 HONEYWELL TP970B2002 WITH DIRECT TP970B2028 HONEYWELL 14004406-111 WITH DIRECT TP970B2028 HONEYWELL 14002573-001 DIRECT TP970B2036 HONEYWELL TP970B2002 WITH DIRECT...
Page 219
Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TP971A2169 HONEYWELL TP971A2191 FUNCTIONAL TP971A2209 HONEYWELL TP971A2003 WITH DIRECT TP971A2209 HONEYWELL 14004878-910 WITH DIRECT TP971A2209 HONEYWELL 14002373-001 DIRECT TP971A2217 HONEYWELL TP971A2003 WITH DIRECT TP971A2217 HONEYWELL 14004878-910 WITH...
Page 220
Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TP972A2135 MIRCOSWITCH TP972A2010 FUNCTIONAL TP972A2168 HONEYWELL TP972A2002 WITH FUNCTIONAL TP972A2168 HONEYWELL 14002373-001 FUNCTIONAL TP972A2176 HONEYWELL NO REPLACEMENT NONE TP972A2200 MIRCOSWITCH TP972A2226 WITH FUNCTIONAL TP972A2200 MIRCOSWITCH 14004401-002 FUNCTIONAL...
Page 221
Pneumatic Product Cross Reference TYPE OF ITEM NUMBER MANUFACTURER REPLACEMENT ITEM REPLACEMENT REMARKS TP973B2189 HONEYWELL TP973B2066 WITH DIRECT TP973B2189 HONEYWELL 14004878-910 DIRECT TP974A HONEYWELL NO REPLACEMENT NONE TP974A1000 HONEYWELL TP974A2000 DIRECT TP975A HONEYWELL NO REPLACEMENT NONE TP975B HONEYWELL NO REPLACEMENT...
WARRANTY POLICY Honeywell warrants the products in this catalog (except those parts designated on Honeywell's price lists as not covered by this warranty) to be free from defects due to workmanship or materials, under normal use and service, for the following warranty periods. Honeywell VisionPRO®, Commercial VisionPRO™, FocusPRO®, PRO 4000, PRO 3000, LineVolt™...