7.9 Relay module
7.10 Install mounting plate
7.10.1 Install mounting plate
Building Technologies
Fire Safety
Figure 60: Mounting of relay module
1
DIN rail
2
Relays Z3B171
3
Locking clamp for the relays
4
Fixing screws for the DIN rail
1. Insert the relays (2) on the DIN rail (1) and press them down until they snap
into place.
2. Mount the locking clamp (3) to secure the relays.
3. Depending on their intended use, connect the relays to the configurable control
outputs of the periphery board. For the pin assignment, refer to the product
data of the respective periphery board.
The mounting plate FHA2008-A1 is used to hold components that have to be
installed above the periphery board. It is supplied in a disassembled state and in a
separate packaging unit.
Mounting plate FHA2007-A1 is delivered unassembled and must be assembled
prior to installation. The edge protector (included) can be slid onto the respective
edges of the mounting plate to protect the cables.
Installing, exchanging and connecting modules
2
1
4
3
7
Relay module