Installing a Fabric Module
• For three modules, they must be in slots FM 2, FM 4, and FM 6
• For four modules, they must be in slots FM2, FM 3, FM 4, and FM 6
• For five modules, they must be in Slots FM 2, FM 3, FM 4, FM 5, and FM 6.
• For six modules, they are in slots FM 1, FM 2, FM 3, FM 4, FM 5, and FM 6
Step 4
Slide the module all the way into the slot.
Step 5
Rotate both ejector levers to the front of the chassis and be sure that the module is locked to the top and bottom of the
slot.
Step 6
Screw in the captive screw on each of the two levers so that each lever is locked in place on the module. Tighten each
screw to 8 in-lb (0.9 N·m) of torque.
Step 7
Power up the fabric module as follows:
a) On the menu bar of the APIC GUI, choose FABRIC > INVENTORY.
If you have already navigated to the fabric module, go to step 7c.
Note
b) In the Navigation pane, navigate to the fabric module as follows:
1. Expand the appropriate Pod.
2. Expand the appropriate spine.
3. Expand Chassis.
4. Expand Fabric Modules.
5. Choose the appropriate fabric slot.
c) On the upper right corner of the Properties screen, choose Actions > Enable.
d) Verify that the Fabric LED for the slot that you specified turns on.
Step 8
Reinstall the fan module over the replaced fabric module by following these steps:
a) Use both of your hands to hold the two handles on the front of the fan tray that you are installing.
Cisco Nexus 9508 ACI-Mode Switch Hardware Installation Guide
68
Replacing or Installing Modules, Fan Trays, and Power Supplies