INSTALLATION AND MAINTENANCE INSTRUCTIONS
FSP-951TAUS and FSP-951TAUS-IV
Intelligent Photoelectric
and Temperature Sensors
SPECIFICATIONS
Operating Voltage Range:
Operating Current @ 24 VDC:
Maximum Alarm Current:
Maximum Current:
Operating Humidity Range:
Operating Temperature Range:
Air Velocity:
Height:
Diameter:
Weight:
Isolator Load Rating:
Applicable Standards:
*Please refer to your isolator base/module manual for isolator calculation instructions.
This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ).
GENERAL DESCRIPTION
FSP-951TAUS and FSP-951TAUS-IV are plug-in type multi-sensor smoke sen-
sors that combine a photoelectronic sensing chamber and fixed temperature
heat detector across addressable-analog communications. The sensors trans-
mit an analog representation of smoke density over a communication line
to a control panel. Rotary dial switches are provided for setting the sensor's
address. (See Figure 1.) The intelligent photoelectric and temperature sensors
also transmit an alarm as per class A2S (AS 7240.5).
FIGURE 1. ROTARY ADDRESS SWITCHES
7
8
6
9
5
4
3
2
14
1 0
15
TENS
Two LEDs on the sensor are controlled by the panel to indicate sensor status.
An output is provided for connection to an optional remote LED annunciator
(P/N RA100Z).
Fire Alarm and Control panels offer different feature sets across different mod-
els. As a result, certain features of the photoelectric and temperature sensors
may be available on some control panels, but not on others. FSP-951TAUS will
support only FlashScan® protocol mode. FSP-951TAUS-IV will support either
FlashScan or CLIP (Classic Loop Interface Protocol) mode. The possible fea-
tures available if supported by the control panel are:
1. The sensor's LEDs can operate in three ways—on, off, and blinking—and
they can be set to red, green, or amber. This is controlled by the panel.
2. The remote output may be synchronized to the LED operation or con-
trolled independent of the LEDs.
3. Devices are point addressable up to 159 addresses.
Please refer to the operation manual for the control panel for specific op-
eration. The photoelectric and temperature sensors require compatible ad-
dressable communications to function properly. Connect these sensors to
listed-compatible control panels only.
Compatible bases: B501AUS-W/B501AUS-IV.
SPACING
Notifier recommends spacing sensors in compliance with AS 1670.1:2015. All
detectors should be spaced and installed in accordance with the requirements
of the relevant authority having jurisdiction. For specific information regarding
sensor spacing, placement, and special applications, refer to AS 1670.1:2015
or the Smoke Detector Application Guide.
15 to 32 VDC
200 uA (one communication every 5 seconds with green LED blink on communication)
2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)
4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)
10% to 93% Relative Humidity, Non-condensing
-10°C to 50°C
0 to 1219.2 m/min.
51 mm installed in B501AUS-W/B501AUS-IV Base
104 mm installed in B501AUS-W/B501AUS-IV Base
95 g
0.0063*
AS 7240.7 and AS 7240.5 (Class A2S)
7
8
6
9
5
10
11
4
12
3
13
2
1 0
ONES
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code,
applicable local codes, and any special requirements of the Authority Having
Jurisdiction. Proper wire gauges should be used. The installation wires should
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the
event of a fire.
Remove power from the communication line before installing sensors.
1. Wire the sensor base (supplied separately) per the wiring diagram, Figure 2.
2. Set the desired address on the sensor address switches, see Figure 1.
3. Install the sensor into the sensor base. Push the sensor into the base while
turning it clockwise to secure it in place.
4. After all sensors have been installed, apply power to the control panel and
activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
C0162-00
Dust covers provide limited protection against airborne dust particles during
shipping. Dust covers must be removed before the sensors can sense smoke.
Remove sensors prior to heavy remodeling or construction.
FIGURE 2. WIRING DIAGRAM
Remote
Annunciator
+
(+)
RA
3
(–)
(–)
CLOSE LOOP OPTIONAL WIRING
(+)
TAMPER-RESISTANCE
Photoelectric and temperature sensors include a tamper-resistant capability
that prevents their removal from the base without the use of a tool. Refer to
the base manual for details on making use of this capability.
1
Baulkham Hills NSW 2153
CAUTION
CAUTION: Do not loop wire under
terminal 1 or 2. Break wire run to
-
supervise connections.
+
+
+
+
2
2
–
–
RA
1
1
3
9 Columbia Way
1800 220 345
+
+
2
–
RA
1
3
C0129-10AUS
I56-7362-000