hit counter script
Siemens SIMOCRANE Operating Instructions Manual
Siemens SIMOCRANE Operating Instructions Manual

Siemens SIMOCRANE Operating Instructions Manual

Energy storage system management v01.01
Table of Contents

Advertisement

Quick Links

Edition
04/2023
Operating Instructions
SIMOCRANE
Energy Storage System Management V01.01

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMOCRANE

  • Page 1 Edition 04/2023 Operating Instructions SIMOCRANE Energy Storage System Management V01.01...
  • Page 3 Introduction Fundamental safety instructions Product description Requirements for use SIMOCRANE Energy Storage System Management V01.01 Block interface Control and engineering Operating Instructions Diagnostic system Appendix Valid for: Energy Storage System Management V01.01 04/2023 A5E51573536B AE...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Table Of Contents

    Residual risks of power drive systems ................. 19 Warranty and liability for energy storage devices ..............20 Product description..........................21 Description ........................21 3.1.1 Description of SIMOCRANE Energy Storage System Management ........21 3.1.2 Product overview ....................... 22 Functional scope........................ 23 3.2.1 Operating modes and functions ..................
  • Page 6 Energy storage system ....................... 29 4.2.2 Hardware components....................... 31 4.2.3 Software components......................31 4.2.4 Installing and uninstalling SIMOCRANE ESSM ..............31 Crane applications ......................34 Licensing ........................... 36 4.4.1 Generating the required licenses ..................36 Block interface ............................ 37 Inputs..........................39 5.1.1...
  • Page 7 7.3.1 Main..........................114 7.3.2 System Config........................116 7.3.3 Mode Control........................118 7.3.4 Sequencer ........................119 7.3.5 Power Management......................125 7.3.6 Unit 1 ..........................126 7.3.7 Unit 2 ..........................128 SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 8 Unit 4 ..........................131 7.3.10 Unit 5 ..........................133 7.3.11 Unit 6 ..........................134 7.3.12 Unit 7 ..........................136 7.3.13 Unit 8 ..........................137 Appendix............................141 Application support ......................141 SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 9: Introduction

    1.2.1 Content Objective of the operating instructions These operating instructions provide you with an overview of the product SIMOCRANE Energy Storage System Management implemented as an S7 library for SIMATIC PLC (Programmable Logic Control). Scope of validity of the documentation This documentation is valid for the product SIMOCRANE Energy Storage System Management (ESSM).
  • Page 10: What's New

    This document may contain hyperlinks to third-party websites. Siemens is not responsible for and shall not be liable for these websites and their content. Siemens has no control over the information which appears on these websites and is not responsible for the content and information provided there.
  • Page 11: Service And Support

    Not all documentation classes are available for every SIMOCRANE product. Service and support 1.4.1 Siemens Industry Online Support on the Web Here are some of the items you can find under Siemens Industry Online Support (https:// support.industry.siemens.com/cs/ww/en/): • Product support •...
  • Page 12: Siemens Industry Online Support On The Road

    1.4 Service and support • Newsletters with information about your products • Catalogs/brochures 1.4.2 Siemens Industry Online Support on the road Figure 1-1 "Siemens Industry Online Support" app The "Industry Online Support" app supports you in the following areas, for example: • Resolving problems when executing a project •...
  • Page 13: Feedback On The Technical Documentation

    1.4 Service and support 1.4.3 Feedback on the technical documentation We welcome your questions, suggestions, and corrections for this technical documentation. Please use the "Provide feedback" link at the end of the entries in Siemens Industry Online Support. Figure 1-2 Requests and feedback 1.4.4...
  • Page 14: Technical Support

    Training SITRAIN – Digital Industry Academy offers a comprehensive range of training courses on Siemens industrial products – directly from the manufacturer, for all industries and use cases, for all knowledge levels from beginner to expert. You can find more information on the Internet at the following address: SITRAIN – Digital Industry Academy.
  • Page 15: Important Product Information

    1.5.2 Compliance with the General Data Protection Regulation Siemens complies with the principles of the General Data Protection Regulation (EU), in particular the principle of data minimization (privacy by design). For this product, this means: The product does not process or store any personal data, only technical function data (e.g. time stamps).
  • Page 16 Introduction 1.5 Important product information SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 17: Fundamental Safety Instructions

    2.1.1 Preliminary remarks with respect to general safety instructions SIMOCRANE Energy Storage System Management (ESSM) is operated in the vicinity of electrical installations. This area may contain high voltages, moving machine parts, hydraulic and pneumatic systems. Take the following general security information into account for this reason.
  • Page 18: General Safety Instructions Related To Software

    As the user you yourself are responsible for ensuring that the products described are operated correctly. Application examples do not relieve you of your responsibility for safe handling when using, installing, operating and maintaining the equipment. SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 19: Security Information

    Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure...
  • Page 20: Industrial Security

    • Make sure that you include all installed products into the holistic industrial security concept. • Protect files stored on exchangeable storage media from malicious software by with suitable protection measures, e.g. virus scanners. • On completion of commissioning, check all security-related settings. SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 21: Residual Risks Of Power Drive Systems

    6. Influence of network-connected communication systems, e.g. ripple-control transmitters or data communication via the network For more information about the residual risks of the drive system components, see the relevant sections in the technical user documentation. SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 22: Warranty And Liability For Energy Storage Devices

    Siemens is not responsible for the proper installation, commissioning, operation, maintenance or disposal of energy storage devices. Siemens accepts no liability for deficiencies of or damage to these energy storage devices, or for deficiencies or damage that have been caused by these energy storage devices.
  • Page 23: Product Description

    (https:// support.industry.siemens.com/cs/ww/en/view/109773591). The SIMOCRANE ESSM Step 7 library provides operating modes, functions and a standardized interface for the modular design and scalability of an energy storage system in a crane system. SIMOCRANE ESSM also offers a standardized interface to the crane application.
  • Page 24: Product Overview

    Product description 3.1 Description 3.1.2 Product overview The product SIMOCRANE Energy Storage System Management is a global executable STEP 7 library comprising: • Functions • Function blocks • Data types A license is required for the encrypted core function "LEssMgmt_Main" (see figure below).
  • Page 25: Functional Scope

    An AC island grid can be set up from the DC link controlled by SIMOCRANE ESSM using an "Active Line Module" (ALM) to create the grid, for example. This makes it possible to operate independently of the line supply. The specified charge and discharge power limit is not exceeded.
  • Page 26 Note You can find details about the dimensioning and application of SINAMICS DCPs in the operating instructions "SINAMICS DCP DC Power Converter" (see section Description of SIMOCRANE Energy Storage System Management (Page 21)). Service function The Service function provides support when commissioning the energy storage system. The Service function allows you to set important parameters, limits and setpoints.
  • Page 27 This is not possible with the normal "Black Start", as only one infeed (SIMOCRANE ESSM) is permissible during operation in this mode. The "Hybrid" function is a combination of the "Black Start" and "Peak Shaving"...
  • Page 28 DC link voltage. Energy measurement SIMOCRANE ESSM features an operating hours counter and energy meters. The energy balance (power flow via the SINAMICS DCPs) can be diagnosed locally. The total energy sum and the energy per direction (charging/discharging) can be measured and differentiated.
  • Page 29: Scope Of Delivery

    3.3 Scope of delivery Scope of delivery MLFB 6GA7235-0AA00-0AA0 comprises: • License key for SIMOCRANE Energy Storage System Management V01.01 The following components are available as a direct download under SIMOCRANE Energy Storage System Management (https://support.industry.siemens.com/cs/ww/en/view/ 109807275): • Energy Storage System Management S7 Library •...
  • Page 30 Product description 3.3 Scope of delivery SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 31: Requirements For Use

    • SINAMICS DCP is used as a power controller between the drive DC link and the battery. SINAMICS DCP 120 kW can be used. • The crane application and crane hardware must be compatible with SIMOCRANE ESSM (see section Crane applications (Page 34)).
  • Page 32 Requirements for use 4.2 Energy storage system Figure 4-1 Layout diagram of energy storage system with SIMOCRANE ESSM Note Selection of the correct low-voltage components You can find more information about selecting the correct low-voltage components, such as fuses, for the SINAMICS DCP under the following link: Fuses.
  • Page 33: Hardware Components

    Management in your TIA Portal as a global library and how to upgrade and delete it. Importing the library Proceed as follows to open a global library: 1. Copy the archive of the SIMOCRANE ESSM library (e.g. SIMOCRANE Energy Storage System Management V01.01.00.00 (protected).zal17) onto your local work environment. 2. Start TIA Portal V17.
  • Page 34 7. You can identify the library file by the file name extension ".zal[version number]". Click "Open as read-only" and select the file type "Compressed libraries...". Open the "….zal17" file. Figure 4-3 Search for and open library SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 35 Management V…". Figure 4-4 Library imported successfully The import of the SIMOCRANE ESSM library was successful and the library is displayed in the "Global libraries" list. If the library was opened as read-only, the library and all its subfolders are grayed.
  • Page 36: Crane Applications

    4.3 Crane applications Deleting the library If you no longer need the SIMOCRANE ESSM library, you can delete it. To do this, proceed as follows: 1. In the "Libraries" task card, click the "Global libraries" palette and select the library you wish to delete.
  • Page 37 You can find more details about setting up a power supply with SINAMICS ALM/AIM under: SINAMICS S120 System Manual Line Infeed (https:// support.industry.siemens.com/cs/ww/en/view/109782591). *SINAMICS ALM/AIM = SINAMICS Active Line Module/Active Interface Module Figure 4-6 Crane application SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 38: Licensing

    License required A license is an essential requirement for operating an energy storage system with a SIMOCRANE ESSM Step 7 library. The SIMOCRANE ESSM Step 7 library cannot be used without a license. No trial license functionality is available. SIMOCRANE Energy Storage System Management V01.01...
  • Page 39: Block Interface

    The battery can be damaged as a result of transferring incorrect battery data. • Make sure that the correct battery data have been transferred. • Protect the data transfer against unauthorized access. SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 40 Block interface Figure 5-1 Block interface SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 41: Inputs

    The inputs of the block consist of structures and setting values. Figure 5-2 Inputs 5.1.2 inInit This input is necessary for initializing SIMOCRANE ESSM and must be gated with the start bit of the relevant organization block, e.g. OB30 (see figure below). Figure 5-3 inInit Table 5-1...
  • Page 42: Inreceivefrommaster

    This input is a structure of the data type "LTypes_Master_Receive" and must be gated with the telegram information of the higher-level control. SIMOCRANE ESSM is controlled via this input structure. The constituent elements of the structure are listed in the following tables.
  • Page 43 Drive configuration: Select unit 2 Bit 2 SelUnit3 Bool Drive configuration: Select unit 3 Bit 3 SelUnit4 Bool Drive configuration: Select unit 4 Bit 4 SelUnit5 Bool Drive configuration: Select unit 5 SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 44 Setpoint/limit for charge power werSet in kW Table 5-11 inReceiveFromMaster.DischargePowerSet Input Name Data Higher-level data Comment type type inReceiveFromMaster.Discharge‐ ChargePowerSet Real inReceiveFromMaster Setpoint/limit for discharge pow‐ PowerSet er in kW SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 45 SOC limit low-start in % Table 5-17 inReceiveFromMaster.VBatMax Input Name Data Higher-level data Comment type type inReceiveFromMaster.VBatMax VBatMax Real inReceiveFromMaster An alarm is output when this up‐ per voltage limit is reached SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 46 (> 50.0) BATDischargeCurrLimit Real Actual discharge current with which the battery can be discharged (> 50.0) AVRGTemp Real °C Average temperature of cells AVRGCellVoltage Real Average cell voltage SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 47: Inreceivefromhmi

    The structure of the block input "inReceiveFromHMI" is identical to that of the input "inReceiveFromMaster". No BMS or watchdog information is transferred from the HMI however. For more details, see "inReceiveFromMaster (Page 40)". SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 48: Inhwinputs

    Block interface 5.1 Inputs This input structure is used for operating SIMOCRANE ESSM from the local operator station (HMI). Table 5-25 inReceiveFromHMI Input Data type Comment inReceiveFromHMI LTypes_HMI_Receive 5.1.5 inHWInputs This input is a 24-bit structure of the type "LTypes_ESS_HW_Inputs" and acts as a source of information about the actual switching states of: •...
  • Page 49 Bypass contactor for unit 6 closed Closed Bit 22 Unit7_LineContactor‐ Bool Bypass contactor for unit 7 closed Closed Bit 23 Unit8_LineContactor‐ Bool Bypass contactor for unit 8 closed Closed SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 50: Innrofdcpsinsystem[X]

    (0-8). All the potentially available SINAMICS DCP units are set up in the hardware configuration of the ESS IF PLC as standard. This is a basic requirement for use of the SIMOCRANE ESSM Step7 library. Should only 2 SINAMICS DCPs be physically present, for example, enter a 2 here. Unused devices in the hardware configuration are deactivated during startup.
  • Page 51: Indroopvaluesdcps[%]

    Droop control makes parallel connection possible. The droop value determined by the energy storage system [%] (p.54127) must be signaled to SIMOCRANE ESSM. This causes a voltage correction to be applied which is dependent on the actual system power. This is necessary in order to compensate for voltage fluctuations in the DC link due to operation in droop control.
  • Page 52: Innocat0Stop

    This input can be used for configuring the "Hybrid" function after startup of the ESS IF PLC: • 0 = No Hybrid • 1 = Hybrid Table 5-32 inDefaultHybrid Input Data type Comment inDefaultHybrid Bool The system starts with this func‐ tion by default. SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 53: Indefaultbypass

    You can use the local operator interface to start/stop and reset an individual timer and energy meter. Table 5-35 inStartIndividualMeas Input Data type Comment inStartIndividualMeas Bool Use this input to start the timer and energy meter of the individ‐ ual measurement. SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 54: Instopindividualmeas

    This input can be used for configuring the "Boost" function after startup of the ESS IF PLC: • 0 = No Hybrid • 1 = Hybrid Table 5-38 ininDefaultBoost Input Data type Comment ininDefaultBoost Bool The system starts with this func‐ tion by default. SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 55: Inlicensekey

    5.1.19 inLicenseKey This input is used for licensing the SIMOCRANE ESSM Step 7 library. The input is an array [1..2] of the type "String" with 32 characters each. License key 1 must be entered in "inLicenseKey[1]". License key 2 must be transferred for "inLicenseKey[2]". If the license keys are swapped, the licenses will be rejected as invalid.
  • Page 56: Inhwaddr_Telegram

    (see figure below). SIMOCRANE ESSM automatically establishes communication with the power converters via this telegram interface. You can find the telegram structure that SIMOCRANE ESSM expects from the power converters in the section Controlling the power converters (Page 88).
  • Page 57: Outputs

    Data type Comment inHWAddr_Telegram Array [1..8] of HW_SUBMODULE System constant for the tele‐ gram address Outputs The outputs of the block consist of structures and setting values. Figure 5-15 Outputs SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 58: Outsendtomaster

    This output is a structure of the data type "LTypes_Master_Send" and must be gated with the telegram information of the higher-level control. SIMOCRANE ESSM uses this output structure to send all system information, such as process values, status information and diagnostic data, to the higher-level control.
  • Page 59 Stopped Bool The system has been stopped Bit 3 Charging Bool SIMOCRANE ESSM is operating in "Manual Mode" and the batteries are being charged Bit 4 Discharging Bool SIMOCRANE ESSM is operating in "Manual Mode" and the batteries are being discharged...
  • Page 60 0: The main breaker must be switched off immediately Bit 11 ESSBoosting Bool SIMOCRANE ESSM is operating in "Peak Shaving" mode and is sup‐ plying power from the battery in the direction of the DC link Bit 12 ESSRecuperating Bool SIMOCRANE ESSM is operating in "Peak Shaving"...
  • Page 61 DW 7 Fault_Unit3 Double word DW 8 Fault_Unit4 Double word DW 9 Fault_Unit5 Double word DW 10 Fault_Unit6 Double word DW 11 Fault_Unit7 Double word DW 12 Fault_Unit8 Double word SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 62 Real Currently permissible maximum DischargePower gePower discharge power Table 5-60 outSendToMaster.ActMinCurrentDerating Output Name Data type Comment outSendToMaster.ActMinCur‐ ActMinCurrentD‐ Real Derating factor in A; reference rentDerating erating value 200 A SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 63 FirmwareVersion Integer First part of the SIMOCRANE ESSM firmware version Example: 102 → V01.02 outSendToMaster.Information FirmwarePatch Integer Second part of the SIMOCRANE ESSM firmware version Example: 600 → V01.02.06.00 SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 64: Outsendtohmi

    • Internal • BMS SIMOCRANE ESSM uses this output structure to send all system information, such as process values, status information and diagnostic data, to the local operator station. The structure of the block input "inReceiveFromHMI" is identical to that of the input "inReceiveFromMaster".
  • Page 65: Internal

    Higher-level data Comment type type outSendToHMI.Internal.Warnings Warnings Struct Internal See outSendToMaster/Warnings (Page 58) Table 5-75 outSendToHMI.Internal.Faults Output Name Data Higher-level data Comment type type outSendToHMI.Internal.Faults Faults Struct Internal See outSendToMaster/Faults (Page 59) SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 66 See outSendToMaster/ActMax‐ SystemChargePower ChargePower SystemChargePower (Page 60) Table 5-81 outSendToHMI. Internal.ActMaxSystemDischargePower Output Name Data Higher-level data Comment type type outSendToHMI. Internal.ActMax‐ ActMaxSystemDi‐ Real Internal See outSendToMaster/ActMax‐ SystemDischargePower schargePower SystemDischargePower (Page 60) SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 67 Hardware for unit 3 deactivated nal.Unit3HWDisabled Table 5-87 outSendToHMI. Internal.Unit4HWDisabled Output Name Data Higher-level data Comment type type outSendToHMI. Inter‐ Unit4HWDisabled Bool Internal Hardware for unit 4 deactivated nal.Unit4HWDisabled SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 68 Real Internal See outSendToMaster/ActMin‐ CurrentDerating erating CurrentDerating (Page 60) Table 5-93 outSendToHMI. Internal.ActMaxI2t Output Name Data Higher-level data Comment type type outSendToHMI. Internal.Act‐ ActMaxI2t Real Internal See outSendToMaster/ActMaxI2t MaxI2t (Page 61) SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 69 Data type Comment outSendToHMI.Internal. LReal Non-volatile value which displays the total discharge power EnrgyMeasLifeTimeDischarge Table 5-100 outSendToHMI.Internal.EnrgyMeasLifeTimeSum Output Data type Comment outSendToHMI.Internal. LReal Sum of charge and discharge power EnrgyMeasLifeTimeSum SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 70: Bms

    LTypes_B outSendToHMI Information about the Battery MS_Bat‐ Management System. For infor‐ tery mation about the constituent el‐ ements, see chapter inReceive‐ FromMaster (Page 44). The struc‐ tures are identical. SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 71: Control And Engineering

    The energy storage system can be controlled via the receive area (from the perspective of the ESS). Status information is transferred via the send area (from the perspective of the ESS). SIMOCRANE ESSM can also be operated from a local operator panel. Figure 6-1 Control SIMOCRANE Energy Storage System Management V01.01...
  • Page 72: Selection Of Operator Interface

    6.1.1 Selection of operator interface Three operator stations are available. SIMOCRANE ESSM is controlled via the remote PLC as standard. It is possible to switch to the "Local" and "Service" modes from the local operator panel for the purpose of maintenance, service or commissioning measures.
  • Page 73: Control Via Remote Plc

    120 kW. In "Overload" mode, transient power levels up to 1.6x the rated power can be reached (see SINAMICS DCP operating instructions). Figure 6-3 Selection of SINAMICS DCPs SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 74: Selection Of Operating Modes

    • The following applies to the "Black Start" and "Peak Shaving" modes in "Hybrid" operation: Ensure that no other device can control the DC link voltage. The energy storage system takes over the control on startup. SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 75: Startup/Shutdown

    If all the conditions for startup are fulfilled, the power converters are activated. The precondition for activation is that the battery system is ready for operation at the time. SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 76 After an acknowledgement, operation can be continued with the remaining power converters despite the presence of a faulted device. The total power is reduced as a consequence. SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 77 Control and engineering 6.2 Control via remote PLC Figure 6-6 Operation with faulted SINAMICS DCPs SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 78: Manual Charging/Discharging

    Shutdown routine 1 can be requested via the telegram interface. If SIMOCRANE ESSM detects a fault state during shutdown routine 1, a fault message is issued and shutdown routine 3 is triggered as a response.
  • Page 79 If only a low charge power is available, e.g. because the landside connection is too weak at < 20 kW, it is advisable to charge the battery using only one SINAMICS DCP. SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 80: User Acknowledgment

    Two acknowledgement types are available: • "Acknowledgement" - and - • "EtechAcknowledgement" (only available for users with the appropriate authorization) See chapter Diagnostic system (Page 99). SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 81: Overload Operation

    The rated current limit can be exceeded as a result. In this operating mode, the "weakest" power converter in the group (e.g. the one with the highest temperature) determines the derating factor. Figure 6-8 Overload operation SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 82: Hybrid Mode

    Shaving" mode. This makes it possible to connect a second infeed source later, for example. This is not possible with the normal "Black Start", as only one infeed (SIMOCRANE ESSM) is permissible during operation in this mode. The "Hybrid" function is a combination of the "Black Start"...
  • Page 83 Control and engineering 6.2 Control via remote PLC Figure 6-10 "Peak Shaving" and "Hybrid" mode SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 84: Bypass

    This increased dynamic response necessitates a higher energy consumption by the SINAMICS DCPs, which has an impact on the energy balance. SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 85: Power Limiting

    Write the "Watchdog" value that you receive via "outSendToMaster" back to the input "inReceiveFromMaster" in the higher-level control. Do not change or apply any delay to the "Watchdog" value. This value is incremented by SIMOCRANE ESSM. You can also check the received "Watchdog" value for any changes in order to detect a possible failure of SIMOCRANE ESSM.
  • Page 86: Fault Handling

    "Acknowledge" command. 6.2.13 Setpoints The following setpoints can be managed when the SIMOCRANE ESSM Step7 library is used: DCLinkVoltageSetp The value must be set to match the currently selected operating mode. In other words, the value must be adjusted when the operating mode changes.
  • Page 87 When the battery voltage reaches this limit, the charge controller stops the flow of energy out of the battery. Any additional energy required must be made available by other means, or the power requirement must be reduced. "SOCBatSysLowEnd" < "SOCBatSysLowStart" SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 88 (inNrOfDCPsInSystem[X]). The number of SINAMICS DCPs that are actually selected on system start is of no relevance here. The values "BATChargeCurrLimit" and "BATDischargeCurrLimit" can be used to implement adequate battery protection. SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 89: System States

    6.3 Control via HMI 6.2.14 System states No information from the crane or from third-party systems is available to SIMOCRANE ESSM. The remote PLC must therefore make certain states relating to the overall system available. These are as follows: • The state of the main crane breaker •...
  • Page 90: Controlling The Power Converters

    Figure 6-13 Controlling the power converters SIMOCRANE ESSM uses the addresses parameterized at the block input to communicate with the connected power converters. A free telegram of the type (PZD-16/16) must be used. In other words, 16 words are sent to the power converter and 16 words are received from it.
  • Page 91 Charge current limit reached [r55125.0] Bit 15 DischrgCurrLimAct Bool Discharge current limit reached [r55125.1] Table 6-4 DCP_Receive.StatusWord2 Name Data Higher-level data Comment type type DCP_Receive.StatusWord2 StatusWord2 Word DCP_Receive Spare SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 92 Actual value for current via inter‐ [r55510] nal device choke, DCP choke Table 6-10 DCP_Receive.AirIntakeTemp STW13 Name Data Higher-level data Comment type type DCP_Receive.AirIntakeTemp AirIntakeTemp WORD DCP_Receive Intake air temperature of power [r52050.5] unit SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 93: Sinamics Dcp Send (16 Word)

    Bool Command "ON/OFF (OFF1)" [p840.0] Bit 1 OFF2 [p844.0] Bool No coasting/coasting (OFF2) Bit 2 Spare Bool Bit 3 EnableOpera‐ Bool EnableOperation [p852.0] tion [p852.0] Bit 4 Spare Bool SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 94 Signal source for the negative Neg_Choke current limit of the voltage con‐ [p54142] troller Table 6-21 DCP_Send.CurrLimNeg_Choke CTW9-16 Name Data Higher-level data Comment type type DCP_Send.CurrLimNeg_Choke ControlWord9-16 Word DCP_Send Spare SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 95: Hardware Configuration

    Control and engineering 6.6 Integration into the user project Hardware configuration The SIMOCRANE ESSM system requires a valid hardware configuration comprising at least the configuration for the PLC, the HMI and up to 8 SINAMICS DCP units. Figure 6-14 Basic hardware configuration in the TIA Portal The hardware configuration is not included in the library.
  • Page 96 The library is then imported into the global library of the TIA Portal. Figure 6-16 Opening library After the import, the library can be seen in the overview of global libraries. Figure 6-17 Library is completely installed SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 97: Creating The Energy Storage Management Project

    "LEssMgmt_Main" block call in a cyclic OB. Select a cycle time of 4 ms for the OB. Figure 6-18 Library overview 6.6.3 The drive project You can find information about opening, editing and downloading the drive project to the SINAMICS DCPs in the application description. SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 98: Download To S7 Cpu/S7 Hmi

    PLC. The download option is also available in the shortcut menu. This method of procedure also applies for the S7 HMI. Figure 6-19 Download SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 99: Upgrading A Library

    6.6.6 Settings You can find an overview and description of the block interface of SIMOCRANE ESSM in chapter Block interface (Page 37). Parameterize each of these inputs with the values described in the table.
  • Page 100 Control and engineering 6.6 Integration into the user project SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 101: Diagnostic System

    Diagnostic system The SIMOCRANE ESSM Step 7 library includes a comprehensive diagnostic system which signals system states to the higher-level crane control system and the local operator interface. The diagnostic system consists of status information, warnings and fault messages. You can find an overview of the telegrams and the meanings of the individual bits below.
  • Page 102: System Config

    Reserved for 250 kW devices Bits 6-31 Spare 7.2.2 System Config Bits 0-31 Spare 7.2.3 Mode Control Bit 0 Manual Start selection blocked; ESS is not OFF Message class Warning Component Control SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 103 Response Request for switchover is rejected Acknowledgement Self-acknowledging Cause A selection of the overload function has been detected during operation Remedy Switch off the ESS before requesting a selection SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 104 Control Response Request for switchover Acknowledgement Self-acknowledging Cause A selection of the "High Dynamic" function has been detected during operation Remedy Switch off the ESS before requesting a selection SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 105: Sequencer

    Main breaker is open Message class Warning Component Switchgear Response Start is blocked on start trigger Acknowledgement Self-acknowledging Cause Main breaker is open Remedy Close the main breaker before startup SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 106 Acknowledgement Self-acknowledging Cause The battery current is too low Remedy Check whether the battery current is limited by the battery and that it is correctly transferred Bits 8-31 Spare SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 107: Power Management

    Adjust the power setpoint to the maximum system power if necessary Bit 3 Discharging power limit > than maximum Message class Warning Component Setpoint input Response Limitation to max. calculated system power Acknowledgement Self-acknowledging SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 108 None Acknowledgement Self-acknowledging Cause A DC link voltage which is too low has been detected Remedy • Check the power limits (SIMOCRANE ESSM/infeed unit) • Adjust the DC link voltage if necessary Bit 6 DC-Link Voltage High Message class Warning...
  • Page 109 SOC < SOCBatSysLowEnd Remedy Charge the battery Bit 11 Battery Voltage Low Message class Warning Component Battery Response None Acknowledgement Self-acknowledging Cause Battery voltage too low Remedy Check the battery SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 110 Battery almost fully charged or discharged Remedy Change the battery to a valid SOC range Bit 17 Overload capacity exhausted > 70 % Message class Warning Component Power converter Response None SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 111: Unit 1

    Unit 1 is tagged as electrically isolated Remedy Check the fuse links Bit 1 Unit Air intake temperature high Message class Warning Component Power converter 1 Response None Acknowledgement Self-acknowledging SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 112: Unit 2

    Unit 3 Bit 0 Unit Disconnected Message class Warning Component Power converter 3 Response None Acknowledgement Self-acknowledging Cause Unit 3 is tagged as electrically isolated Remedy Check the fuse links SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 113: Unit 4

    Unit 4 intake air temperature > 35 °C Remedy Check the air conditioning Bits 2-31 Spare 7.2.10 Unit 5 Bit 0 Unit Disconnected Message class Warning Component Power converter 5 SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 114: Unit 6

    Unit Air intake temperature high Message class Warning Component Power converter 6 Response None Acknowledgement Self-acknowledging Cause Unit 6 intake air temperature > 35 °C Remedy Check the air conditioning Bits 2-31 Spare SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 115: Unit 7

    Unit Air intake temperature high Message class Warning Component Power converter 8 Response None Acknowledgement Self-acknowledging Cause Unit 8 intake air temperature > 35 °C Remedy Check the air conditioning SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 116: Faults

    Component PROFINET communication Response Shutdown routine 3 Acknowledgement ETechAcknowledge Cause • I-Device communication between the master and the SIMOCRANE ESSM IF PLC is interrupted • Incorrect hardware configuration • Watchdog interconnection in master PLC faulted Remedy • Check the communication parameters •...
  • Page 117 Critical parametrization error: BMS discharge current limit invalid Message class Fault Component Response Shutdown routine 3 Acknowledgement ETechAcknowledge Cause BMS charge current limit invalid Remedy Check the BMS information Bits 7-31 Spare SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 118: System Config

    Hardware configuration of ESS IF PLC Response Shutdown routine 3 Acknowledgement Warm restart of ESS IF PLC Cause Incorrect parameterization of input inNrOfDCPSInSystem[X] Remedy Check the input inNrOfDCPSInSystem[X] (Page 48) SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 119 Hardware configuration of ESS IF PLC Response Shutdown routine 3 Acknowledgement Warm restart of ESS IF PLC Cause Incorrect parameterization of input inNrOfDCPSInSystem[X] Remedy Check the input inHWAddr_Head (Page 53) SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 120: Mode Control

    Mode configuration Response Shutdown routine 3 Acknowledgement Warm restart of ESS IF PLC Cause Incorrect parameterization of input inDefaultOperationMode[X] (Page 49) Remedy Check the input inDefaultOperationMode[X] (Page 49) Bits 1-31 Spare SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 121: Sequencer

    Fault Component Internal SIMOCRANE ESSM Vx.x Response Shutdown routine 3 Acknowledgement ETechAcknowledge Cause Opening of the main battery breaker requested due to critical fault Remedy Check further fault messages SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 122 Wait until the precharge resistors have cooled down before startup in order to avoid hardware damage Bit 7 Start inhibited: Cool down active Unit 4 Message class Fault Component Internal SIMOCRANE ESSM Vx.x Response Shutdown routine 2 Acknowledgement Acknowledge SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 123 Check the storage battery • Rectify any faults in the battery system Bit 11 External CAT-0 Stop detected Message class Fault Component Master PLC Response Shutdown routine 3 Acknowledgement ETechAcknowledge SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 124 Remedy Close the main battery breaker before starting up the ESS Bit 16 Internal CAT-0 Stop detected Message class Fault Component Internal SIMOCRANE ESSM Vx.x Response Shutdown routine 3 SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 125 Clarify the cause and acknowledge the fault provided no safety hazard exists Bit 21 System Check failed. No valid start config Message class Fault Component Internal SIMOCRANE ESSM Vx.x SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 126 In order to avoid hardware damage, wait until the precharge resistors have cooled down before startup Bit 25 Start inhibited: Cool down active Unit 7 Message class Fault Component Internal ESSM Vx.x SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 127: Power Management

    Bit 1 Spare (Later boosting DC-Link failed. OFF-2 all drives in DC-Link) Bit 2 Battery voltage too low Message class Fault Component Internal SIMOCRANE ESSM Vx.x Response Shutdown routine 2 SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 128 Clarify the cause of the overcurrent Bits 6-31 Spare 7.3.6 Unit 1 Bit 0 Unit CAT-0 Stop Message class Fault Component Internal SIMOCRANE ESSM Vx.x Response Shutdown routine 3 Acknowledgement ETechAcknowledge SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 129: Unit 1

    Acknowledgement ETechAcknowledge Cause • Unit 1 has detected a fault at the precharge contactor • Defective precharge contactor Remedy • Clarify the cause • Replace the contactor if necessary SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 130: Unit 2

    Unit Communication Fault Message class Fault Component Internal SIMOCRANE ESSM Vx.x Response Shutdown routine 3 Acknowledgement ETechAcknowledge Cause The communication connection to the unit is faulted Remedy Check the network connection SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 131 Clarify the cause • Replace the fuse links if necessary Bits 6-31 Spare 7.3.8 Unit 3 Bit 0 Unit CAT-0 Stop Message class Fault Component Internal SIMOCRANE ESSM Vx.x SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 132: Unit 3

    Unit Communication Fault Message class Fault Component Internal SIMOCRANE ESSM Vx.x Response Shutdown routine 3 Acknowledgement ETechAcknowledge Cause The communication connection to the unit is faulted Remedy Check the network connection SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 133: Unit 4

    Unit 4 has triggered an internal CAT-0 stop Remedy Clarify the cause (see following messages) Bit 1 Unit Fault present Message class Fault Component Internal SIMOCRANE ESSM Vx.x Response Shutdown routine 3 Acknowledgement ETechAcknowledge SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 134 Clarify the cause • Replace the contactor if necessary Bit 5 Unit Disconnected while running Message class Fault Component Internal SIMOCRANE ESSM Vx.x Response Shutdown routine 3 Acknowledgement ETechAcknowledge SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 135: Unit 5

    The communication connection to the unit is faulted Remedy Check the network connection Bit 3 Unit Line contactor failure Message class Fault Component Internal SIMOCRANE ESSM Vx.x Response Shutdown routine 3 SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 136: Unit 6

    Message class Fault Component Internal SIMOCRANE ESSM Vx.x Response Shutdown routine 3 Acknowledgement ETechAcknowledge Cause Unit 6 has triggered an internal CAT-0 stop Remedy Clarify the cause (see following messages) SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 137 Remedy • Clarify the cause • Replace the contactor if necessary Bit 5 Unit Disconnected while running Message class Fault Component Internal SIMOCRANE ESSM Vx.x Response Shutdown routine 3 SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 138: Unit 7

    ETechAcknowledge Cause The communication connection to the unit is faulted Remedy Check the network connection Bit 3 Unit Line contactor failure Message class Fault Component Internal SIMOCRANE ESSM Vx.x SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 139 Replace the fuse links if necessary Bits 6-31 Spare 7.3.13 Unit 8 Bit 0 Unit CAT-0 Stop Message class Fault Component Internal ESSM Vx.x Response Shutdown routine 3 Acknowledgement ETechAcknowledge SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 140: Unit 8

    Acknowledgement ETechAcknowledge Cause • Unit 8 has detected a fault at the precharge contactor • Defective precharge contactor Remedy • Clarify the cause • Replace the contactor if necessary SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 141 • Unit 8 was disconnected from the line supply during operation • Fuse tripped Remedy • Clarify the cause • Replace the fuse links if necessary Bits 6-31 Spare SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 142 Diagnostic system 7.3 Faults SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 143: Appendix

    Application support Siemens AG Digital Industries Motion Control Digital Application Engineering Cranes DI MC GMC CR PSM DAE Frauenauracher Str. 80 91056 Erlangen, Germany mailto: Digital Application Engineering Cranes (applications.cranes.aud@siemens.com) SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 144 Appendix A.1 Application support SIMOCRANE Energy Storage System Management V01.01 Operating Instructions, 04/2023, A5E51573536B AE...
  • Page 146 More information SIMOCRANE www.siemens.com/simocrane SIMOTION www.siemens.com/simotion SINAMICS www.siemens.com/sinamics Siemens AG Digital Industries Motion Control Postfach 3180 91050 Erlangen Germany Scan the QR-Code for product information...

Table of Contents