12 Clintonville Road
Northford, CT 06472-1610 USA
800-289-3473 • FAX 203-484-7118
www.notifier.com
For additional documentation on this product, visit notifiermanuals.com. This additional documentation for the NFS2-640 may be used as a reference
only.
NOTE: The term NFS2-640 is used to refer to the NFS2-640 and NFS2-640E unless otherwise noted.
NOTE: For Mass Notification applications, Class A circuits called out in this manual are Class X.
1 Installation
Wiring methods used shall be in accordance with Standard for Installation and Classification of Burglar and Holdup Alarm Systems, UL 681.
Wiring methods used shall be in accordance with Standard for Central Station Alarm Services, UL 827.
This product is intended to be installed in accordance with the following:
•
NFPA 70 - National Electrical Code
•
NFPA 72 - National Fire Alarm Code
•
NFPA 12 - Standard on Carbon Dioxide Extinguishing Systems
•
NFPA 12A - Standard on Halon 1301 Fire Extinguishing Systems
•
NFPA 13 - Standard for Installation of Sprinkler Systems
•
Canadian Electrical Code, Part I
•
ULC S524 - Standard for the Installation of Fire Alarm Systems
•
NFPA 92 - Standard for Smoke-Control Systems
•
NFPA 2010 - Standard for Fixed Aerosol Fire Extinguishing System •
•
UL 2572 - Standard for Mass Notification Systems
Follow these guidelines when mounting the product's backbox:
•
Backbox should be installed in a dry, indoor location.
•
It is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27°C/60-80°F and at
a relative humidity of 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F).
•
Locate the backbox so the top edge is 66 inches (1.6764 m) above the surface of the finished floor.
•
Access to the cabinet shall be in accordance with NFPA 90, article 110.33.
•
Allow sufficient clearance around cabinet for door to swing freely.
Terminal Block/
Connector
TB4
Alarm & Trouble Output Relays -
Common
TB5
Supervisory & Security Output Relay
- Common or programmable
Description
• Power-limited (Class 2) only if connected to a power-limited source
• Voltage and Current: Rated 2.0 A at 30 VDC resistive
• Non-supervised
• Power-limited (Class 2) only if connected to a power-limited source
• Voltage and Current: Rated 2.0 A at 30 VDC resistive
• Can be programmed as Alarm via VeriFire Tools
• Non-supervised
Table 1 CPU2-640 Wiring Connections (1 of 2)
NFS2-640
Listing Document
PN 52741LD:H9 5/19/2022 ECN: 16475
•
NFPA 16 - Standard for Deluge-Foam Water Systems
•
NFPA 17 - Standard for Dry Chemical Extinguishing Systems
•
NFPA 17A - Standard for Wet Chemical Extinguishing Systems
•
NFPA 2001 - Standard for Clean Agent Fire Extinguishing Systems
•
UL 2610 - Standard for Commercial Premises Security Alarm Units
and Systems
•
NFPA 15 - Standard for Water Spray Fixed Systems
•
ULC S561 - Installation and Services for Fire Signal Receiving
Centers and Systems
•
ULC-S527-11 - Standard for Control Units for Fire Alarm Systems
UL 864 Standard for Control Units and Accessories for Fire Alarm
Systems, 10th Edition
Specifications