HX-RIO3 Series 1.1 Safety Instruction 1.1.1 Symbols Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death property damage, or economic loss. Identifies information that is critical for successful application and understanding of the product.
HX-RIO3 Series 2.1.2 LED Indicator LED No. LED Function / Description LED Color Aph Input Ch# 0 Green Bph Input Ch# 0 Green Aph Input Ch# 1 Green Bph Input Ch# 1 Green 2.1.3 Channel Status LED Status LED is...
HX-RIO3 Series 2.1.4 Specification Items Specification Input specification Number of channels 2 channels - Encoder, High Speed Counter, Frequency measurement Pulse width & Period measurement Indicators 4 green terminal input Input voltage 24Vdc nominal (Max 28.8Vdc) Input current 3mA @ 24Vdc Min on-state voltage ≥16.5Vdc...
HX-RIO3 Series 2.1.5 Mapping data into the image table Input Image Data – 8byte Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Counter Value Ch#0 LL Counter Value Ch#0 LH Counter Value Ch#0 HL...
Page 10
HX-RIO3 Series Count Mode Ch#0, Ch#1 Value Count Mode Description Up Counter - Aph Input acts as Up Clock B’ 0000 (0x0) - Bph Input is not used Down Counter - Aph Input acts as Down Clock Down B’ 0001 (0x1) - Bph Input is not used B’...
HX-RIO3 Series 3 Environment Specification Environmental specification Operating Temperature -20℃ ~ 70℃ UL Temperature -20℃ ~ 60℃ Storage Temperature -40℃ ~ 85℃ Relative Humidity 5% ~ 90% non-condensing Mounting DIN rail General specification Shock Operating IEC 60068-2-27: 2008/15g, 11ms Based on IEC 60068-2-6...
HX-RIO3 Series 5 Mounting Caution! Hot surface! The surface of the housing can become hot during operation. If the device was operated at high ambient temperatures, allow it to cool off before touching it. Notice! Perform work on devices only if they are de-energized! Working on energized devices can damage them.
HX-RIO3 Series 5.2 RTB (Removable Terminal Block) Whole terminal block can be combined and removed for the convenience if its maintenance. There is a locking switch on the RTB for the easy combination and easy removal. Easy combination and easy removal for IO modules on the din rail through One Touch Locking Switch.
HX-RIO3 Series 6 G-Bus Pin Description Communication between the Network Adapter and the expansion module as well as system / field power supply of the bus modules is carried out via the internal bus. It is comprised of 6 data pin and 2 field power pin.
HX-RIO3 Series 7 APPENDIX A 7.1 Product List Please refer the separate HX-RIO3 product list document 7.2 Glossary System Power: The power for starting up CPU. Field Power: The power for input and output line. Terminator Resistor: Resistor for prevention reflected wave.