MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. USE, COPYING, AND DISTRIBUTION OF ANY DELL SOFTWARE DESCRIBED IN THIS PUBLICATION REQUIRES AN APPLICABLE SOFTWARE LICENSE. Dell, EMC, and other trademarks are trademarks of Dell Inc. or its subsidiaries. Other trademarks may be the property of their respective owners. Published in the USA.
CONTENTS Figures Tables Preface Chapter 1 Before You Begin Conventions used in this document.............12 Where to get help..................12 Site requirements..................13 Hardware acclimation times................ 13 Installing a 2U1N configuration in a 40U cabinet..........14 Installing a 2U4N configuration in a 40U cabinet......... 15 Chapter 2 2U1N Configuration Equipment Installation 2U1N configuration installation guidelines...........
Page 4
CONTENTS Three-phase delta wiring for 2U1N configuration ........53 Three-phase wye wiring for 2U1N configuration ........55 Management network wiring for 2U1N configuration .........57 Data network A wiring for 2U1N configuration ...........60 Data network B wiring for 2U1N configuration ...........63 Chapter 5 Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Guidelines for wiring a 2U4N configuration in a single-phase cabinet..
FIGURES Cabinet stack up for 2U1N configurations..............19 Removing the inner rail from the slide rail..............22 Correct location for ball bearing retainer assembly............. 24 Aligning the inner rail with white plastic guide block........... 25 Inner rail over the first part of ball bearing retainer assembly........25 Inserting the server in the cabinet................
TABLES Site requirements......................13 Hardware acclimation times (systems and components)..........13 Stack up for a minimum configuration................. 18 Stack up for a maximum configuration................ 18 Mounting kit parts...................... 20 Maximum stack up in cabinets with single-phase power distribution......32 Maximum stack up in cabinets with three-phase delta or 3-phase wye power distribution.........................
Preface As part of an effort to improve its product lines, Dell EMC periodically releases revisions of its software and hardware. Therefore, some functions described in this document might not be supported by all versions of the software or hardware currently in use.
Page 10
EMC products, go to Dell EMC Online Support at https://support.emc.com. Technical support Go to Dell EMC Online Support and click Service Center. You will see several options for contacting Dell EMC Technical Support. Note that to open a service request, you must have a valid support agreement. Contact your Dell EMC sales representative for details about obtaining a valid support agreement or with questions about your account.
CHAPTER 1 Before You Begin This chapter provides information to obtain assistance and to prepare for the installation. Topics include: Conventions used in this document..............12 Where to get help....................12 Site requirements....................13 Hardware acclimation times................13 Installing a 2U1N configuration in a 40U cabinet..........
Note To open a service request through the Dell EMC Online Support site, you must have a valid support agreement. Contact your Dell EMC sales representative for details about obtaining a valid support agreement or to answer any questions about your account.
Before You Begin Site requirements Confirm that the customer site meets all requirements before you begin the installation. The following table describes site requirements and provides references to additional information. Table 1 Site requirements Requirement Description Computer room The system requires a properly equipped computer room with controlled temperature and humidity, proper airflow and ventilation, proper power and grounding, system cable routing facilities, and fire equipment.
Before You Begin Table 2 Hardware acclimation times (systems and components) (continued) …then let the system or component If the last 24 hours of the acclimate in the new TRANSIT/STORAGE …and the OPERATING environment this many environment was this: environment is this: hours: Nominal 68-72°F Nominal...
Before You Begin Installing a 2U4N configuration in a 40U cabinet NOTICE After the installation is complete, you must complete the registration as described Chapter 7 Update the Install Database on page 115 If you are installing a 2U4N configuration, refer to the following chapters in this document: Install the hardware components as described in: 2U4N Configuration Equipment...
Page 16
Before You Begin VxRack Node Hardware Installation Guide...
CHAPTER 2 2U1N Configuration Equipment Installation This chapter provides information for installation of the equipment used in a 2U1N configuration. The chapter contains the following topics: 2U1N configuration installation guidelines............18 Install the 2U1N server in the cabinet..............19 Install the management server in the cabinet.............
2U1N Configuration Equipment Installation 2U1N configuration installation guidelines Assuming installation is into an empty rack, always begin component installation at the bottom of the cabinet and work upward. Install components at the lowest available space for that component type. If you are installing the minimum configuration, the stack up will be as follows: Table 3 Stack up for a minimum configuration Component Description...
2U1N Configuration Equipment Installation Figure 1 Cabinet stack up for 2U1N configurations Install the 2U1N server in the cabinet CAUTION The server is heavy and should be installed in a rack by two people. To avoid personal injury and/or damage to the equipment, do not attempt to lift and install the enclosure into a rack without a mechanical lift and/or help from another person.
2U1N Configuration Equipment Installation Procedure 1. Install the slide rails in the cabinet. 2. On both sides of the cabinet, extend the ball bearing and inner rail fully out of the cabinet until they lock in the extended position. Note Mounting posts on each side of the server rest in vertical slots in the inner slide rail.
2U1N Configuration Equipment Installation Table 5 Mounting kit parts (continued) Component Four Phillips pan-head 8-32 x 0.35 in Stabilize the server and rail mounting screws 1U bezel (application specific) Covers front of server in cabinet CL4887 You need a # 2 Phillips-head screwdriver to complete the installation of the rails and server.
2U1N Configuration Equipment Installation Figure 2 Removing the inner rail from the slide rail CL4883 Attach the inner rails to the server Attach an inner rail to each side of the server by performing the procedure that follows for each rail. Procedure 1.
Page 23
2U1N Configuration Equipment Installation CL4961 Attach the inner rails to the server...
2U1N Configuration Equipment Installation Installing the server on the rails in the cabinet CAUTION The enclosure is heavy and should be installed into or removed from a rack by two people. To avoid personal injury and/or damage to the equipment, do not attempt to lift and install the enclosure into a rack without a mechanical lift and/or help from another person.
2U1N Configuration Equipment Installation Note For clarity, Figure 5 shows the inner rail without the server attached. Figure 4 Aligning the inner rail with white plastic guide block CL5093 3. Slide the server into the cabinet so the inner rails extends over the plastic guide blocks and the first part of the ball bearing retainer assemblies.
2U1N Configuration Equipment Installation Figure 6 Inserting the server in the cabinet CL4962 6. To further secure the rail assembly and server in the cabinet, insert and tighten a small stabilizer screw directly behind each bezel latch. Figure 7 Installing the stabilizer screws CL4963 7.
2U1N Configuration Equipment Installation 3. Align one of the inner rails to the mounting position on the management switch. 4. Attach the inner rail to the management switch with the three flat head Philips screws. 5. Repeat previous two steps to attach the inner rail to other side of the management switch.
2U1N Configuration Equipment Installation 8. Login to the switch again , this time the password is Scaleio123 9. Type and click enter. enable 10. Type terminal (or ) to enter global configuration mode. configure config 11. Type to enter interface configuration mode for the interface management 0 virtual interface which accesses management port 1 on the currently active supervisor.
2U1N Configuration Equipment Installation Configure the data switch This procedure is used to configure the data switch. Procedure 1. Copy the configuration filename from the USB flash drive using the following command: enable 2. Then, copy usb1:<configuration file>startup-config Example: localhost> enable locathot>...
Page 30
2U1N Configuration Equipment Installation Note Arista switches are by default set to Use Jumbo Frames; no additional configuration is needed on switches for Performance Best Practice. 16. Repeat this procedure if required to configure additional data switches. VxRack Node Hardware Installation Guide...
CHAPTER 3 2U4N Configuration Equipment Installation This chapter provides information for installation of the equipment used in a 2U4N configuration. The chapter contains the following topics: 2U4N configuration installation guidelines............32 Install the 2U4N server in the cabinet..............35 Install the management server in the cabinet.............
2U4N Configuration Equipment Installation 2U4N configuration installation guidelines Assuming installation is into an empty rack, always begin component installation at the bottom of the cabinet and install upward. Install components at the lowest available space for that component type. The quantities of components that can be installed in a cabinet are dependant on the type of power distribution units installed in the cabinet.
2U4N Configuration Equipment Installation Figure 8 Stack up in cabinets with single-phase power distribution Installation in cabinets with 3-phase delta or 3-phase wye power distribution If you are installing the system in a cabinet with 3-phase delta power distribution, the maximum stack up will be as follows: Installation in cabinets with 3-phase delta or 3-phase wye power distribution...
2U4N Configuration Equipment Installation Table 7 Maximum stack up in cabinets with three-phase delta or 3-phase wye power distribution Component Description Quantity Cabinet U Space Function Data Server Quanta 2U4N Server 2 - 17 and 26 - 31 Management Server Kylin 1U Server Management Switch Arista 7010T-48...
2U4N Configuration Equipment Installation Figure 9 Stack up in cabinets with 3-phase delta or 3-phase wye power distribution Install the 2U4N server in the cabinet There are cabinet slides (left and right). Each cabinets slide consists of the part that is installed in the cabinet (slide rail) and the part that is mounted on the side of the server (inner rail).
2U4N Configuration Equipment Installation 2. Install the slide rails in the cabinet with the hardware provided. 3. Position one of the inner rails on the mounting studs on corresponding side of the replacement chassis. 4. Slide the inner rail forward until it clicks, which locks it in place on the server. Figure 10 Attaching an inner rail to the server 5.
2U4N Configuration Equipment Installation Figure 12 Correct location for ball bearing retainer assembly 8. From the front of the cabinet, align the inner rails attached to the server with the plastic guide block on the front inside of each slide rail. Figure 13 Inner rail over the first part of ball bearing retainer assembly 9.
2U4N Configuration Equipment Installation Figure 14 Inner rail over the first part of ball bearing retainer assembly 10. Once the inner rails are properly engaged with the ball bearing retainer assemblies, push the server into the cabinet until the slide rails are engaged and locked.
2U4N Configuration Equipment Installation Install the management server in the cabinet Verifying the mounting kit parts Verify that the server mounting kit includes the parts listed in table that follows. Table 8 Mounting kit parts Component 2 universal rail assemblies Attach back to front on either side between (consists of slide rails for connection to the cabinet channels...
2U4N Configuration Equipment Installation Figure 16 Removing the inner rail from the slide rail CL4883 Attach the inner rails to the server Attach an inner rail to each side of the server by performing the procedure that follows for each rail. Procedure 1.
Page 41
2U4N Configuration Equipment Installation CL4961 Attach the inner rails to the server...
2U4N Configuration Equipment Installation Installing the server on the rails in the cabinet CAUTION The enclosure is heavy and should be installed into or removed from a rack by two people. To avoid personal injury and/or damage to the equipment, do not attempt to lift and install the enclosure into a rack without a mechanical lift and/or help from another person.
2U4N Configuration Equipment Installation Note For clarity, Figure 5 shows the inner rail without the server attached. Figure 18 Aligning the inner rail with white plastic guide block CL5093 3. Slide the server into the cabinet so the inner rails extends over the plastic guide blocks and the first part of the ball bearing retainer assemblies.
2U4N Configuration Equipment Installation Figure 20 Inserting the server in the cabinet CL4962 6. To further secure the rail assembly and server in the cabinet, insert and tighten a small stabilizer screw directly behind each bezel latch. Figure 21 Installing the stabilizer screws CL4963 7.
2U4N Configuration Equipment Installation 3. Align one of the inner rails to the mounting position on the management switch. 4. Attach the inner rail to the management switch with the three flat head Philips screws. 5. Repeat previous two steps to attach the inner rail to other side of the management switch.
2U4N Configuration Equipment Installation 8. Login to the switch again , this time the password is Scaleio123 9. Type and click enter. enable 10. Type terminal (or ) to enter global configuration mode. configure config 11. Type to enter interface configuration mode for the interface management 0 virtual interface which accesses management port 1 on the currently active supervisor.
2U4N Configuration Equipment Installation Configure the data switch This procedure is used to configure the data switch. Procedure 1. Copy the configuration filename from the USB flash drive using the following command: enable 2. Then, copy usb1:<configuration file>startup-config Example: localhost> enable locathot>...
Page 48
2U4N Configuration Equipment Installation Note Arista switches are by default set to Use Jumbo Frames; no additional configuration is needed on switches for Performance Best Practice. 16. Repeat this procedure if required to configure additional data switches. VxRack Node Hardware Installation Guide...
CHAPTER 4 Wiring Diagrams for a 2U1N Configuration This chapter provides the power, management, and data wiring diagrams for the 2U1N configuration. Topics included: Guidelines for wiring a 2U1N configuration............50 Single-phase wiring for 2U1N configuration ............51 Three-phase delta wiring for 2U1N configuration ..........
Wiring Diagrams for a 2U1N Configuration Guidelines for wiring a 2U1N configuration Use the following illustration as reference for connectors on rear of the servers: Figure 22 Connectors on rear of servers Use the wiring diagrams to connect power, management, and data cables. As cables are installed and connected, dress and tie cables frequently so that excess slack does not interfere with routing of adjacent cables.
Wiring Diagrams for a 2U1N Configuration Single-phase wiring for 2U1N configuration Use Figure 25 to connect power cables in cabinets with single-phase power distribution. Single-phase wiring for 2U1N configuration...
Wiring Diagrams for a 2U1N Configuration Three-phase delta wiring for 2U1N configuration Use Figure 26 to connect power cables in cabinets with three-phase delta power distribution. Three-phase delta wiring for 2U1N configuration...
Wiring Diagrams for a 2U1N Configuration Three-phase wye wiring for 2U1N configuration Use Figure 27 to connect power cables in cabinets with three-phase wye power distribution. Three-phase wye wiring for 2U1N configuration...
Wiring Diagrams for a 2U1N Configuration Management network wiring for 2U1N configuration Use Figure 28 and Table 9 to connect the management network cables. Note Space on the page with Figure 28 does not provide enough space to illustrate cabling of the maximum number of nodes in the management network.
Wiring Diagrams for a 2U1N Configuration Table 9 Management network cabling (continued) Management Switch Arista 7010 Source Destination Node17 BMC Management Switch Port 29 Node17 NIC1 Management Switch Port 31 Data Network Switch A Mgmt Port Management Switch Port 47 Data Network Switch B Mgmt Port Management Switch Port 48 Management Server NIC1...
Wiring Diagrams for a 2U1N Configuration Table 10 Data network A cabling Data Switch A Source Destination Node 1 Onboard Port 0 Data Network Switch A Port 2 Node 1 Mezzanine Port 0 Data Network Switch B Port 4 Node 2 Onboard Port 0 Data Network Switch A Port 6 Node 2 Mezzanine Port 0 Data Network Switch B Port 8...
Wiring Diagrams for a 2U1N Configuration Table 10 Data network A cabling (continued) Data Switch A Node 16 Mezzanine Port 0 Data Network Switch B Port 27 Node 17 Onboard Port 0 Data Network Switch A Port 29 Node 17 Mezzanine Port 0 Data Network Switch B Port 31 Data network B wiring for 2U1N configuration Use Figure 30 and Table 11 to connect the data network B cables.
Wiring Diagrams for a 2U1N Configuration Table 11 Data network B cabling Data Switch B Source Destination Node 1 Onboard Port 1 Data Network Switch B Port 2 Node 1 Mezzanine Port 1 Data Network Switch A Port 4 Node 2 Onboard Port 1 Data Network Switch B Port 6 Node 2 Mezzanine Port 1 Data Network Switch A Port 8...
Page 66
Wiring Diagrams for a 2U1N Configuration Table 11 Data network B cabling (continued) Data Switch B Node 16 Mezzanine Port 1 Data Network Switch A Port 27 Node 17 Onboard Port 1 Data Network Switch B Port 29 Node 17 Mezzanine Port 1 Data Network Switch A Port 31 VxRack Node Hardware Installation Guide...
CHAPTER 5 Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution This chapter provides the power, management, and data wiring diagrams for 2U4N configuration installed in a cabinet with single-phase power distribution. Topics included: Guidelines for wiring a 2U4N configuration in a single-phase cabinet....68 Single-phase wiring for 2U4N configuration ............69...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Guidelines for wiring a 2U4N configuration in a single-phase cabinet Use the following illustration as reference for connectors on rear of the servers: Figure 29 Connectors on rear of servers Use the wiring diagrams to connect power, management, and data cables.
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Power Single-phase wiring for 2U4N configuration on page 69 Management A networkManagement network A wiring for 2U4N configuration in a single-phase cabinet on page 71 Data network: Data network A nodes 1 - 3 and 9 - 11 wiring for 2U4N configuration in a single- phase cabinet on page 76...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Figure 30 Single-phase power distribution VxRack Node Hardware Installation Guide...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Management network A wiring for 2U4N configuration in a single-phase cabinet Use Figure 33 and the table that follows to connect the management network A cables. Note Space on the page with Figure 33 does not provide enough space to illustrate cabling of the maximum number of nodes in management network A.
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Figure 31 Management network A VxRack Node Hardware Installation Guide...
Page 73
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Management network A wiring for 2U4N configuration in a single-phase cabinet...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Management network B wiring for 2U4N configuration in a single-phase cabinet Use Figure 34 and the table that follows to connect the management network B cables. VxRack Node Hardware Installation Guide...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Figure 32 Management network B Management network B wiring for 2U4N configuration in a single-phase cabinet...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Data network A nodes 1 - 3 and 9 - 11 wiring for 2U4N configuration in a single-phase cabinet Use Figure 35 and table that follows to connect the data network A cables for nodes 1 - 3 and 9 - 11.
Page 77
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Figure 33 Data network A nodes 1-3 and 9-11 Data network A nodes 1 - 3 and 9 - 11 wiring for 2U4N configuration in a single-phase cabinet...
Page 78
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution VxRack Node Hardware Installation Guide...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Data network A nodes 4 - 8 wiring for 2U4N configuration in a single-phase cabinet Use Figure 36 and the table that follows to connect the data network A for nodes 4 - Note Space on the page with Figure 36 does not provide enough space to illustrate cabling of the maximum number of nodes in data network A, nodes 4 - 8.
Page 80
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Figure 34 Data network A, nodes 4 - 8 VxRack Node Hardware Installation Guide...
Page 81
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Data Switch A Source Destination Node4 MB1 Mezz0 Port0 Data Network Switch A Port 95 Node4 MB1 Mezz1 Port1 Data Network Switch A Port 93 Node4 MB2 Mezz0 Port0 Data Network Switch A Port 91 Node4 MB2 Mezz1 Port1 Data Network Switch A Port 89...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Data Switch A Source Destination Node8 MB1 Mezz1 Port1 Data Network Switch A Port 38 Node8 MB2 Mezz0 Port0 Data Network Switch A Port 36 Node8 MB2 Mezz1 Port1 Data Network Switch A Port 34 Node8 MB3 Mezz0 Port0 Data Network Switch A Port 10...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Figure 35 Data network B, nodes 1 - 3 and 9 - 11 Data network B nodes 1 - 3 and 9 - 11 wiring for 2U4N configuration in a single-phase cabinet...
Page 84
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution VxRack Node Hardware Installation Guide...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Data network B nodes 4 - 8 wiring for 2U4N configuration in a single-phase cabinet Use Figure 38 and table that follows to connect the data network B for nodes 4 - 8. Note Space on the page with Figure 38 does not provide enough space to illustrate cabling of the maximum number of nodes in data network B, nodes 4 - 8.
Page 86
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Figure 36 Data network B, nodes 4 - 8 VxRack Node Hardware Installation Guide...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Data network C nodes 12 - 14 wiring for 2U4N configuration in a single-phase cabinet Use Figure 39 and the table that follows to connect the data network C for nodes 12 - Data network C nodes 12 - 14 wiring for 2U4N configuration in a single-phase cabinet...
Page 88
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Figure 37 Data network C nodes 12 - 14 VxRack Node Hardware Installation Guide...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Data network D nodes 12 - 14 wiring for 2U4N configuration in a single-phase cabinet Use Figure 40 and the table that follows to connect the data network D for nodes 12 - Data network D nodes 12 - 14 wiring for 2U4N configuration in a single-phase cabinet...
Page 90
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Figure 38 Data network D nodes 12 - 14 VxRack Node Hardware Installation Guide...
Page 91
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution Data network D nodes 12 - 14 wiring for 2U4N configuration in a single-phase cabinet...
Page 92
Wiring Diagrams for a 2U4N Configuration in a Cabinet with Single-Phase Power Distribution VxRack Node Hardware Installation Guide...
CHAPTER 6 Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution This chapter provides the power, management, and data wiring diagrams for 2U4N configuration installed in a cabinet with 3-phase delta or 3-phase wye power distribution.
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Guidelines for wiring a 2U4N configuration in a 3-phase cabinet Use the following illustration as reference for connectors on rear of the servers: Figure 39 Connectors on rear of servers Use the wiring diagrams to connect power, management, and data cables.
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Power(as applicable to power distribution in the cabinet): Three-phase delta wiring for 2U4N configuration on page 95 Three-phase wye wiring for 2U4N configuration on page 97 Management A network Management network A wiring for 2U4N configuration in...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Figure 40 Three-phase delta power distribution VxRack Node Hardware Installation Guide...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Three-phase wye wiring for 2U4N configuration Use Figure 43 to connect power cables in cabinets with three-phase wye power distribution. Three-phase wye wiring for 2U4N configuration...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Figure 41 Three-phase wye power distribution VxRack Node Hardware Installation Guide...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Management network A wiring for 2U4N configuration in a 3-phase cabinet Use Figure 44 and table that follows to connect the management network A cables. Note Space on the page with Figure 44 does not provide enough space to illustrate cabling of the maximum number of nodes in management network A.
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Figure 42 Management network A VxRack Node Hardware Installation Guide...
Page 101
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Management network A wiring for 2U4N configuration in a 3-phase cabinet...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Data network A nodes 1 - 3 and 9 - 11 wiring for 2U4N configuration in a 3-phase cabinet Use Figure 45 and table that follows to connect the data network A cables for nodes 1 - 3 and 9 - 11.
Page 103
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Figure 43 Data network A nodes 1 - 3 and 9 - 11 Data network A nodes 1 - 3 and 9 - 11 wiring for 2U4N configuration in a 3-phase cabinet...
Page 104
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution VxRack Node Hardware Installation Guide...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Data network A nodes 4 - 8 wiring for 2U4N configuration in a 3-phase cabinet Use Figure 46 and the table that follows to connect the data network A for nodes 4 - Note Space on the page with Figure 46 does not provide enough space to illustrate cabling of the maximum number of nodes in data network A, nodes 4 - 8.
Page 106
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Figure 44 Data network A nodes 4 - 8 VxRack Node Hardware Installation Guide...
Page 107
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Data Switch A Source Destination Node4 MB1 Mezz0 Port0 Data Network Switch A Port 95 Node4 MB1 Mezz1 Port1 Data Network Switch A Port 93 Node4 MB2 Mezz0 Port0 Data Network Switch A Port 91 Node4 MB2 Mezz1 Port1...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Data Switch A Source Destination Node8 MB1 Mezz1 Port1 Data Network Switch A Port 38 Node8 MB2 Mezz0 Port0 Data Network Switch A Port 36 Node8 MB2 Mezz1 Port1 Data Network Switch A Port 34 Node8 MB3 Mezz0 Port0...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Figure 45 Data network B nodes 1 - 3 and 9 - 11 Data network B nodes 1 - 3 and 9 - 11 wiring for 2U4N configuration in a 3-phase cabinet...
Page 110
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution VxRack Node Hardware Installation Guide...
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Data network B nodes 4 - 8 wiring for 2U4N configuration in a 3-phase cabinet Use Figure 48 and table that follows to connect the data network B for nodes 4 - 8. Note Space on the page with Figure 48 does not provide enough space to illustrate cabling of the maximum number of nodes in data network B, nodes 4 - 8.
Page 112
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Figure 46 Data network B nodes 4 - 8 VxRack Node Hardware Installation Guide...
Page 113
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution Data network B nodes 4 - 8 wiring for 2U4N configuration in a 3-phase cabinet...
Page 114
Wiring Diagrams for a 2U4N Configuration in a Cabinet with 3-Phase Delta or 3-Phase Wye Power Distribution VxRack Node Hardware Installation Guide...
CHAPTER 7 Update the Install Database This chapter provides information to update the install database after all work is completed. The chapter contains the following topic: Update the install database................116 Update the Install Database...
After all work is complete, use this procedure to update the install database. Procedure 1. Open a web browser and navigate to the Dell EMC Business Services website at http://emc.force.com/BusinessServices. 2. In the Post Sales area, click Install Base Group.