hit counter script

Siemens SIMATIC ET 200MP Manual page 50

Interface module
Hide thumbs Also See for SIMATIC ET 200MP:
Table of Contents

Advertisement

Response times
B.1 Response times of the ET 200MP
Example configuration for the calculation of the backplane bus cycle time
The following are used in the example:
Table B- 1
Example configuration for the calculation of the backplane bus cycle time
I/O module
Analog output module AQ 4xU/I ST
Analog output module AQ 4xU/I ST with value
status
Digital output module DQ 32x24VDC/0.5A ST
with value status
Digital input module DI 32x24VDC HF
Analog input module AI 8xU/I/RTD/TC ST
Sum
Example calculation of the backplane bus cycle time
Backplane bus cycle time in μs:
● (20 + 3) x 0.0668 + 1.6131 = 3.1495 ≈ 4 μs (rounded)
plus
● (25 + 4) x 0.0959 + 2.5901 = 5.3712 ≈ 6 μs (rounded)
plus
● Operating system processing time 500 μs
Result of backplane bus cycle time
Backplane bus cycle time = 510 μs
50
Output data
Input data
in bytes
in bytes
8
-
8
1
4
4
-
4
-
16
20
25
IM 155-5 PN ST interface module (6ES7155-5AA00-0AB0)
Number of
Number of
output
input
addresses
addresses
1
-
1
1
1
1
-
1
-
1
3
4
Manual, 08/2013, A5E03612323-02

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic im 155-5 pn st6es7155-5aa00-0ab0

Table of Contents