Duct Mounted Electronic Air Cleaner
APPLICATION
The high efficiency F58F Electronic Air Cleaner is
mounted in the return air duct of a forced air heating,
cooling, or ventilating system. It captures a significant
amount of airborne particles 0.5 microns and larger from
the air circulated through it. All models have an internal
airflow switch to operate the F58F when the system
blower is on.
PLANNING THE INSTALLATION
Review Installation Requirements
The air cleaner should be installed where all the air
passing through the system circulates through it. The best
location is in the return air duct next to the blower compart-
ment so the air cleaner can help keep the blower motor
and evaporator coils clean.
IMPORTANT
Do not mount in the discharge air duct.
For most efficient air cleaning, airflow must be spread
evenly across the face of the air cleaner. If the duct is a
different size than the air cleaner cabinet, gradual transi-
tions are recommended. If the duct turns sharply just
before the air cleaner, turning vanes are recommended.
Applications with Air Conditioning
The air cleaner should be installed upstream from the
evaporator coil. The air cleaner will help keep the coil
clean, reducing maintenance.
Applications with a Humidifier
An evaporative humidifier can be mounted upstream from
the air cleaner. An atomizing humidifier should be mounted
downstream from the air cleaner, even though hard water
salts will be blown into the living space and deposited as
dust. If an atomizing humidifier must be mounted upstream
from the air cleaner:
1. Mount it as far upstream as possible from the
air cleaner.
2. Install a standard disposable furnace filter between
the humidifier and the air cleaner to trap water
droplets and hard water salts.
3. Frequently clean the air cleaner to prevent a hard
water salt buildup.
NOTE: The volume of water that passes through an
atomizing humidifier can overload the air cleaner,
resulting in hard water salts being deposited as
dust in the living space.
®U.S. Registered Trademark
Copyright © 1998 Honeywell Inc. • All Rights Reserved
INSTALLATION INSTRUCTIONS
Applications with an Activated Carbon Filter
An activated carbon (charcoal) filter can be used to remove
odors or other gaseous contaminants (not particle-based) that
are not removed by the air cleaner. Locate the carbon filter:
• Downstream from the air cleaner. This means that dust
from the carbon filter will not be collected by the air
cleaner and will be deposited in the living space.
• Outside the air cleaner cabinet. Some carbon filters are
combustible and contact with high voltage could result
in smoke or fire.
• Where carbon granules cannot fall into the electronic
cell. If necessary, use a disposable furnace filter
between the carbon filter and the electronic cell.
• With proper transitions, if the activated carbon filter
requires a differently size duct than the air cleaner.
Allow 20 degrees expansion per side, per fitting.
NOTE: Honeywell does not offer carbon filters. Refer to
an activated carbon filter manufacturer for sizing
and application.
Applications with Outdoor Air Intake
Return air temperature must be at least 40°F (4°C). Lower
temperatures can cause ionizer wire failure. If outdoor air is
used, warm it upstream from the air cleaner by:
• Making sure the outdoor intake is far enough upstream
from the air cleaner so the return and outdoor air is
thoroughly mixed. Stratified air can dump a stream of
very cold air into one section of the air cleaner.
• Adding baffles upstream from the air cleaner to force
thorough air mixing.
• Installing a preheater if large amounts of outdoor air are
used. The preheater, which could be an electric strip
heater or hot water coil, should be controlled by a
thermostat. Hot water or steam coils should be
protected by a freeze-up control.
Optional W8600F
The F58F terminal board is recessed slightly so it or the wires
will not interfere with installation. The entire power supply box
can be unplugged and removed to provide access to the
terminals. The W8600F air cleaner monitor can be mounted in
the living area or in the furnace room. It should be located in a
convenient location to observe the display.
X-XX UL
F58F
69-0976B-1

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell F58C Series

  • Page 1 The air cleaner should be installed where all the air passing through the system circulates through it. The best NOTE: Honeywell does not offer carbon filters. Refer to location is in the return air duct next to the blower compart-...
  • Page 2: Choose Location

    F58F DUCT MOUNTED ELECTRONIC AIR CLEANER The air cleaner can be mounted in any position except with Choose Location the access door facing down. Choose a location that is readily accessible for regular inspection and cleaning. Allow at least 13 in. [330 mm] in Multiple electronic air cleaner installations are needed for front of the access door for removing the prefilter and many commercial systems.
  • Page 3: Installation

    F58F DUCT MOUNTED ELECTRONIC AIR CLEANER Determine Duct Design Requirements INSTALLATION The air cleaner is adaptable to all new or existing forced air heating, cooling and ventilating systems used in residential When Installing this Product… applications. Transitions, turning vanes, or offsets may be 1.
  • Page 4 F58F DUCT MOUNTED ELECTRONIC AIR CLEANER Fasten Cabinet To Ductwork W8600F Install a transition if the opening in the air cleaner cabinet and the duct are different sizes. See Fig. 2. Fasten the other side of the cabinet to the elbow using sheet metal screws, rivets, or slip joints as appropriate.
  • Page 5: Complete Wiring

    F58F DUCT MOUNTED ELECTRONIC AIR CLEANER 3. Insert the divided tab into the square hole. 4. Fold up the wedge and insert it into the divided tab to lock the handle in place. If necessary, press with a blunt instrument like the end of a pliers. DOWNSTREAM AIRFLOW Reassemble Air Cleaner...
  • Page 6 F58F DUCT MOUNTED ELECTRONIC AIR CLEANER BLACK COLLECTOR TEST RED IONIZER BUTTON BLACK CONTACT BOARD BLACK BLACK POWER SUPPLY BROWN BLACK BLUE ORANGE GRAY VIOLET GREEN BLACK BLACK BLACK 1 INTERLOCK SWITCH. W4 W2 W1 W3 2 SHORTING BAR. 3 AIRFLOW SWITCH DISABLE JUMPER. 4 OPTIONAL W8600F AIR CLEANER MONITOR.
  • Page 7: Operation

    F58F DUCT MOUNTED ELECTRONIC AIR CLEANER Alternatively, the F58F can be wired with conduit. OPERATION 1. Open access door. 2. Remove and retain the (2) screws from the front of Large particles (lint, hair) are caught by the prefilter. As the the power box and the (2) screws from the sides of dirty air passes through the intense high voltage electric the power box.
  • Page 8: Troubleshooting And Service

    F58F DUCT MOUNTED ELECTRONIC AIR CLEANER Modification To Reduce Ozone Odor TROUBLESHOOTING AND SERVICE WARNING WARNING Electric shock hazard. Can cause personal injury. Electrical Shock Hazard. Always disconnect power and open the access Can cause personal injury or door before opening the power supply cover. equipment damage.
  • Page 9 F58F DUCT MOUNTED ELECTRONIC AIR CLEANER START TO USE THIS CHART: FOLLOW THE STEPS IN ORDER; DO NOT SKIP AROUND. EACH TIME YOU ISOLATE AND FIX A PROBLEM, GO BACK TO START. REPEAT ALL THE STEPS UNTIL THE AIR CLEANER CHECKS OUT OK. MAKE SURE ELECTRONIC CELL(S) ARE CLEAN, DRY AND PROPERLY INSTALLED.
  • Page 10 F58F DUCT MOUNTED ELECTRONIC AIR CLEANER REMOVE POWER BOX FROM AIR CLEANER AND REMOVE THE COVER. M6168A Fig. 13. Removing the power box. M10609 Fig. 14. Move J5 shorting bar to reduce ozone production about 20-25 percent. 69-0976B—1...
  • Page 11 F58F DUCT MOUNTED ELECTRONIC AIR CLEANER 69-0976B—1...
  • Page 12 F58F DUCT MOUNTED ELECTRONIC AIR CLEANER Automaiton and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 69-0976B—1 J.H. Rev. 8-98 www.honeywell.com/yourhome 69-0976B—1...
  • Page 13: Planification De L'installation

    3. Nettoyer le filtre à air fréquemment pour empêcher l’accumulation de sédiments d’eau dure. ®Marque de commerce enregistrée aux États-Unis. X-XX UL 69-0976B-1 Copyright © 1998 Honeywell Inc. • Tous droits réservés 69-0976B—1...
  • Page 14: Raccords De Gaines Requis

    FILTRE À AIR ÉLECTRONIQUE POUR MONTAGE EN GAINE F58F F58F DUCT MOUNTED ELECTRONIC AIR CLEANER Ajout du W8600F (en option) Raccords de gaines requis Le bornier du F58F est un peu en retrait pour éviter que la Le filtre à air se combine à tout système résidentiel de plaque à...
  • Page 15 FILTRE À AIR ÉLECTRONIQUE POUR MONTAGE EN GAINE F58F F58F DUCT MOUNTED ELECTRONIC AIR CLEANER PRÉVOIR UN DÉGAGEMENT MINIMUM DE 330 MM [13 PO] POUR ENLEVER LA CELLULE ET LA TOILE MÉTALLIQUE. MF5769 Fig. 1. Installation typique de plusieurs filtres à air électroniques F58F. MODIFIER L’ENCOMBREMENT DE LA GAINE AVEC DES RACCORDS DE TRANSITION POUR MINIMISER LA TURBULENCE.
  • Page 16 FILTRE À AIR ÉLECTRONIQUE POUR MONTAGE EN GAINE F58F F58F DUCT MOUNTED ELECTRONIC AIR CLEANER UTILISATION TYPIQUE DU RACCORD DE DÉRIVATION DE LA GAINE POUR ASSURER UN DÉGAGEMENT W8600F SUFFISANT POUR LE FILTRE À AIR ÉLECTRONIQUE. FILTRE À AIR ÉLECTRONIQUE RACCORD DE BORNIER SUR MOINS DE...
  • Page 17: Installer Les Déflecteurs

    FILTRE À AIR ÉLECTRONIQUE POUR MONTAGE EN GAINE F58F F58F DUCT MOUNTED ELECTRONIC AIR CLEANER Si la position de la clavette doit être inversée : Installer les déflecteurs 1. Retirer la cellule électronique. Installer les déflecteurs à l’intérieur du raccord coudé (à 2.
  • Page 18 FILTRE À AIR ÉLECTRONIQUE POUR MONTAGE EN GAINE F58F F58F DUCT MOUNTED ELECTRONIC AIR CLEANER 3. Insérer la languette divisée dans le trou carré. • Tous les raccordements doivent être conformes aux 4. Plier la cale et l’insérer dans la languette divisée règlements et aux codes locaux.
  • Page 19: Vérifier L'installation

    FILTRE À AIR ÉLECTRONIQUE POUR MONTAGE EN GAINE F58F F58F DUCT MOUNTED ELECTRONIC AIR CLEANER Le F58F peut aussi être raccordé à l’aide d’un fil FONCTIONNEMENT conducteur. 1. Ouvrir la porte d’accès. Les grosses particules (charpie, poils) sont captées par le 2.
  • Page 20: Dépannage Et Entretien

    FILTRE À AIR ÉLECTRONIQUE POUR MONTAGE EN GAINE F58F F58F DUCT MOUNTED ELECTRONIC AIR CLEANER Réduction de l’odeur d’ozone DÉPANNAGE ET ENTRETIEN AVERTISSEMENT AVERTISSEMENT Risque de choc électrique. Risque de choc électrique. Peut causer des blessures. Peut causer des blessures ou endommager Toujours couper l’alimentation et ouvrir la porte l’équipement.
  • Page 21 FILTRE À AIR ÉLECTRONIQUE POUR MONTAGE EN GAINE F58F F58F DUCT MOUNTED ELECTRONIC AIR CLEANER DÉBUT POUR UTILISER CE DIAGRAMME : 1. SUIVRE LES ÉTAPES DANS L’ORDRE, NE PAS SAUTER D’ÉTAPE. 2. CHAQUE FOIS QUE VOUS TROUVEZ UN PROBLÈME ET QUE VOUS LE RÉPAREZ, RETOURNEZ AU DÉBUT.
  • Page 22 FILTRE À AIR ÉLECTRONIQUE POUR MONTAGE EN GAINE F58F F58F DUCT MOUNTED ELECTRONIC AIR CLEANER RETIRER LE BLOC D’ALIMENTATION DU FILTRE À AIR ET ENLEVER LE COUVERCLE. MF6168A Fig. 13. Retirer le bloc d’alimentation du filtre à air pour enlever le couvercle. M10609 Fig.
  • Page 23 FILTRE À AIR ÉLECTRONIQUE POUR MONTAGE EN GAINE F58F F58F DUCT MOUNTED ELECTRONIC AIR CLEANER 69-0976B—1 69-0976B—1...
  • Page 24 FILTRE À AIR ÉLECTRONIQUE POUR MONTAGE EN GAINE F58F F58F DUCT MOUNTED ELECTRONIC AIR CLEANER Régulation résidentielle et commerciale Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35, Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 69-0976B—1 G.H.

This manual is also suitable for:

F58f series

Table of Contents