Venturi Manifold for
VR9105V, F and VR9205V, F
Gas Controls
APPLICATION
The Venturi manifold system is a gas/air mixing unit that
allows modulation of a premix burner with constant gas/air
ratio down to 20% of maximum load. It is to be used in
combination with a fan and a Honeywell 1:1 regulating gas
valve.
Modulation is accomplished by changing the fan speed.
The outlet pressure of the gas valve is regulated to
ambient pressure by the gas valve.
The Venturi generates negative pressure against ambient
pressure by which the gas is drawn through the gas valve
outlet.
The Venturi manifold can be trimmed to the correct gas/air
ratio by turning the throttle screw.
Valve capacities are shown in Table 1.
Table 1. Reference load
Inlet and outlet
Venturi
45900444-001
45900444-002
45900444-003
45900446-050
c
45900446-051
45900446-052
45900446-053
45900446-055
a
The inlet and outlet codes are visible on the top and
bottom of the Venturis throat.
b
The reference load is the total appliance load at which
the Venturi manifold has an overall pressure drop of 1.8
in. WC.
c
Suitable only in specially adapted applications.
Reference load
a
code
(KBtu/h)
001
191
002
137
003
92
050
280
051
246
052
157
053
116
055
55
INSTALLATION INSTRUCTIONS
SPECIFICATIONS
Gas Control:
VR9105V, F and VR9205V, F direct ignition gas control
with integrated 1:1 regulator. See installation instruc-
tions, form 69-2471EF.
Ambient Temperature Range: 32°F to 158°F.
Reference Load: See Table 1.
Natural-LP Gas Conversion Kits: See Table 2.
Approvals: CSA Design Certificate. File # 158158.
PLANNING THE
INSTALLATION
WARNING
b
Fire or Explosion Hazard.
Can cause property damage, severe injury,
or death.
Follow these warnings exactly:
1. Plan the installation as outlined below.
2. Plan for frequent maintenance as described in
the maintenance section.
Heavy demands are made on controls when direct
ignition systems are used on central heating equipment
in barns, greenhouses, and commercial properties and
on heating appliances such as commercial cookers,
agricultural equipment, industrial heating equipment and
pool heaters.
Special steps may be required to prevent nuisance
shutdowns and control failure due to frequent cycling,
severe environmental conditions related to moisture,
corrosive chemicals, dust or excessive heat. These
applications require Honeywell Combustion Engineering
review, so contact your Honeywell Sales Representative
for assistance.
Review the following conditions that can apply to your
specific installation and follow the precautions
suggested.
69-2484EF-01

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Venturi VR9105V

  • Page 1 VR9105V, F and VR9205V, F direct ignition gas control ratio down to 20% of maximum load. It is to be used in with integrated 1:1 regulator. See installation instruc- combination with a fan and a Honeywell 1:1 regulating gas tions, form 69-2471EF. valve.
  • Page 2: Installation

    VENTURI MANIFOLD FOR VR9105V, F AND VR9205V, F GAS CONTROLS Frequent Cycling Corrosive Chemicals The Venturi control is designed for use on appliances that Corrosive chemicals can attack the control, eventually typically cycle three to four times an hour during only the causing failure.
  • Page 3: Mounting Position

    VENTURI MANIFOLD FOR VR9105V, F AND VR9205V, F GAS CONTROLS Mounting position Converting Venturi Manifold from Natural Gas to LP Gas (or LP Gas The Venturi manifold can be mounted directly on the gas valve in horizontal or vertical position onto the side outlet, to Natural Gas) or in vertical position onto the end outlet.
  • Page 4: Maintenance

    Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limitée 35 Dynamic Drive ® U.S. Registered Trademark Toronto, Ontario M1V 4Z9 © 2010 Honeywell International Inc. 69-2484EF—01 T.D. Rev. 10-10 customer.honeywell.com Printed in U.S.A.
  • Page 5: Caractéristiques

    VR9205V, F avec régulateur 1:1 intégré. Voir la notice charge maximale. Il peut être utilisé avec un ventilateur et d'installation, formulaire 69-2471EF. un régulateur à gaz 1:1 Honeywell. Plage de température ambiante: 32 °F à 158 °F. La modulation s'accomplit en modifiant la vitesse du ventilateur.
  • Page 6 COLLECTEUR VENTURI POUR RÉGULATEURS À GAZ VR9105V, F ET VR9205V, F d'ingénierie de la combustion de Honeywell; contacter le humide, s'assurer que la circulation d'air autour du représentant commercial de Honeywell pour obtenir de régulateur est suffisante pour éviter la condensation.
  • Page 7: Position De Montage

    COLLECTEUR VENTURI POUR RÉGULATEURS À GAZ VR9105V, F ET VR9205V, F INSTALLATION S'assurer que l'entrée du Venturi n'est pas obstruée pour ne pas affecter le facteur d'air. Si la distance d'un autre composant de l'appareil à l'entrée Venturi est supérieure à 2 pouces, le facteur d'air et la charge de l'appareil ne sont Lors de l'installation de ce pas influencés.
  • Page 8: Entretien

    Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limitée 35, Dynamic Drive ® Marque de commerce déposée aux É.U. © 2010 Honeywell International Inc. Toronto (Ontario) M1V 4Z9 Tous droits réservés 69-2484EF—01 T.D. Rev. 10-10 customer.honeywell.com...