Advertisement
NOTE: If Optional Cover Plate is not required, see "UWP Mounting System installation".
Use the Optional Cover Plate when:
Insert R and C wires into designated terminals for primary AC power (C terminal is optional if batteries are installed, but it is recommended). Remove wires by depressing the terminal tabs.
Insert AA batteries for primary or backup power.
Set R Slider Tab.
NOTE: Slider Tabs for U terminals should be left in place for T6 Pro models.
UWP Mounting System
R/Rc slider tab
Note: Not all terminals may be used, depending on the system type that is being wired. The most commonly used terminals are shaded.
S | Input for wired indoor or outdoor sensors (TH6320U and TH6220U only) |
S | |
Y | Compressor contactor (stage 1) |
Y2 | Compressor contactor (stage 2) |
G | Fan Relay |
C | 24VAC common. For 2 transformer systems, use common wire from cooling transformer. |
U | Unused |
U | |
L/A-A | Heat Pump fault input (Common (C) wire required for LA/A) |
O/B | Changeover valve |
AUX - W2 | Auxiliary heat relay Heat relay (stage 2) |
E | Emergency Heat relay |
W | Heat relay (stage 1) |
K | Connect to K on Wire Saver Module** |
R | 24VAC power from heating transformer* |
Rc | 24VAC power from cooling transformer* |
* Terminal can be jumped using Slider Tab. See "Setting Slider Tabs" above.
** The THP9045A1023 Wire Saver Module is used on heat/cool systems when you only have four wires at the thermostat, and you need a fifth wire for a common wire. Use the K terminal in place of the Y and G terminals on conventional or heat pump systems to provide control of the fan and the compressor through a single wire—the unused wire then becomes your common wire. See THP9045 instructions for more information.
Shaded areas below apply only to TH6320U/TH6220U or as otherwise noted.
1H/1C System (1 transformer)
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor
C 24VAC common [3]
W Heat relay
G Fan relay
1H/1C System (2 transformers)
R Power (heating transformer) [1]
Rc Power (cooling transformer) [1]
Y Compressor contactor
C 24VAC common [3, 4]
W Heat relay
G Fan relay
Heat-only System
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
C 24VAC common [3]
W Heat relay
Heat-only System with Fan
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
C 24VAC common [3]
W Heat relay
G Fan relay
Heat-only System (Series 20) [5]
R Series 20 valve terminal "R" [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Series 20 valve terminal "W"
C 24VAC common [3]
W Series 20 valve terminal "B"
Cool-only System
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor
C 24VAC common [3]
G Fan relay
Heat-only System (power open zone valve) [5]
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
W Valve
C 24VAC common [3]
2H/2C System (1 transformer) [6]
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor (stage 1)
C 24VAC common [3]
W Heat relay (stage 1)
G Fan relay
W2 Heat relay (stage 2)
Y2 Compressor contactor (stage 2)
NOTES
Wire specifications: Use 18- to 22-gauge thermostat wire. Shielded cable is not required.
[1] Power supply. Provide disconnect means and overload protection as required.
[2] Move R-Slider Tab on UWP to the R setting. For more information, see "Setting Slider Tabs".
[3] Optional 24VAC common connection.
[4] Common connection must come from cooling transformer.
[5] In ISU set Heat system type to Radiant Heat. Set number of cool stages to 0.
[6] In Installer Setup, set system type to 2Heat/2Cool Conventional.
Shaded areas below apply only to TH6320U/TH6220U or as otherwise noted.
1H/1C Heat Pump System
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor
C 24VAC common [3]
O/B Changeover valve [7]
G Fan relay
W Do not use this terminal for heat pump applications!
2H/1C Heat Pump System [8]
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor
C 24VAC common [3]
O/B Changeover valve [7]
G Fan relay
Aux Auxiliary heat
E Emergency heat relay
L Heat pump fault input
W Do not use this terminal for heat pump applications!
2H/2C Heat Pump System (TH6320U only) [9]
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor (stage 1)
C 24VAC common [3]
O/B Changeover valve [7]
G Fan relay
Y2 Compressor contactor (stage 2)
L Heat pump fault input
W Do not use this terminal for heat pump applications!
3H/2C Heat Pump System (TH6320U only) [10]
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor (stage 1)
C 24VAC common [3]
O/B Changeover valve [7]
G Fan relay
Aux Auxiliary heat
E Emergency heat relay
Y2 Compressor contactor (stage 2)
L Heat pump fault input
W Do not use this terminal for heat pump applications!
Dual Fuel System (TH6320U / TH6220U only)
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor (stage 1)
C 24VAC common [3]
O/B Changeover valve [7]
G Fan relay
Aux Auxiliary heat
E Emergency heat relay
Y2 Compressor contactor (stage 2 - if needed) [11]
L Heat pump fault input
S Outdoor sensor
S Outdoor sensor
W Do not use this terminal for heat pump applications!
NOTES
Wire specifications: Use 18- to 22-gauge thermostat wire. Shielded cable is not required.
[1] Power supply. Provide disconnect means and overload protection as required.
[2] Move R-Slider Tab on UWP to the R setting. For more information, see "Setting Slider Tabs".
[3] Optional 24VAC common connection.
[6] In Installer Setup, set system type to 2Heat/2Cool Conventional.
[7] In Installer Setup, set changeover valve to O (for cool changeover) or B (for heat changeover).
[8] In ISU set Heat system type to Heat pump. 1 compressor and 1 stage of backup heat.
[9] In ISU set Heat system type to Heat pump. 2 compressors and 0 stage of backup heat.
[10] In ISU set Heat system type to Heat pump. 2 compressors and 1 stage of backup heat.
[11] Dual fuel with Y2 only for TH6320U.
Time
Date
NOTE: Available System modes vary by model and system settings.
System modes:
‒ Auto
‒ Heat
‒ Cool
‒ Em Heat
‒ Off
NOTE: Available Fan modes vary with system settings.
Fan modes:
‒ Auto: Fan runs only when the heating or cooling system is on.
‒ On: Fan is always on.
‒ Circ: Fan runs randomly about 33% of the time.
* Some alerts cannot be snoozed or cleared. Please call your local heating and cooling professional if this occurs. The heating and cooling system may require service.
NOTE: A complete list of all setup (ISU) parameters and options starts below.
NOTE: Depending on system settings, not all options may be available.
#ISU | ISU Name | ISU Options (factory default in bold) |
120 | Scheduling Options | 0 = Non-Programmable 2 = 5-2 Programmable 3 = 5-1-1 Programmable 4 = 7-Day Programmable |
125 | Temperature Indication Scale | 0 = Fahrenheit 1 = Celsius |
130 | Outdoor Sensor (TH6320U / TH6220U only) | 0 = None 1 = Wired Outdoor Sensor |
200 | Heating System Type | 1 = Conventional Forced Air Heat 2 = Heat Pump 3 = Radiant Heat 5 = None (Cool Only) |
205 | Heating Equipment Type | Conventional Forced Air Heat: 1 = Standard Efficiency Gas Forced Air 2 = High Efficiency Gas Forced Air 3 = Oil Forced Air 4 = Electric Forced Air 5 = Hot Water Fan Coil Heat Pump: 7 = Air to Air Heat Pump 8 = Geothermal Heat Pump Radiant Heat: 9 = Hot Water Radiant Heat 12 = Steam |
218 | Reversing Valve O/B | 0 = O (O/B in Cool) 1 = B (O/B in Heat) |
220 | Cool Stages / Compressor Stages 200=Conv / 200=HP | 0, 1, 2 Note: Only 1 compressor stage available on TH6210U model. Only 1 compressor stage available on TH6220U model if configured for heat pump. |
221 | Heat Stages / Backup Heat Stages | Heat Stages: 1, 2 Backup Heat Stages: 0, 1 |
230 | Fan Control in Heat | 1 = Equipment Controls Fan 2 = Thermostat Controls Fan |
253 | Aux/E terminal control (Fixed to "0" setting on all models except TH6320U) | 0 = Drive both Aux & E together 1 = Aux and E independent |
255 | Backup Heat Source (Heat Pump Only) (TH6320U / TH6220U only) | 1 = Electric Forced Air 2 = Gas/Oil Forced Air (or Fossil Forced Air) |
256 | Emergency Heat Source (TH6320U only) | 1 = Electric Forced Air 2 = Gas/Oil Forced Air (or Fossil Forced Air) |
260 | External Fossil Fuel Kit (TH6320U / TH6220U only) | 0 = Thermostat Controls Backup Heat 1 = External Fossil Fuel Kit Controls Backup Heat |
300 | System Changeover | 0 = Manual 1 = Automatic |
303 | Auto Changeover Differential | 0°F to 5°F 0.0°C to 2.5°C Note: Differential is NOT deadband. Honeywell uses an advanced algorithm that fixes deadband at 0°F. The differential setting is the minimum number of degrees from set-point needed to switch from the last mode running (heat or cool) to the opposite mode when the thermostat is in auto-changeover. This is more advanced than previous thermostats. |
340 | Backup Heat Droop | 0 = Comfort 2 = 2°F 3 = 3°F 4 = 4°F 5 = 5°F 6 = 6°F 7 = 7°F 8 = 8°F 9 = 9°F 10 = 10°F 11 = 11°F 12 = 12°F 13 = 13°F 14 = 14°F 15 = 15°F Note: 0 (comfort) setting only available if backup heat (ISU 255) is set to electric. |
350 | Upstage Timer for Backup Heat | 0 = Off 1 = 30 minutes 2 = 45 minutes 3 = 60 minutes 4 = 75 minutes 5 = 90 minutes 6 = 2 hours 7 = 3 hours 8 = 4 hours 9 = 5 hours 10 = 6 hours 11 = 8 hours 12 = 10 hours 13 = 12 hours 14 = 14 hours 16 = 16 hours |
355 | Compressor Lockout / Balance Point | -- = Off 5°F to 60°F (in 5°F increments) -15.0°C to 15.5°C (in 2.5°C or 3.0°C increments) Note: Use a wired sensor to set compressor lockout / balance point on TH6320U / TH6220U. |
356 | Outdoor Lockout Backup Heat | -- = Off 5°F to 65°F (in 5°F increments) -15.0°C to 18.5°C (in 2.5°C or 3.0°C increments) |
365 | Compressor Cycle Rate (Stage 1) | 1 - 6 |
366 | Compressor Cycle Rate (Stage 1) | 1 - 6 |
370 | Heating Cycle Rate (Stage 1) | 1 - 12 |
371 | Heating Cycle Rate (Stage 2) | 1 - 12 |
375 | Heating Cycle Rate Auxiliary Heat | 1 - 12 |
378 | Heating Cycle Rate Emergency Heat (TH6320U only) | 1 - 12 |
387 | Compressor Protection | 0 = Off 1 - 5 minutes |
425 | Adaptive Intelligent Recovery | 0 = No 1 = Yes Note: Adaptive Intelligent Recovery (AIR) is a comfort setting. Heating or cooling equipment will turn on earlier, ensuring the indoor temperature will match the setpoint at the scheduled time. |
430 | Minimum Cool Setpoint | 50°F to 99°F (50°F) 10.0°C to 37.0°C (10.0°C) |
431 | Maximum Heat Setpoint | 40°F to 90°F (90°F) 4.5°C to 32.0°C (32.0°C) |
435 | Keypad Lockout | 0 = None 1 = Partial 2 = Full |
500 | Is Indoor Temperature Sensor WIRED to your system? (TH6320U / TH6220U only) | 0 = No 1 = Yes |
515 | Indoor Sensor type (TH6320U / TH6220U only) | 0 = 10k 1 = 20k |
520 | Which Sensors will be used for TEMPERATURE Control? (Multiple Sensors are Averaged) TH6320U / TH6220U only) | 1 = Thermostat Only 2 = Wired Only 3 = Average |
702 | Number of Air Filters | 0 - 2 |
711 | Air Filter 1 Replacement Reminder | 0 = Off 1 = 10 Run Time Days 2 = 20 Run Time Days 3 = 30 Run Time Days 4 = 45 Run Time Days 5 = 60 Run Time Days 6 = 90 Run Time Days 7 = 120 Run Time Days 8 = 150 Run Time Days 9 = 30 Calendar Days 10 = 45 Calendar Days 11 = 60 Calendar Days 12 = 75 Calendar Days 13 = 3 Calendar Months 14 = 4 Calendar Months 15 = 5 Calendar Months 16 = 6 Calendar Months 17 = 9 Calendar Months 18 = 12 Calendar Months 19 = 15 Calendar Months |
712 | Air Filter 2 Replacement Reminder | 0 = Off 1 = 10 Run Time Days 2 = 20 Run Time Days 3 = 30 Run Time Days 4 = 45 Run Time Days 5 = 60 Run Time Days 6 = 90 Run Time Days 7 = 120 Run Time Days 8 = 150 Run Time Days 9 = 30 Calendar Days 10 = 45 Calendar Days 11 = 60 Calendar Days 12 = 75 Calendar Days 13 = 3 Calendar Months 14 = 4 Calendar Months 15 = 5 Calendar Months 16 = 6 Calendar Months 17 = 9 Calendar Months 18 = 12 Calendar Months 19 = 15 Calendar Months |
1400 | Backlighting | 0 = On Demand 1 = Continuous Note: Common wire needed for continuous. |
1401 | Backlight brightness | 1 - 5 Note: Only displayed if continuous backlight selected. |
1410 | Clock Format | 12 / 24 |
1415 | Daylight Saving Time | 0 = Off 1 = On |
1420 | Temperature Display Offset | -3 to 3F (0) -1.5 to 1.5C (0) |
To perform a System Test:
System test | System status | |
Shaded areas below apply only to TH6320U/TH6220U or as otherwise noted. | ||
Heat | 0 | All Off |
1 | Heat Stage 1 on | |
2 | Heat Stage 2 also on | |
3 | Heat Stage 3 also on | |
Cool | 0 | All Off |
1 | Cool Stage 1 on | |
2 | Cool Stage 2 also on | |
Em Heat | 0 | All Off |
1 | Em Heat on | |
Fan | 0 | Fan Off |
1 | Fan On |
Temperature Ranges
Heat: 40°F to 90°F (4.5°C to 32.0°C)
Cool: 50°F to 99°F (10.0°C to 37.0°C)
Working Ambient Temperature
32°F to 120°F (0 C° to 48.9°C)
Operating Ambient Temperature
37°F to 102°F (2.8°C to 38.9°C)
Shipping Temperature
-20°F to 120°F (-28.9°C to 48.9°C)
Operating Relative Humidity
5% to 90% (non-condensing)
Physical Dimensions in inches (mm) (H x W x D)
4-1/16" H x 4-1/16" W x 1-5/32" D
103.5 mm H x 103.5 mm W x 29 mm D
Electrical Ratings
Terminal | Voltage (50/60Hz) | Running Current |
W Heating (Powerpile) | 20-30 Vac 750 mV DC | 0.02-1.0 A 100 mA DC |
W2 (Aux) Heating | 20-30 Vac | 0.02-1.0 A |
E Emergency Heat | 20-30 Vac | 0.02-0.5 A |
Y Compressor Stage 1 | 20-30 Vac | 0.02-1.0 A |
Y2 Compressor Stage 2 | 20-30 Vac | 0.02-1.0 A |
G Fan | 20-30 Vac | 0.02-0.5 A |
O/B Changeover | 20-30 Vac | 0.02-0.5 A |
L/A Input | 20-30 Vac | 0.02-0.5 A |
If you have difficulty with your thermostat, please try the following suggestions.
Most problems can be corrected quickly and easily.
Make sure heating and cooling temperatures are set to acceptable ranges:
ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.
EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.
For assistance with this product, please visit customer.honeywell.com.
Or call Honeywell Customer Care toll-free at 1-800-468-1502.
Pull to remove the thermostat from the UWP.
Home and Building Technologies
In the U.S.:
Honeywell
715 Peachtree Street NE
Atlanta, GA 30308
customer.honeywell.com
® U.S. Registered Trademark.
© 2018 Honeywell International Inc.
33-00181EFS—11 M.S. Rev. 02-18
Printed in U.S.A.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Thank you! Your question has been received!
Need Assistance?
Do you have a question about the T6 Pro that isn't answered in the manual? Leave your question here.