Page 1
E1070 Installation Manual English MA00776E, 2014-12...
Page 2
The information in this document is subject to change without notice and is provided as available at the time of printing. Mitsubishi Electric Automation Inc reserves the right to change any information without updating this publication. Mitsubishi Electric Automation Inc assumes no responsibility for any errors that may appear in this document.
UL and cUL Installation Caution: This section is only valid for UL labeled E1070 panels. • This equipment is suitable for use in non-hazardous locations only. [Combinations of equipment in your system are subject to investigation by the local authority having jurisdiction at the time of installation].
Page 5
X1/X100 Anytek connectors AWG 24–12 • These devices are Class 2 supplied programmable controllers (industrial PCs) for the use in industrial control equipment and are intended to be (front) panel mounted (Type 1 and 4x for indoor use only). Mitsubishi Electric, MA00776E...
• Replacing the battery incorrectly may result in explosion. Only use batteries recommended by the supplier. During the warranty period, the battery needs to be replaced by an authorized Mitsubishi Electric service center. Dismantling and Scrapping • The operator panel or parts thereof shall be recycled according to local regulations.
1. Unpack and check the delivery. If damage is found, notify the supplier. Panel cut out 245.5 x 138.5 mm (9.67 x 5.45 inch) Note: Place the operator panel on a stable surface during installation. Dropping it or letting it fall may cause damage. Mitsubishi Electric, MA00776E...
Page 8
For text strip 5.0 mm (0.20 inch) 18.0 mm (0.71 inch) 3. Secure the operator panel in position, using all the fastening holes and the provided brackets and screws: 0.5 - 1.0 Nm Mitsubishi Electric, MA00776E...
Page 9
Connect cable C. – Connect cable D. – 5. Carefully remove the laminated film over the operator panel display, to avoid static electricity that could damage the panel. Mitsubishi Electric, MA00776E...
Cables, peripheral equipment and accessories must be suitable for the application and its environment. For further details or recommendations, please refer to the supplier. Caution: When using a compact flash card, do not remove the card when the busy indicator is illuminated. Mitsubishi Electric, MA00776E...
UL and cUL: The power supply must conform with the requirements for class II power supplies. Ambient Vertical installation: 0 ° to +50 °C temperature Horizontal installation: 0 ° to +40 °C Storage temperature -20 ° to +70 °C Mitsubishi Electric, MA00776E...
Page 12
Parameter E1070 Relative humidity 5 - 85 % non-condensed Approvals and Information is available on the web site. certifications * See section Chemical Resistance for more information. Up to type number 7919A (2) From type number 7919B Mitsubishi Electric, MA00776E...
4.2.2 Screen Surface The screen surface on the operator panel withstands exposure to the following solvents without visible change: Solvents Time Acetone 10 minutes Isopropanol 10 minutes Toluene 5 hours Mitsubishi Electric, MA00776E...
Screen and Keyboard Protector For harsh environments and exposure to outdoor conditions, it is recommended to use a protective film to guard the screen and the keyboard from damage. These optional parts can be ordered from Mitsubishi Electric. Mitsubishi Electric, MA00776E...
Multi-wire conductors are better than single wire conductors with the same area. A braided conductor wire with the same area is even better. The best is a short, thick grounding braid. Mitsubishi Electric, MA00776E...
A more elegant method is to expand the shielded Ethernet cabling with a piece of unshielded Ethernet cable, see 4 in drawing above. You can ground the shield via an external 0.1 μ F/250 V plastic capacitor, see 5 in drawing above. This will connect the HF transients to the ground. Mitsubishi Electric, MA00776E...
Ferrite cores that are snapped onto the shielded cabling may remove minor disturbances. Large ferrite pieces that are snapped onto unshielded cabling and where the wires go 2-4 times around the cores are approximately 5-25 times more efficient. Mitsubishi Electric, MA00776E...
An approximate value of the net power consumption for the operator panel can be calculated by multiplying the supply voltage with the current drawn by the operator panel. This is assuming that all supplied power is transformed to heat. Mitsubishi Electric, MA00776E...
Transients on the 24 V feed are connected to the ground. • No risk that the 24 V feed is at a high level in relationship to the ground. This is not unusual since there is high static electricity. Mitsubishi Electric, MA00776E...
24 V feed, disturbances and grounding currents from the 0 V on the 24 V side will disrupt communication. Using this type of unit solves one problem but creates a larger problem! A substandard installation may work now, but problems may arise when other devices are connected. Mitsubishi Electric, MA00776E...
Set jumper pins 6-19. • Use CAB8. It offers the option of bus termination with pull-up/-down. It is also easy to connect the bus cable via the screw terminal block. See 4 in drawing above. Mitsubishi Electric, MA00776E...