Dimensions
Outer Enclosure
62mm deep
(behind ceiling for
MLS2021DF and
MLS2021DALIF)
Technical Data
MLS CABLE : 1.5mm unscreened twisted-pair (applicable when
detector is used as part of a full MLS Digital Managed Lighting
System): see Application Note AN4001
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3.0m
RANGE: Cone-shaped detection
pattern, diameter (at floor level)
= 2.4 x mounting height
OFF DELAY: 1 minute - 96 hours (adjustable)
PHOTOCELL: Adjustable 50-5000 lux via HP2000
OPERATING VOLTAGE: 230V ~ 50Hz (UK & Europe)
PRODUCT RATING AND RECOMMENDED CIRCUIT
PROTECTION: 10 Amps
MAXIMUM RECOMMENDED LOAD (VOLT-FREE): 6 Amps
MAXIMUM RECOMMENDED LOAD (DSI/DALI): 25 Ballasts
COLOUR: White (RAL9010)
MATERIAL: Flame retardant PC/ABS
WEIGHT: 210g (flush version), 187g (surface version)
IP RATING: 3X
OPERATING TEMPERATURE: 0 C to 40 C
Honeywell Ex-Or
St. Marks Court, North Street,
Horsham, West Sussex, RH12 1BW, UK
Tel:+44 (0)1942 719229
Fax: +44 (0)1942 508753
Email: technicalsales.ex-or@honeywell.com
www.ex-or.com
2
o
100mm
6.0m
o
8
Fascia
10mm
deep
2.5m
At the end of their useful life
the packaging and product
should be disposed of via a
suitable recycling centre.
Do not dispose of with normal
household waste.
Do not burn.
W4426G