AMC2 enclosure with 2 DIN rails Table of contents | en Table of contents System overview Components of the enclosure Parts included Mounting the enclosure Connections Connecting the devices Connecting the cables Connections for supporting Universal Power Supply 12 V mode operation 3.3.1...
| System overview AMC2 enclosure with 2 DIN rails System overview Components of the enclosure Figure 1.1: Components of the enclosure 2022-02 | V06 | F.01U.330.017 Bosch Security Systems B.V.
Page 5
AMC2 enclosure with 2 DIN rails System overview | en Position Description Cover grounding point Main grounding point Mounting rail for power supply unit (PSU) and Access Modular Controller (AMC2) AMC2 grounding point Cable knock-outs for reader and signal cables...
| System overview AMC2 enclosure with 2 DIN rails Parts included 2022-02 | V06 | F.01U.330.017 Bosch Security Systems B.V.
Page 7
AMC2 enclosure with 2 DIN rails System overview | en Position Description Cable ties to secure cables Three screw anchors S8 and M6 × 50 screws Bracket for cable fixing Cover grounding cable Battery cable Power supply cable (AMC2) Power supply cable (battery)
| Mounting the enclosure AMC2 enclosure with 2 DIN rails Mounting the enclosure The enclosure is designed to be mounted on a wall. Open the door lock of the enclosure with the provided key. Hold the enclosure at the desired position against the wall.
Page 9
AMC2 enclosure with 2 DIN rails Mounting the enclosure | en 401 mm 15,787 in 86,5 mm 200,5 mm 3,406 in 7,894 in 5 mm 0,197 in 10 mm 0,394 in 536 mm 21,102 in 5 mm 0,197 in 10 mm...
| Connections AMC2 enclosure with 2 DIN rails Connections Connecting the devices Precondition: Install readers and other peripheral devices as described in the corresponding technical documentation. 1 2 3 4 5 6 Power Supply RS-485 EXT AMC2 controller /...
Page 11
Disconnect the mains supply voltage before you work on the devices inside the enclosure. Installing the components Mount the Access Modular Controller (AMC2) on the right- hand side of the mounting rail. Mount the power supply unit on the left-hand side of the mounting rail.
| Connections AMC2 enclosure with 2 DIN rails Connecting the cables Connecting the AMC2 power cable (F) Connect the 7-pin plug to the AMC2 connector labeled POWER. Connect the 4-pin plug to the power supply connector labeled OK. Connect the 2-pin plug to the power supply connector labeled DC.
Page 13
AMC2 enclosure with 2 DIN rails Connections | en Figure 3.2: Connections of the LED indicator Connecting the tamper contact (H) Connect the loose ends of the tamper contact cable to the two-pin screw connector (marked with T) at the top of the AMC2.
| Connections AMC2 enclosure with 2 DIN rails Connecting the cover grounding cable (D) Connect the mounted grounding cable (see position D of Parts included, page 6 ) to the cover grounding point (Figure 1.1, position 1) and to the grounding point on the cover of the enclosure.
AMC2 enclosure with 2 DIN rails Connections | en 3.3.1 12 V mode operation Notice! Make sure that the power supply has the correct output voltage (12 V). Figure 3.3: 12 V mode with one battery (left); 12 V mode with two batteries (right) 12 V mode operation using one battery...
Page 16
| Connections AMC2 enclosure with 2 DIN rails 12 V mode operation using two batteries Set the switch of the power supply unit to 12 V. Connect the 2-pin plug to the power supply interface labeled BAT. Connect 1b (black) to the rechargeable negative (-) terminal of the battery.
AMC2 enclosure with 2 DIN rails Connections | en 3.3.2 24 V mode operation Notice! Make sure that the power supply has the correct output voltage (24 V). Figure 3.4: 24 V mode Connecting the battery cables Set the switch of the power supply unit to 24 V.
Page 18
| Connections AMC2 enclosure with 2 DIN rails Attach the connectors 2a and 2b to the bracket. Attach the bracket (C) to the back of the housing next to the batteries. 2022-02 | V06 | F.01U.330.017 Bosch Security Systems B.V.
Appendices | en Appendices UL requirements Notice! All cables connected to the AMC2 modules and the power supply are classified as Class 2 conductors. The battery cable and the AC input cable are non-power limited circuits. Notice! Maintain a minimum of 6.4 mm spacing between all class 2 or 3...
Visit the Bosch Building Technologies Academy website and have access to training courses, video tutorials and documents: www.boschsecurity.com/xc/en/support/training/ Visit the Bosch online product catalog for the latest technical documentation for this product. 2022-02 | V06 | F.01U.330.017 Bosch Security Systems B.V.