MS-9200UDLSC
Intelligent Addressable FACP
with Built-In Communicator
General
The Fire•Lite MS-9200UDLSC Rev 3 with Version 5.0 firmware
is a combination FACP (Fire Alarm Control Panel) and DACT
(Digital Alarm Communicator/Transmitter) all on one circuit
board. This compact intelligent addressable control panel has
an extensive list of powerful features.
While the MS-9200UDLSC may be used with a DCL configured
in the CLIP (Classic Loop Interface Protocol) mode, it can also
operate in LiteSpeed™ mode—Fire•Lite's latest polling technol-
ogy—for a quicker device response time. LiteSpeed's patented
technology polls 10 devices at a time. This improvement allows
a fully-loaded panel with up to 198 devices to report an incident
and activate the notification circuits in under 10 seconds. With
Litespeed polling, devices can be wired on standard twisted,
unshielded wire up to a distance of 3,000 meters.
The MS-9200UDLSC's quick-remove chassis protects the elec-
tronics during construction. The backbox can be installed allow-
ing field wiring to be pulled. When construction is completed, the
electronics can be quickly installed with just two bolts.
Features include removable terminal blocks, improved transient
protection, additional secondary ANN-BUS, increased resetta-
ble power, and remote sync output.
Available accessories include ANN-BUS devices as well as ACS
LED, graphic and LCD annunciators, and reverse polarity/city
box transmitter.
The integral DACT transmits system status (alarms, superviso-
ries, troubles, AC loss, etc.) to a Central Station via the public
switched telephone network. It also allows remote and local pro-
gramming of the control panel using the PS-Tools Upload/Down-
load utility. In addition, the control panel may be programmed or
interrogated off-site via the public switched telephone network.
Any personal computer with Windows® XP or greater, a com-
patible modem, and PS-Tools, the Fire•Lite Upload/Download
software kit, may serve as a Service Terminal. This allows
download of the entire program or upload of the entire program,
history file, walktest data, current status and system voltages.
The panel can also be programmed through the FACP's keypad
or via a standard PS-2 computer keyboard, which can be
plugged directly into the printed circuit board. This permits easy
typing of address labels and other programming information.
Version 5.0 firmware supports the following: ANN-bus devices,
AD355 (LiteSpeed), USB port, and NAC circuit diagnostics. A
new report has been added to the walk-test that lists untested
devices, Photo Supervisory and auto-resettable Drill (non-latch-
ing).
Features
• ULC Listed.
• On-board DACT.
• Remote site or local USB port upload/download, using PS-
Tools.
• Four Style Y (Class B) NAC circuits, which can be converted
to four Style Z (Class A) circuits with optional ZNAC-92 con-
verter module. (Up to 6.0 amps total NAC power when using
optional XRM-24B.)
• Selectable strobe synchronization for System Sensor, and
Wheelock.
• Primary and secondary ANN-BUS for connection to following
optional modules (cannot be used if ACS annunciators are
used):
– ANN-80C Remote LCD Annunciator
Addressable Fire Alarm Control Panel
– ANN-I/O LED Driver
– ANN-S/PG Printer Module
– ANN-RLY Relay Module
– ANN-LED Annunciator Module
– ANN-RLED Annunciator Module alarms only
• ACS/TERM:
– ACS Annunciators: Up to 32 ACM Series annunciators
(ACM-16AT or ACM-32 series). Cannot be used if ANN-
BUS devices are used.
– Terminal-mode Annunciators: Up to 32 LCD-80FC remote
annunciators.
• EIA-232 printer/PC interface (variable baud rate) on main cir-
cuit board, for use with optional ULC-listed printer PRN-6F.
• Integral 80-character LCD display with backlighting.
• Real-time clock/calendar with automatic daylight savings
control.
• History file with 1,000-event capacity.
• Maintenance alert warns when smoke detector dust accumu-
lation is excessive.
• Automatic device type-code verification.
• One person audible or silent walk test with walk-test log and
printout.
• Point trouble identification.
• Waterflow (nonsilenceable) selection per monitor point.
• System alarm verification selection per detector point.
• PAS (Positive Alarm Sequence) and presignal delay per
point.
NOTE: Only detectors may participate in PAS.
DCL LOOP:
• DCL can be configured for NFPA Style 4, 6, or 7 operation.
• DCL supports up to 198 addressable devices per loop (99
detectors and 99 monitor, control, or relay modules).
• DCL loop maximum length 3,000 m.
See installation manual for wire tables.
Canadian DF-60599:B
DF-60599:B • 02/11/2011 — Page 1 of 4