OPERATION PROCEDURE
6. Removing the indoor fan motor and the line flow fan
(1) Remove the panel and the corner box. (Refer to procedure 1)
(2) Remove the electrical box (Refer to procedure 2) and the
nozzle assembly (Refer to procedure 3).
(3) Remove the water cut. (See Photo 2)
(4) Remove the screw fixing the line flow fan. (See Photo 8)
(5) Remove 5 screws fixing the motor bed. (See Photo 7)
(6) Remove the lead wire of pipe thermistor from the hook of
motor bed. (See Photo 7)
(7) Remove the screw fixing motor band. (See Photo 7)
(8) Remove the motor bed together with fan motor and motor
band.
(9) Remove 3 screws fixing the left side of the heat exchanger.
(See Photo 9)
(10) Lift the heat exchanger, and pull out the line flow fan to the
lower-left.
Photo 9
Screws of the
left side of the
heat exchanger
7. Removing the pipe temperature thermistor/liquid
(TH2) and cond./ eva. temperature thermistor (TH5)
(1) Remove the panel and the corner box. (Refer to procedure 1)
(2) Remove the electrical box covers. (Refer to procedure 2)
(3) Remove the water cut. (See Photo 2)
(4) Remove the pipe temperature thermistor/liquid (TH2) and
cond./ eva. temperature thermistor (TH5).
(5) Disconnect the connector (CN44) on the indoor controller
board.
OCH661
PHOTOS
Photo 7
Photo 8
Photo 10
Cond. /eva. temp.
thermistor (TH5)
Pipe temp.
thermistor/liquid(TH2)
38
Screw of the motor band
Lead wire of pipe ther-
mistor
Screws of the motor
bed
Screw of the line flow
fan