Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 TABLE OF CONTENTS PAGE APPROVALS ............................... 1 SECTION 1: INTRODUCTION ......................... 1 System Overview ....................... 1 1.1.1 Fire Response Stage 1 - ALERT ................1 1.1.2 Fire Response Stage 2 - ALARM ................1 1.1.3...
Page 4
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 TABLE OF CONTENTS PAGE SECTION 3: CONTROLLER OPERATION...................... 8 FS7-130-SX Controller with FS7-2173 Detectors ..............8 Configuring the Controller and Detectors ................8 3.2.1 Using the FSC SX Software ................8 System Operating Modes ....................
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 APPROVALS FS7-130-SX and SX2 Controllers are manufactured in compliance with the requirements of the ISO- 9001 standard and are approved by: Factory Mutual (FM) for the United States ...
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 1.1.3 FirePic FirePic’s digital spectral data provides information facilitating the analysis of the probable cause of the fire. This data can be used to prevent a subsequent, potentially damaging fire from occurring.
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 1.3.1 Controller Outputs There are five 24 VDC, 1 A Fire Signal Output Relays in the Controller for interfacing with external equipment, such as a Fire Control Panel.
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 1.3.8 FireBusII All FS7-2173 Detectors are interconnected by the FireBusII. A maximum of 12 Detectors may be attached to any SX Controller and the maximum cable length is 1000 feet.
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 Figure 3: FS7-2173 Fire Detector Housing 3.00" 1.70' Detector View Side 2.00" 4.50" 1.69" Chassis m ount slide bracket 1.10" 1.4 FSC Junction Boxes FSC Junction Boxes (Part No. JB-4) and cables with self-locking connectors are used for connecting the FS7-2173 Detectors to the Controller.
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 SECTION 2: INSTALLATION 2.1 Wiring Requirements 2.1.1 Power Warning: Apply ONLY 24 VDC to the Controllers External Electrical Input Power Connections. 2.1.2 Controller Installation and Wiring The characteristics of the interconnecting cable for connecting the Detectors to the Controller must conform to the specifications for RS-485 or RS-232.
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 2.4 Mounting Locations 2.4.1 Mounting FS7-2173 Fire Detectors The FS7-2173 Fire Detectors have a 120-degree conical Field-of-View (viewing angle). It is recommended that the Detectors be positioned with the primary fire threat location aimed in the center of the Detector’s Field-of-View.
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 SECTION 3: CONTROLLER OPERATION 3.1 FS7-130-SX / -SX2 Controller with FS7-2173 Detectors The FS7-130-SX Controllers do NOT have an ON/OFF switch. The Controller turns ON when the external 24 VDC Power is turned on. When the Controller is powered up for the first time, the FS7-2173 Detector’s Green LED will illuminate briefly and then blink every 10 seconds to...
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 3.3.3 Detector Test The Controller automatically performs FS7-2173 Detector self-tests every 10 minutes (factory set) to check the operation of its Detector. While these Detector self-tests are occurring, the FS System 7 is still functional and able to detect and alarm to a fire.
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 SECTION 4: MAINTENANCE AND REPLACEMENT 4.1 Personnel Tests must be performed by qualified authorized personnel observing standard safety practices. WARNING: Hazardous voltages may be present during testing procedures.
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 4.3 Routine Maintenance and Calibration 4.3.1 FS7-2173 Detector The Detector has no calibration requirements or field calibration options. It is recommended to perform the Detector testing according to a periodic schedule.
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 SECTION 5: PINOUT DATA Table 2: FS7-2173 Fire Detector Male Connector Pin-outs Male Connector: FIRE DETECTOR (Factory Pre-Wired) WIRE COLOR Ground Return BLACK (Not Chassis Ground) Shield BARE Data “A”...
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 J2 Connector Pin # Description Zone 1 Alarm Relay - A contact Zone 1 Alarm Relay - B contact Zone 2 Alarm Relay - A contact Zone 2 Alarm Relay - B contact...
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 SECTION 6: ORDERING INFORMATION FS7-2173 Fire Detector, FS7-130-SX Controller, Test Lamps, Junction Boxes, and Cabling DESCRIPTION PART NUMBER FS7-2173 Fire Detector: Electro-Optical Fire Detector with Wide Band FS7-2173 Infrared Spectral Sensor Array.
Fire Sentry FS7-130-SX and FS-130-SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521-001_Rev E_08-12 INDEX COMM Fault, 7 Controller Module, 6 Communication Fault, 8 Detector, 6 Multi-Spectral Array, 1 Controller Module Fault, 8 Detector Normal Operation, 7 Cable, 9 Power Fault, 8...
Page 20
Asia Pacific Data may change, as well as legislation, and you are strongly advised to Honeywell Analytics Asia Pacific obtain copies of the most recently issued regulations, standards, and #508, Kolon Science Valley (I) guidelines.