Ductless Split Heat Pump Indoor Outdoor AW09EH2VHD 1U09EH2VHD AW12EH2VHD 1U12EH2VHD AW18EH2VHD 1U18EH2VHD Service Manual Please read this manual before installing this product. Design may vary b y model number. Keep this user manual for future reference. ● Table of Contents Safety Precautions/Introduction....................3...
Page 3
Introduction Table of Contents Safety Precautions ................................4 Warnings and Cautions ..................................4 Introduction to System ..............................5 ........................5 System Fundamentals..................................5 INTRODUCTION PAGE 3...
Page 4
Failure to follow any CAUTION may in some cases result in grave consequences.
Page 5
Introduction Introduction to System The inverter compressor system in the outdoor unit will vary Single Zone Ductless Split System Heat Pumps feature a wall the comfort requirement inside the conditioned space. If an mounted indoor fan/evaporator unit that receives refrigerant abnormal condition is detected by the system’s sensors, the from an inverter driven variable speed outdoor condensing system has the ability to take reactive measures.
Page 7
Outdoor Unit Controls and Components Table of Contents Outdoor Unit Introduction ..............................8 ............................ Outdoor Main Control Boa rd .............................. 9 Terminal Block .................................. 10 ● Reactor .................................... 10 Compressor ..................................10 Outdoor Fan Motor ................................10 Discharge Temperature Sensor ............................11 Defrost Temperature Sensor ............................
Page 8
Outdoor Unit Introduction The outdoor unit has two circuit boards, drives the compressor and main control an Inverter Power Module (IPM) that board (PCB) that manages system functions and inverter calculations. Sensors monitor key temperatures throughout the system to manage operational decisions. 4-Way Valve Accumulator Compressor...
Page 9
5VDC and 15VDC pulsing communication connection between the PCB and the IPM ●...
Page 15
Connector for coil temperature sensor and room temperature sensor ●...
Page 16
Terminal Block Ambient Temperature Sensor The unit terminal block receives electrical power from the The Ambient (room) Temperature Sensor is a negative outdoor unit. There are 4 connections for electrical wires. thermistor that will decrease in resistance with Terminals 1 and 2 are connected to terminals 1 and 2 of the increases in room air temperature.
DIP Switch DIP Switch Settings The PCB has a set of DIP switches that must be set when replacing the PCB. ● The replacement PCB is shipped with all switches set to the OFF position. ● Switch settings: J5 Selects remote code A or B. Normally set to connection state for code A operation.
Indoor Unit System Power To enter the cool mode, point the infrared remote control at The 230 Volt AC power for the system connects to terminals the indoor unit and press the power button, then press the 1(N), 2(L), and ground of the outdoor unit terminal block. This COOL mode button if not already set to cool mode.
operating parameter and the call is communicated from the The outdoor unit main board also controls the position of the indoor unit to the outdoor unit. EEV (Electronic Expansion Valve) to regulate the ow of refrigerant to the indoor unit evapora- The indoor unit louver will open using a stepper motor.
Tempe rature Sensors Four temperature sensors located in the outdoor unit provide information to the outdoor unit PCB for control of the system Upon exiting the defrost cycle, the following conditions will take place: The outdoor ambient temperature sensor provides the temperature of the air drawn into the condenser c The defrost temperature sensor provides the temperature sensed at the output of the condenser c...
Page 25
3. Compressor Ov O er-current Protection If the current draw of the compressor at start-up is greater than the values listed on the chart below for approximately 3 seconds, the compressor will stop. After 3 minutes the 52°F // / / compressor will restart.
System System M odel Name Outdoor 1U09EH2VHD 1U12EH2VHD 1U18EH2VHD Indoor AW09EH2VHD AW12EH2VHD AW18EH2VHD Rated Capacity Btu/hr 9,000 12,000 18,000 Capacity Range Btu/hr 3100~12000 3100~15000 8,500~21000 Rated Power Input W 1,385 Cooling SEER 16.0 15.0 13.0 M oisture Removal Pt./h 0.60 1.60...
Page 28
Check This First Outdoor Unit ................................29 Check This First Indoor Unit ................................30 Check This First - Indoor Unit Wiring Diagram Reference..................................31 Error Code (Indoor/Outdoor) F1/LED1: 2 Flash IPM Power Module Failure (IPM power module protection)................................32 Error Code: F1/LED1: 2 Flash................................33 Wiring Diagram Reference Error Code (Indoor/Outdoor) F2/LED1: 24 Flash Overcurrent of the Compressor................
Conditions Needed for Basic Operation Check This First Outoor Unit Models: 1U09EH2VHD Line voltage available at: • 1 (N) and 3 (C): 0-80 1U12EH2VHD 1. TERMINAL STRIP - 1(N) & 2 (L) 1U18EH2VHD • 2 (L) and 3 (C): 2. AC-L & AC-N at the PCB - CN2 & CN1 3.
Check This First Indoor Unit There is 230 VAC (+/- 10%) at terminal Models: AW09EH2VHD no more than a 2% deviation between AW12EH2VHD AW18EH2VHD There is a pulsing 0 to 80 power from OD unit or phase VAC between terminal strip...
(Indoor/Outdoor) Start F2/LED1: 24 Flash Overcurrent of the Compressor The set temperature is 5°F max. Complete the “Check This First” Flow Chart before continuing. Models: AW09EH2VHD AW12EH2VHD AW18EH2VHD 1U09EH2VHD 1U12EH2VHD 1U18EH2VHD Change set temperature Continue to monitor; the system is starting under an abnormal load ●...
Page 36
F3/LED1: 4 Flash Line voltage at AC-L & AC-N Communication Fault Between IPM and Outdoor PCB Complete the “Check This First” Flow Chart before continuing. Models: AW09EH2VHD Line voltage at AW12EH2VHD from building AC-L OUT & AC-N AW18EH2VHD OUT on the PCB...
Page 40
Room Temperature Sensor Failure E2/LED1: No Flash Indoor Coil Temperature Sensor Failure (See Reverse side.) Complete the “Check This First” Flow Chart before continuing. Models: AW09EH2VHD AW12EH2VHD Go to next step AW18EH2VHD to test the board as well before 1U09EH2VHD...
Page 42
Error Code (Indoor/Outdoor) F8/LED1: 9 Flash Start Outdoor DC Fan Motor Fault Complete the “Check This First” Flow Chart before continuing. Models: AW09EH2VHD AW12EH2VHD AW18EH2VHD 1U09EH2VHD 1U12EH2VHD 1U18EH2VHD ● Measure DC voltage at fan motor plug CN21 Re-apply power. Does the between Pin 1 (RED) and Pin 3 (BLACK).
Page 43
Error Code: F8/LED1: 9 Flash Wiring Diagram Reference OUTDOOR UNIT WIRING DIAGRAM 0011509127 COMPRESSOR ● ERROR CODES and Troubleshooting GE 43 ●...
Page 44
Error Code (Indoor/Outdoor) F11/LED1: 18 Flash Loss of Compressor Synchronization Complete the “Check This First” Flow Chart before continuing. Models: AW09EH2VHD AW12EH2VHD AW18EH2VHD Momentary loss A windings or grounding of building power 1U09EH2VHD 1U12EH2VHD power quality 1U18EH2VHD There is 50-200 VAC ●...
Page 46
Error Code (Indoor/Outdoor) F12/LED1: 1 Flash EEPROM Error After 10 minutes with the power Complete the “Check This First” Flow Chart before continuing. Models: AW09EH2VHD AW12EH2VHD ● AW18EH2VHD The 10-minute 1U09EH2VHD reboot has 1U12EH2VHD ● 1U18EH2VHD issue Wiring Diagram Reference...
Page 47
(Indoor/Outdoor) E5/LED1: 22 Flash Coil Frost Protection There is 5 VDC at CN6 on the Indoor Complete the “Check This First” Flow Chart before continuing. Models: AW09EH2VHD AW12EH2VHD The Coil and Ambient AW18EH2VHD within 3% of the value 1U09EH2VHD 1U12EH2VHD 1U18EH2VHD ●...
Page 49
(Indoor/Outdoor) E7/LED1: 15 Flash ID and OD Loss of Communication Complete the “Check This First” Flow Chart for both ID and OD units before continuing. Models: AW09EH2VHD AW12EH2VHD Is the Indoor PCB LED AW18EH2VHD 1U09EH2VHD 1U12EH2VHD 1U18EH2VHD Is the voltage from...
Page 52
Error Code Start (Indoor) Indoor Fan Motor Failure Complete the “Check This First” Flow Chart before continuing. Models: AW09EH2VHD AW12EH2VHD AW18EH2VHD the fan by hand. Does it power supply motor ● Measure DC voltage at fan Re-apply power. Does the motor plug CN9 between Pin 1 (RED) and Pin 4 (BLACK).
Page 54
Ductless Troubleshooting The resistance value of the coil should be 1.2 kilo ohms to Checking System Components 1.8 kilo ohms. Replace the valve c NOTE: Component resistance readings shown in this section are for reference only. Actual resistance values may based on model being tested.
Page 55
Disconnect the sensor from the PCB for this test. Failure to do so may provide inaccurate readings. Step 2 Determine the temperature of the sensor being tested. AGE 55 ERROR CODES and Troubleshooting Haier Ductless Technical Support Phone: 866.814.3633 (option 3) Email: ductlesshelp@geappliances.com Online: www.HaierDuctlessHelp.com ● Rev. 04-20...
Page 56
594.3 Ohm 594.5 Ohm Pink 594.3 Ohm Blue Step 3 Re-seat the plug on the PCB at the conclusion of the test. ERROR CODES and Troubleshooting PAGE 56 Haier Ductless Technical Support Phone: 866.814.3633 (option 3) Email: ductlesshelp@geappliances.com Online: www.HaierDuctlessHelp.com ● Rev. 04-20...
Outdoor Board Diagram OUTDOOR UNIT WIRING DIAGRAM 0011509127 COMPRESSOR Electrical Shock Hazard Riesgo de Descarga Eléctrica Risque de choc électrique Capacitor retains charge a er El capacitor re ene carga una vez Le condensateur conserve sa charge après la power is disconnected. Con rm desconectada la corriente.
Indoor Board Diagram INDOOR UNIT DIAGRAM 0011509128 DC FAN MOTOR Diagnostic CN38 B:Black R:Red RJ45 port W:White BL:Blue Y:Yellow BR:Brown CN56 HUMAN SENSOR Y/G:Yellow/Green CN35 WIFI Unit SW1 DIP Switch CN21 position CN51 ROOM CARD 1 2 3 4 CN34 off off off off WK-B...