Smoke Control Listed BACnet Fume
Hood Controller
Generic Controller I/O Layout. See Wiring Diagram for application specific details.
Control Applications
6740, 6741 and 6742
Product Description
These instructions explain how to field install or
replace the Fume Hood Controller (FHC).
This BACnet Fume Hood Controls a Fast-acting
Damper or Venturi Air Valve to maintain control of a
chemical fume hood with up to 2 sashes. It uses
fast-acting electronic actuators (shipped separately)
to control the exhaust control device.
Item No. 570-136. Rev. CA
Installation Instructions
The application cannot detect a
broken wire to the analog input
for the second sash.
An external sash aggregating
device should be used to
calculate the face area for all
fume hoods with more than one
sash.
This controller supports up to two Offboard AVS
signals. Offboard Air Module(s) (OAM) house AVS
transducers and send signals to the AVS input(s) on
the controller board. The controller can operate
stand-alone, with a field panel, or as part of a
network.
Document No. 570-136
October 26, 2016
WARNING
Page 1 of 11

Advertisement

Table of Contents
loading

Summary of Contents for Siemens BACnet

  • Page 1 Fume Hood Controller (FHC). calculate the face area for all fume hoods with more than one This BACnet Fume Hood Controls a Fast-acting sash. Damper or Venturi Air Valve to maintain control of a chemical fume hood with up to 2 sashes. It uses...
  • Page 2: Product Numbers

    Operator Display Panel II (ODP II) 575-820A Warning/Caution Notation Power Module AQM2200 WARNING Siemens fast-acting Lab Electronic GNP191.1U Actuator(s) – order and ship Personal injury/loss of life may separately) occur if you do not follow the procedures as specified.
  • Page 3: Required Tools And Equipment

    (FLN) trunk from the field panel. 5. Wire the FLN trunk to the controller. After all controllers are connected to the FLN, reconnect the FLN trunk to the field panel. Siemens Industry, Inc. Page 3 of 11...
  • Page 4 Smoke Control Systems Application and  Engineering Manual ( 125-1806) Smoke Control System Application Guide  125-1816) NFPA and UL Standards Relevant to Smoke  Control System Application Guide ( 125- 1817) Dimensions. Page 4 of 11 Siemens Industry, Inc.
  • Page 5: Wiring Diagrams

     and receiver. Connect the equipment into an outlet on a circuit  different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV  technician for help. Siemens Industry, Inc. Page 5 of 11...
  • Page 6 Doit utiliser une alimentation externe de 10 V. Ne pas alimenter un AI à partir d’un AO forcé à 10 volts. Wiring for AI4: Sash Sensor 2. Wiring for AI with a 4 to 20 mA Sensor. Page 6 of 11 Siemens Industry, Inc.
  • Page 7 10V control signal and ties AC neutral to DC common, an additional wire must connect the actuator AC neutral to the DC common of the PTEC/TEC AO being used to control the actuator. Siemens Industry, Inc. Page 7 of 11...
  • Page 8 Document No. 570-136 Installation Instructions October 26, 2016 Application 6740 Wiring Diagram. Page 8 of 11 Siemens Industry, Inc.
  • Page 9 Document No. 570-136 Installation Instructions October 26, 2016 Application 6741 Wiring Diagram. Siemens Industry, Inc. Page 9 of 11...
  • Page 10 Document No. 570-136 Installation Instructions October 26, 2016 Application 6742 Wiring Diagram. Page 10 of 11 Siemens Industry, Inc.
  • Page 11: Cyber Security Disclaimer

    Document No. 570-136 Installation Instructions October 26, 2016 Cyber security disclaimer Products, solutions and services from Siemens include security functions to ensure the secure operation of building automation and control, fire safety, security management, and physical security systems. The security...

This manual is also suitable for:

570-00701pka

Table of Contents