D/A Conversion
Data Format
Supplementary
Two output registers (both channels) should be specified to output when executing direct output.
6F8C0836
Analog Value (mA)
20
10
4
0
50 100 150 200 250
Digital Value
(a) 4-20mA range : A=0.064×D+4
(b) 1-5V range : A=0.016×D+1
(c) 0-10V range : A=0.04×D
F E D C B A 9 8 7 6 5 4 3 2 1 0
YW
*
*
*
*
*
*
*
D:Data bit (8 bits)
0-250 (H00-HFA)
*:No effect (No effect on D/A conversion)
2 words occupied
(Y2W)
Analog Value (V)
(a)
10
5
1
0
50 100 150 200 250
Digital Value
A = Analog Value
D = Digital Value
* D D D D D D D D
F
CH1
YWn
CH2
YWn+1
2.3 I/O Module Specification
(c)
(b)
0
93
2