Page 1
DPD01156B Siemens Industry, Inc. Flange Mount Kits for Frames FS4 to FS7 Mounting Instructions General Using the optional Flange Mounting Kit, you can mount your drive through the cabinet wall or similar surface so that the control unit of the drive remains inside the cabinet.
Page 2
Siemens Industry, Inc. DPD01156B Flange Mount - Frames FS4 - FS7 Figures 2. - 5. present the dimensions of the drives with the flange mount option. Figure 6. present the dimensions of the opening and the drive outline with the flange.
Page 6
Siemens Industry, Inc. DPD01156B flange outline cutout 11136.emf Figure 6. Flange mount cutout and drive outline dimensions for FS4 to FS7. Table 1. Flange mount cutout dimensions for FS4 to FS7 in mm (in). Frame 315 (12.40) 137 (5.39) 357 (14.05) 152 (5.98)
Page 7
DPD01156B Siemens Industry, Inc. Flange Mount Kit for Frame FS4 The kit consists of: 1. Top collar, (70CMR00281) 2. Bottom collar, (70CMR00280) 3. Side collars (2 pcs), (70CMR00282) 4. Internal fan, (70CPE00132, 70CPE00056) depends on the M4x16 control unit 5. Sealing plug (3 pcs), (70CMR00324)
Page 8
Siemens Industry, Inc. DPD01156B Remove the cover of the drive. Lift up the I/O protection plate. The location of the internal fan depends on the control unit. If you have the control unit presented in the upper picture, slide the internal fan into the opening with the label facing the cabling end of the drive.
Page 9
DPD01156B Siemens Industry, Inc. Connect the power wire to the power connector. The location of the power connector depends on the control unit. 11148.emf 11149.emf Remove the main fan. 9289.emf...
Page 10
Siemens Industry, Inc. DPD01156B Insert the three sealing plugs into position where indicated. Remount the main fan carefully, checking its position. 11151.emf Attach the side collars with three screws size 4x12. The tightening torque for the screws is 2 Nm (17.70 lbf-in).
Page 11
DPD01156B Siemens Industry, Inc. Mount the top collar with the four screws size 4x16; the tightening torque is 2 Nm (17.70 lbf-in). Mount the bottom collar with the four screws size 4x16, (2 Nm (17.70 lbf-in) torque) and the two screws size 3.5x10;...
Page 12
Siemens Industry, Inc. DPD01156B Flange Mount Kit for Frame FS5 The kit consists of: 1. Top collar, (70CMR00176) 2. Bottom collar, (70CMR00175) 3. Side collars (2 pcs), (70CMR00090) 4. Internal fan, (70CPE00056) M4x16 5. Sealing plugs (4 pcs), (70CMR00324) Additionally: M4x12 •...
Page 13
DPD01156B Siemens Industry, Inc. Remove the cover of the drive. The location of the internal fan depends on the control unit. If you have the control unit presented in the upper picture, install the internal fan with the label facing upwards.
Page 14
Siemens Industry, Inc. DPD01156B Then insert the power connector of the internal fan into the power terminal. 11156.emf The location of the power connector depends on the control unit. Remount the drive cover. 11149.emf Remove the main fan. 9289.emf...
Page 15
DPD01156B Siemens Industry, Inc. Insert the sealing plugs. Remount the main fan. 11145.emf Attach the side collars with the four screws size 4x12; the tightening torque for the screws is 2 Nm (17.70 lbf-in). 9269.emf...
Page 16
Siemens Industry, Inc. DPD01156B Then mount the top collar with the four screws size 4x16; the tightening torque is 2 Nm (17.70 lbf-in). Mount the bottom collar with the four screws size 4x16, (2 Nm (17.70 lbf-in torque )) and the two screws size 3.5x10;...
Page 17
DPD01156B Siemens Industry, Inc. Flange Mount Kit for Frame FS6 The kit consists of: 1. Top collar, (70CMR00174) 2. Bottom collar, (70CMR00173) 3. Side collars (2 pcs), (70CMR00145) 4. Internal fan, (70CPE00056) M4x16 5. Sealing plugs (6 pcs), (70CMR00324) 6. Fan grille 50 mm, (70CTC1102509) 7.
Page 18
Siemens Industry, Inc. DPD01156B 11137.emf 11137.emf Install the internal fan to the fan grille so that the label is facing upwards. 11137.emf 11138.emf...
Page 19
DPD01156B Siemens Industry, Inc. 11139.emf Install the internal fan and the fan grille assembly to frame. NOTE: The direction of the wire depends on the control unit. Insert the power connector of the internal fan to the power terminal. NOTE: The location of the power connector depends on the control unit.
Page 20
Siemens Industry, Inc. DPD01156B Remove the screw and detach the main fan. 9299.emf Insert the sealing plugs (6 pcs). Remount the main fan. 9300.emf Attach the side collar with the six screws size 4x12; the tightening torque for the screws is 2 Nm (17.70 lbf-in).
Page 21
DPD01156B Siemens Industry, Inc. Mount the top collar with the four screws size 4x16; the tightening torque is 2 Nm (17.70 lbf-in). 11154.emf Mount the bottom collar with the four screws size 4x16, (2 Nm (17.70 lbf-in) torque) and the two screws size 3.5x10;...
Page 22
Siemens Industry, Inc. DPD01156B In case the back plate bends more than 1.5 mm (.05 in), the use of the additional snaps is required to guarantee sealing. The snaps can be battered down from the bottom cover (4 mm (.15 in) screws to be used with the snaps).
Page 23
DPD01156B Siemens Industry, Inc. Flange Mount Kit for Frame FS7 The kit consists of: 1. Top collar, (70CMC00343) 2. Bottom collar, (70CMC00344) 3. Side collars (2 pcs), (70CMC00345) 4. Bushing rubber (1 pcs), (MC00016) M5 DIN315 5. Fan grille, (70CTC1102699) 6.
Page 24
Siemens Industry, Inc. DPD01156B Insert the bushing rubber into position. Install the internal fan so that the wire leaves to right direction. The direction depends on the control unit. See the step 4 below.
Page 25
DPD01156B Siemens Industry, Inc. 11161.emf To power the fan, connect it to the power terminal next to the keypad. The location of the power connector depends on the control unit. 11162.emf Remount the drive cover.
Page 26
Siemens Industry, Inc. DPD01156B Remove the screws as shown in the picture from both sides of the drive. Use the torx head provided with the kit. 9275.emf Remove the screws as shown in the 9276.emf picture from the top and bottom of the drive.
Page 27