hit counter script

Engineering Of Large Plants - Siemens Synco 700 Series Basic Documentation

Communication via the knx bus
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Engineering with ACS
Addressing
Note
Send subnetwork
address
Note
90/120
Building Technologies
HVAC Products
8.3

Engineering of large plants

The ACS7... software is recommended for the engineering of large plants, because
it can be used to set all the necessary addresses and configuration values.
1. Address the area/line couplers (see section 5.9) and IP routers (see section
5.10).
2. Set the device addresses for the bus devices (see section 5.2 ff).
3. Additional settings for the IP network in the IP router via ACS Service
(see further below).
If the area/line couplers and IP routers are addressed before the bus devices, them
the bus devices will be ready to receive the "area" and "line" components of the
address. See "Transmitting the subnet address" below.
The following settings are possible in conjunction with transmission of the
subnetwork address (SNA):
• If inconsistent
• Daily
• After change
• On request
(default)
For transmission of the subnet address (SNA) all settings should be enabled (i.e.
ensure that all checkboxes are selected).
Basic documentation: Communication via the KNX bus
Large plants
CE1P3127en
30.08.2007

Advertisement

Table of Contents
loading

Table of Contents