Page 1
Operating voltage AC 24 V, 10 Nm ● For air-handling units (AHU) and other ventilation applications ● Operating voltage AC 24 V ● 5 and 10 Nm nominal torque ● Modbus RTU communication ● UL listed A6V10881141_en--_c Siemens 2019-04-25 Smart Infrastructure...
Page 2
Installation Instruction Mounting / installation instruction for rotary M4634 actuators 5 / 10 Nm Related documents such as environmental declarations, CE declarations, etc., can be downloaded at the following Internet address: http://siemens.com/bt/download 2 / 12 Siemens A6V10881141_en--_c Smart Infrastructure 2019-04-25...
Page 3
3. If the button is pressed within these 3s, the reset is cancelled. 4. After those 3s à LED shines (reset), then green (start-up). Related documents such as environmental declarations, CE declarations, etc., can be downloaded at the following Internet address: http://siemens.com/bt/download 3 / 12 A6V10881141_en--_c Siemens 2019-04-25 Smart Infrastructure...
Page 4
1. Enter addressing mode 2. Set 1-digits: Press button 5-times à LED flashes green per button press 3. Store address: press button until LED shines à address is stored and displayed 1x for confirmation 4 / 12 Siemens A6V10881141_en--_c Smart Infrastructure 2019-04-25...
0 = Ready / 1 = Load / 2 = Discard Status See below Device information 1281 Factory Index 1282-83 Factory Date Cf. product documentation CE1Z4634 1284-85 Factory SeqNo 1409-16 TypeASN [Char_16..1] The documents can be downloaded from http://siemens.com/bt/download 5 / 12 A6V10881141_en--_c Siemens 2019-04-25 Smart Infrastructure...
Page 6
Cf. mounting instr. A6V10409478 Not to be used for fixation of the actuator, use anti-rotation-bracket instead. Related documents such as environmental declarations, CE declarations, etc., can be downloaded at the following internet address: http://siemens.com/bt/download 6 / 12 Siemens A6V10881141_en--_c Smart Infrastructure...
Page 7
New value (ex.) MacAddress Baudrate 0 = auto 1 = 9600 Transmission Mode 0 = 1-8-E-1 3 = 1-8-N-2 Termination 0 = Off 0 = Off BusConfigCmd 0 = Ready 1 = Load 7 / 12 A6V10881141_en--_c Siemens 2019-04-25 Smart Infrastructure...
Page 8
Comply with all local and currently applicable laws and regulations. Warranty Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations". Siemens rejects any and all warranties in the event that third-party products are used.
120 Ω electronically switchable Termination Default: Off Degree of protection Degree of protection Degree of protection acc. to EN 60529 IP54 (see mounting instruction) Safety class Safety class acc. to EN 60730 9 / 12 A6V10881141_en--_c Siemens 2019-04-25 Smart Infrastructure...
Page 10
Suitable drive shafts Round shaft (with centering element) 8...16 mm (8...10 mm) Square shaft 6...12.8 mm Min. drive shaft length 30 mm Max. shaft hardness <300 HV The documents can be downloaded from http://siemens.com/bt/download 10 / 12 Siemens A6V10881141_en--_c Smart Infrastructure 2019-04-25...
Page 11
The operating voltage at terminals G and G0 must comply with the requirements under SELV or PELV. Safety transformers with twofold insulation as per EN 61558 required; they must be designed to be on 100 % of the time. Dimensions G..B111.1E/.. Measurements in mm 11 / 12 A6V10881141_en--_c Siemens 2019-04-25 Smart Infrastructure...