Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
This document describes the SUN2000L-(2KTL-5KTL) in terms of its installation, electrical connections, commissioning, maintenance, and troubleshooting. SUN2000L-(2KTL-5KTL) is abbreviated as SUN2000L. Before installing and operating the SUN2000L, ensure that you are familiar with the features, functions, and safety precautions provided in this document.
4.4 Installing the Mounting Bracket ..........................24 4.4.1 Wall-Mounted Installation ............................25 4.4.2 Support-mounted Installation ..........................27 4.5 Installing the SUN2000L ............................29 4.6 Installing the WLAN Antenna ............................ 33 5 Electrical Connections ........................ 34 5.1 Preparing Cables ................................. 34 5.2 Installing the PE Cable ...............................
Page 6
6.4 Powering Off the System ............................61 7 System Maintenance........................62 7.1 Routine Maintenance ..............................62 7.2 Troubleshooting ................................63 8 Handling the SUN2000L ......................70 8.1 Removing the SUN2000L ............................70 8.2 Packing the SUN2000L .............................. 70 8.3 Disposing of the SUN2000L............................70 9 Technical Specifications ......................
The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this document do not cover all the safety instructions. They are only supplements to the safety instructions. Huawei will not be liable for any consequence caused by the violation of general safety requirements or design, production, and usage safety standards.
Do not touch the energized equipment, as the enclosure is hot. 1.2 Personnel Requirements Personnel who plan to install or maintain Huawei equipment must receive thorough training, understand all necessary safety precautions, and be able to correctly perform all operations.
Product Overview 2.1 Product Introduction Function The SUN2000L is a single-phase grid-tied PV string inverter that converts the DC power generated by PV strings into AC power and feeds the electricity into the power grid. Models This document involves the following product models: ...
Surge protection is supported on both the DC and AC sides. The SUN2000L has a reserved battery port to connect to batteries, which are used to store the surplus power produced by PV strings and not required by residential loads. The power stored in batteries can be exported to the power grid based on the load condition to meet peak and valley power consumption requirements and maximize the benefits.
Page 24
Operating In Operating mode: The SUN2000L converts DC power from PV strings into AC power and feeds the energy to the power grid. The SUN2000L tracks the maximum power point to maximize the PV string output.
Keep the storage temperature at –40° C to +70° C and the humidity at 5%–95% RH. The SUN2000L should be stored in a clean and dry place and be protected from dust and water vapor corrosion. A maximum of 10 SUN2000Ls can be stacked. To avoid personal injury or device damage, stack SUN2000Ls with caution to prevent them from falling over.
Before unpacking the SUN2000L, check the outer packing materials for damage, such as holes and cracks, and check the SUN2000L model. If any damage is found or the SUN2000L model is not what you requested, do not unpack the product and contact your supplier as soon as possible.
The SUN2000L is protected to IP65 and can be installed indoors or outdoors. Do not install the SUN2000L in a place where a person can easily touch it because its enclosure and heat sinks are extremely hot during operation.
Page 29
The SUN2000L must be installed in a well-ventilated environment to ensure good heat dissipation. When installed under direct sunlight, the power of the SUN2000L may be derated due to additional temperature rise. Install the SUN2000L in a sheltered place or install an awning over the SUN2000L.
SUN2000L-(2KTL-5KTL) User Manual 4 System Installation Installation Clearance Requirements Reserve enough clearance around the SUN2000L to ensure sufficient space for installation and heat dissipation. Figure 4-2 Installation clearance requirements 4.4 Installing the Mounting Bracket Fixing holes can be used in three combinations. Select a hole combination based on site requirements.
Page 32
4 System Installation Avoid drilling holes in the utility pipes and/or cables attached to back of the wall. If the length or number of M8x80 expansion bolts supplied with the SUN2000L is not enough, prepare M8 stainless steel expansion anchor bolts.
Page 36
Step 2 Install the SUN2000L on the mounting bracket and align the SUN2000L enclosure with the mounting bracket. If the bottom of the mounting plate does not snap into place, push the SUN2000L from the front until the bottom of the mounting plate snaps into the mounting bracket.
Page 37
SUN2000L-(2KTL-5KTL) User Manual 4 System Installation Figure 4-13 Mounting a SUN2000L Step 3 Tighten screw assemblies. Fixing holes can be used in three combinations. Select a hole combination based on site requirements. Combination A is preferred. Figure 4-14 Fixing holes...
Page 38
Figure 4-15 Tightening screw assemblies Step 4 (Optional) Install an anti-theft lock. The function of an anti-theft lock is to secure the SUN2000L to the mounting bracket and protect it from being stolen. Use an anti-theft lock suitable for the lock hole diameter (Ф8 mm). The anti-theft lock is ...
Page 41
SUN2000L-(2KTL-5KTL) User Manual 5 Electrical Connections Figure 5-2 SUN2000L cable connections (dashed boxes indicate optional components) Table 5-1 Component description Component Description Source A PV string is composed Purchased by the PV string of the PV modules customer connected in series and works with an optimizer.
Page 43
5 Electrical Connections The SUN2000L is embedded with a residual current monitoring unit (RCMU). Only a single-phase circuit breaker or a similar AC load breaking device is required to function as the external AC switch (shown by G in...
5.3 Installing the AC Output Power Cable Prerequisites An AC switch must be installed on the AC side of the SUN2000L to ensure that the SUN2000L can be safely disconnected from the power grid. Do not connect any load between the SUN2000L and the AC switch.
Page 47
User Manual 5 Electrical Connections According to IEC62109, to ensure the safe operation of the SUN2000L in the case of PE cable damage or disconnection, connect the SUN2000L PE cable according to the requirements described 5.2 Installing the PE Cable and ensure that the SUN2000L PE cable meets at least one of the following requirements before disabling the grounding detection function.
Before connecting the DC input power cable, ensure that the DC voltage is within the safe range (lower than 60 V DC) and that the DC switch on the SUN2000L is OFF. Failing to do so may result in electric shocks.
Page 51
During the installation of PV strings and SUN2000L, the positive or negative terminals of PV strings may be grounded if power cables are not properly installed or routed. In this case, an AC or DC short circuit may occur and damage the SUN2000L. This damage is not covered under any warranty.
Page 54
Figure 5-14 Observing core wires through the hole on the terminal Step 2 Ensure that the DC input voltage of each PV string is within the specified range of the SUN2000L using a multimeter and check that the polarities of DC input power cables are correct.
Page 55
Follow-up Procedure Before removing the positive and negative connectors, ensure that the DC switch is OFF. To remove the positive and negative connectors from the SUN2000L, insert an open-end wrench into the notch and press the wrench with an appropriate force.
If no battery connects to the SUN2000L, do not remove the watertight cap from the battery terminal. Otherwise, the SUN2000L will not comply with its Ingress Protection Rating. If a battery connects to the SUN2000L, set aside the watertight cap. Reinstall the watertight cap immediately after removing the connector.
Page 57
In this case, an AC or DC short circuit may occur and damage the SUN2000L. This damage is not covered under any warranty or service agreement.
Page 60
Residual Current Sensor alarm. The ALARM port reserves an RS485/12 V signal port. The alarm beacon should be installed within 2 meters away from the SUN2000L. The shield layer of the device signal cable connected to the ALARM port and the COM port is also advised to be grounded.
Grounding securely, and reliably. Switch status The DC switch and all the switches connecting to the SUN2000L are OFF. The AC output power cable, DC input power Cable connections cable, battery cable, and signal cable are connected correctly, securely, and reliably.
AC voltage on the power grid side of the AC switch is within the specified range. If the DC is on and the AC is off, the SUN2000L reports a Grid Loss alarm. The SUN2000L starts normally only after the fault is rectified.
Step 3 Turn off the DC switch at the bottom of the SUN2000L. Step 4 Turn off the DC switch between the PV string and the SUN2000L if there is any. Step 5 If a battery connects to the battery port, turn off the battery switch.
System Maintenance 7.1 Routine Maintenance To ensure that the SUN2000L can operate properly in the long term, you are advised to perform routine maintenance on it as described in this chapter. Before cleaning the system, connecting cables, and maintaining the grounding reliability, power off the system (see 6.4 Powering Off the System...
Major: The SUN2000L enters Shutdown mode and disconnects from the power grid to stop generating power after a fault occurs. Minor: Some components are faulty but the SUN2000L can still connect to the power grid and generate power. ...
Page 70
Check whether the PV string is Reversed connected. reversely connected to the SUN2000L. If so, wait until the solar irradiance declines at night and the PV string current reduces to below 0.5 A. Then, turn off the DC switch and correct the PV string polarity.
Page 72
2. If the alarm occurs frequently, check whether the grid frequency is within the acceptable range. If not, contact the local power operator. 1. The SUN2000L monitors its 2039 Output Major Cause ID = 1 external working conditions in Overcurrent The grid voltage drops real time.
Page 73
PE. poor insulation points. The PV string is installed 2. Check that the SUN2000L PE in a moist environment cable is correctly connected. for a long time. 3. If you confirm that the...
Page 75
2. Replace the peripheral, and then start a self-check to check that the port functions properly. Contact your supplier or Huawei technical support if all failure analysis procedures listed above are completed and the fault still exists. Issue 06 (2020-03-19)
Step 5 Remove the mounting bracket. ----End 8.2 Packing the SUN2000L If the original packaging is available, put the SUN2000L inside it and then seal it using adhesive tape. If the original packaging is not available, put the SUN2000L inside a suitable cardboard box and seal it properly.
L-2KTL L-3KTL L-3.68KT L-4KTL L-4.6KTL L-5KTL Maximum 600 V (No battery connects to the SUN2000L.) input 495 V (An LG-RESU battery connects to the SUN2000L.) voltage Maximum 11 A input current (per MPPT) Maximum 15 A short-circu it current...
Page 78
PV array Operating 90–500 V (No battery connects to the SUN2000L.) voltage 90–495 V (An LG-RESU battery connects to the SUN2000L.) range Start 120–600 V (No battery connects to the SUN2000L.) voltage 120–495 V (An LG-RESU battery connects to the SUN2000L.)
Page 79
(rated power) Note a: The maximum output power of the SUN2000L-5KTL is 4990 W if the Australian AS4777 grid code is selected. Note b: The maximum apparent power of the SUN2000L-4.6KTL is 4600 VA if the Germany VDE-AR-N 4105 grid code is selected. The maximum apparent power of the SUN2000L-4.6KTL and SUN2000L-5KTL is 4990 VA if the Australian AS4777 grid...