Honeywell Gent Vigilon Compact Operating Instructions Manual

Honeywell Gent Vigilon Compact Operating Instructions Manual

Voice alarm based fire detection and alarm system
Table of Contents

Advertisement

4188-1004 issue 1_10/10_Vigilon Compact VA Ops inst.
Vigilon Compact Voice Alarm based
1
2
Zones
17
18
Fault
Power Fault
Panel healthy
System Fault
Delay
Test
Disablement
MIC
EN54 Part 2, 4 & 16
Vigilo n
by Honeywell
COMPACT VOICE
Operating Instructions
Fire detection and alarm system
3
4
5
6
7
8
9
10
11
12
13
14
15
16
19
20
21
22
23
24
25
26
27
28
29
30
30
32
Fire
Verify
15:45
Sounder
Vigilon Compact Voice Alarm System
CB253
GENT 2010
Designed to EN54 Pts 2, 4 & 16
CB254
Power
Previous
Next
Voice Alarm Zones
1
2
3
4
5
6
7
8
9
10
All Zones
Clear Zones
Speak Now
VA Activated
Auxiliary messages
Emergency messages
1
TEST START
ALERT
1
TEST END
EVACUATE
2
2
BOMB
STAND DOWN
3
3
by Honeywell

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Gent Vigilon Compact

  • Page 1 Honeywell Operating Instructions Vigilon Compact Voice Alarm based Fire detection and alarm system Zones Fault Fire Power Fault Verify Panel healthy 15:45 System Fault Sounder Vigilon Compact Voice Alarm System Delay CB253 GENT 2010 Designed to EN54 Pts 2, 4 & 16...
  • Page 2: Table Of Contents

    Operating instructions micro Distributed Amplifier Unit Contents volume control - - - - - - - - - - - - - 25 Menu controls - - - - - - - - - - - - - - 26 User responsibility - - - - - - - - - - - - 4 How to carry out a display test - - - - - - 27 Daily - - - - - - - - - - - - - - - - - - 4...
  • Page 3 Vigilon COMPACT VOICE ALARM Symbol Keys Preface This third issue of the operating instructions is for the Vigilon Compact combined Fire and Voice alarm system. What you will see. Associated documents ¨ Vigilon Compact Voice Alarm What you will hear. - Installation instructions ¨...
  • Page 4: User Responsibility

    Operating instructions Daily User responsibility BS 5839:Part 1, states that the system should be Your fire alarm system should have been designed, inspected daily to ensure: installed and commissioned to your site specific ¨ That a normal indication is given at the control requirements and in accordance with the requirements and indicating equipment.
  • Page 5: Quarterly

    Vigilon COMPACT VOICE ALARM Quarterly Background music At quarterly intervals the system should be inspected Before playing background music via the Vigilon and any work necessary should be performed by a Compact Voice Alarm system it is important to acquire trained maintenance engineer.
  • Page 6: System Control And Indicating Equipment

    Mains Powered Interface Units via their speaker circuits provide alert and EN54 Part 2, 4 & 16 Vigilon by Honeywell COMPACT VOICE evacuation voice alarm to warn occupants in the event of a fire. The Audio loop is also routed through the protected premises and connects to each micro Distributed Amplifier Unit and Mains Powered Distributed Amplifier Unit on the corresponding analogue loop circuit.
  • Page 7: Description Of Controls And Indications

    EVACUATE Auxiliary messages Emergency messages TEST START ALERT STAND DOWN BOMB EN54 Part 2 & 4:1997 Vigilon by Honeywell TEST END EVACUATE COMPACT VOICE STAND DOWN BOMB Key lock for Access level 1 the outer door Controls to scroll events...
  • Page 8 Operating instructions Indicators and controls Descriptions Display The Display provides messages of the system status / events by means of 8 lines by 40 characters per line display. Hidden-until-lit fire zone indicators. When the "Zones" text and Zones (red) number(s) are illuminated it indicates that a FIRE has been detected in the specified zone(s) of the local system.
  • Page 9 Vigilon COMPACT VOICE ALARM Indicators and controls Descriptions Sound Alarms Pressing the Sound Alarms button will activate evacuation message and sound evacuate alarms. This button is only pressed in an emergency or at other agreed times, for example when conducting a system test or practice evacuation.
  • Page 10 Operating instructions VA Indications Voice Alarm Zones All Zones Clear Zones VA Activated Speak Now Auxiliary messages Emergency messages TEST START ALERT TEST END EVACUATE BOMB STAND DOWN Pressing one or more of the 10 buttons selects the local Voice Alarm Zone(s) of the local system to which emergency or auxiliary messages, or emergency microphone is to be announced.
  • Page 11 Vigilon COMPACT VOICE ALARM When 'Speak Now' LED is illuminated it indicates the local system Speak Now is ready to allow live speech announcement to selected local Voice (green) Alarm Zones via the Emergency microphone. The indicator is lit following selection of Voice Alarm Zones and on pressing the Press to Talk (PTT) button on the Emergency microphone.
  • Page 12: Normal Condition

    VA Activated Auxiliary messages Emergency messages TEST START ALERT TEST END EVACUATE STAND DOWN BOMB EN54 Part 2 & 4:1997 Vigilon by Honeywell COMPACT VOICE Key: Flashing Fault Fault Fire Panel healthy 15:45 Verify Power Fault Vigilon Compact Voice Alarm System...
  • Page 13: Weekly Test

    Vigilon COMPACT VOICE ALARM Weekly test Every week during normal working hours the fire detection and voice alarm system should be tested. It is important to inform the alarm receiving centre of the fire test. " It is important to inform occupants in the building before carrying out a test. A 'Start test' and an 'End test' announcements can be made from the panel by activating Auxiliary message 1 (Test Start) and Auxiliary message 2 (End Test), see page 19.
  • Page 14: How To Make An Announcement Using The Emergency Microphone

    Operating instructions How to make an announcement using the Emergency Microphone Live emergency announcements using the Emergency microphone can be made to guide occupants away from fire. " Announcements made using the Emergency Microphone is broadcast to the local system ONLY and is not across the entire network. Key: Flashing Open the panel door.
  • Page 15: How To Announce Emergency Messages

    Vigilon COMPACT VOICE ALARM How to announce emergency messages If an emergency situation should occur, you can announce 'fire alert', 'fire evacuate' Evac. and 'bomb alert' messages to selected local voice alarm zones. Alert Bomb Open the panel door. Flashing Select the Voice Alarm Zones in which the...
  • Page 16: How To Manually Raise A Fire Alarm

    Operating instructions How to manually raise a fire alarm If you see a fire in the protected premises and want to raise a fire alarm to warn occupants in the building, you can do this manually by: ¨ Going to the nearest manual call point that is located away from the fire hazard. ¨...
  • Page 17: Automatic Detection Of Fire

    Vigilon COMPACT VOICE ALARM Automatic detection of FIRE A fire in your protected premises is automatically sensed at any one of the fire detection device installed in the building, such as a sensor or a fire input from an interface. The control panel actions the voice alarm in the system and at the same time give the details of the fire event across the network.
  • Page 18: To Reset System

    Operating instructions Reset To return the system to To reset system normal condition clear any residual smoke or heat from Press: devices and reset any fire Display reads 'System being inputs. Reset - please wait..' Ensure the fire system is checked by your servicing organisation, if there has been fire damage in the...
  • Page 19: How To Announce An Auxiliary Message

    Vigilon COMPACT VOICE ALARM How to announce an auxiliary message There are three auxiliary messages at the control panel and these are factory set to Auxiliary announce a 'start of fire alarm test', 'end of fire alarm test' and a 'stand down' to inform Message that the emergency is over.
  • Page 20: Fault Conditions

    Operating instructions Fault conditions A fault in the local system such as a failure of the mains power to the panel or removal of any monitoring device will cause a Fault condition at the control panel. The control panel will provide details of the fault event, this event indication is repeated at all networked control panel, repeat indicators and mimic panels in the system.
  • Page 21: Typical Fault Messages

    Vigilon COMPACT VOICE ALARM Typical fault messages The following table shows some of the more typical fault messages that may occur along with their meaning and possible rectification action. Flashing Message Indication Meaning Action The mains supply to the control Restore the mains supply to Mains failed Fault...
  • Page 22 Operating instructions There is a short circuit on loop n Identify the device where a Wiring Fault (Card n) wiring. cable fault has occurred and changed short rectify the fault. circuit at card n There is an open or short circuit Locate and rectify the wiring Interface Fault...
  • Page 23: Disablement Condition

    Vigilon COMPACT VOICE ALARM Disablement condition A disablement condition is the manual or automatic disablement of a part of the local fire detection and voice alarm system. An automatic disablement may be pre-configured for your premises to disable smoke sensors during the normal working hours if there is a likelihood of smoke being present.
  • Page 24: Typical Disablement Messages

    Operating instructions Typical disablement messages The following table shows some typical disablement messages that may appear at the panel. Message Indication Meaning Action The central background music The music may have been Disablement has been disabled. disabled manually, if required re-enable the background music.
  • Page 25: How To Adjust The Background Music Volume

    Vigilon COMPACT VOICE ALARM How to adjust the background music volume In certain types of applications, such as in a hospital, there may be a requirement to set the volume level of the background music at a Distributed Amplifier Units (DAU) using a remote control. This volume adjustment will apply to the speaker circuits associated with the respective DAU.
  • Page 26: Menu Controls

    Operating instructions Menu controls Key: Panel beeps Flashing on each button press Fault Fault Fire 15:45 Verify Power Fault System Fault Sounder Vigilon Compact Voice Alarm System GENT 2010 Designed to EN54 pts 2, 4 & 16 Delay CB253 Test CB254 [Control] [ Set Up ] [ Info ]...
  • Page 27: How To Carry Out A Display Test

    Vigilon COMPACT VOICE ALARM How to carry out a display test How to change your PIN code " You can test the message display and the indicators on the control panel. The terms Password, PIN, Press the MENU ON/OFF key and then the F4 Usercode and Access code are used key to select [Test/Eng].
  • Page 28: How To View The Historic Events

    Operating instructions How to view the historic events Cards inside the control panel There can be up to 255 events stored in the Historic In the following text CARD n notation is a physical slot log of the panel. To view the Historic events log. on the PCB inside the panel, while 'Card n' notation is a menu reference used to describe a function.
  • Page 29: How To Save Changes To Memory

    Vigilon COMPACT VOICE ALARM How to save changes to memory How to view active events If you make any changes to Labels or Password then An active event is an event that is still present and has you must save these to the NVM (Non Volatile not cleared.
  • Page 30: How To Set The System Clock

    Operating instructions How to set the system clock How to use the external printer & These functions are only applicable if your panel has a external printer connected. An incorrect setting of the To Switch On the Printer system clock will affect any time Press the MENU ON/OFF key.
  • Page 31: How To Enable/Disable A Zone

    Vigilon COMPACT VOICE ALARM How to enable/disable a zone How to enable/disable a device " A zone is a subdivision of your premises protected by the fire alarm system. There can be up to 128 zones It is only possible to disable a configured in a system.
  • Page 32: How To Enable/Disable An Io Line

    Operating instructions How to enable/disable an IO line How to enable/disable public address An IO line is an input or output line of an interface. There can be up to four input/output lines on an The public address (PA) microphone connected to the interface unit, which can be disabled or enabled.
  • Page 33: How To Enable/Disable Background Music

    Vigilon COMPACT VOICE ALARM How to enable/disable How to enable/disable aux relay background music The control panel has two auxiliary relays that provide voltage free contacts to control external equipment in The optional entertainment system connected to the the event of a fire or fault on the system. The control panel will output background music to operation of the relays can be disabled or enabled.
  • Page 34: Viewing Labels

    Operating instructions Viewing labels How to view I/O line labels The identification label given to each system device An interface unit can have up to four input/output (IO) can be checked, devices such as fire sensors, alarm lines. Each line can be given a label that appears on sounders, manual call points, interface units - the display during an event.
  • Page 35: How To View Zone Labels

    Vigilon COMPACT VOICE ALARM How to view zone labels How to view the local panel label A zone is a subdivision of a building used for fire When there is a network of control panels connected detection. To view a zone label you will need to know together in a system then each panel is usually given the zone number and the loop on which it resides.
  • Page 36: To View Or Print A Loop Map

    Operating instructions To view or print a loop map Editing labels " A loop map provides information on devices that are connected to a loop on the system. Changes to labels must be Press the MENU ON/OFF button. backed up to the Memory, see the section Press the F3 button to select [Info].
  • Page 37: How To Edit Input/Output Line Label

    Vigilon COMPACT VOICE ALARM How to edit Input/output line label How to edit a zone label Each input / output (IO) line of an interface unit can be Each zone can be given a label and an entered label given a label and a previously entered label can be can be modified.
  • Page 38: How To Edit A Local Panel Label

    Operating instructions How to edit a local panel label How to edit the custom label The local panel label is normally given to the control A custom label or message is displayed beneath the panel to identify its location in a network of control Designed to EN54 Pt s 2 , 4 &...
  • Page 39: Maintenance

    Vigilon COMPACT VOICE ALARM Maintenance Replacing the glass on a Manual Call Point Disengage the front cover from the call point assembly using the end of the test key. Insert the key into the slots 'E' and from the bottom edge lift out the cover.
  • Page 40: Replacing Broken Glass On An Old Manual Call Point

    Operating instructions Replacing broken glass on an old Battery replacement Manual call point It is recommended that batteries are replaced at 4 yearly intervals from the date the Vigilon compact & system is first commissioned. Take appropriate " precautions when clearing broken Any servicing work on the glass to prevent injury.
  • Page 41: Repair Function

    Vigilon COMPACT VOICE ALARM Repair function Any wiring fault on the system must be rectified by an engineer from the servicing organisation, see log book for contact details. A wiring fault will require correction to the wiring followed by running a repair command at the main panel.
  • Page 42 Operating instructions Notes...
  • Page 43 Vigilon COMPACT VOICE ALARM Notes...
  • Page 44 Do not dispose of with your normal household waste. Do not burn. Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes.