Page 1
SIMATIC NET S7 - CPs for PROFIBUS Manual Part B4 CP 443-5 Extended for PROFIBUS 6GK7 443-5DX04-0XE0 Version 1 or higher (Firmware Version V6.1 or higher) for SIMATIC S7-400 / S7-400H Status and fault LEDs Mode selector PROFIBUS interface (9-pin D - sub female...
Page 2
Compatibility with the Previous Version Note Make sure that you read the information regarding extended functionality and restrictions in Chapter 6 of this manual! CP 443-5 Extended for PROFIBUS / Manual Part B4 B4-2 Release 6/2005 C79000-G8976-C162-06...
- DP master (class 1) (redundant operation in fault-tolerant system also possible) - Direct data exchange (DP slave to DP slave) As a DP master, the CP 443-5 Extended is capable of enabling direct data exchange for “its” DP slaves. - SYNC /FREEZE (please refer to Tables 2-1 and 2-2) The outputs or inputs can be synchronized from the within the user program using system function SFC11.
Page 5
2. - Identifying the bus topology in a DP master system As a DP master, the CP 443-5 Extended supports the measurement of the PROFIBUS bus topology in a DP master system using a diagnostic repeater (DP slave).
Page 6
SIMATIC PDM (Process Device Manager; see also SIMATIC PDM documentation...). The services of the CP 443-5 Extended module listed above can be used at the same time. Blocks for S7 communication (see also STEP 7 online help or “System Software for S7-300/400 System and Standard Functions”...
Page 7
General Part of this manual. Replacing Modules without a Programming Device When installing the CP 443-5 Extended, the configuration data of the CP are always stored in the CPU. Therefore replacing modules is possible without having to download the configuration data from the PG.
2 Requirements for Use 2 Requirements for Use The CP 443-5 Extended V 6.1 described here is supported by all CPU operating systems in the versions listed in Tables 2-1 and 2-2. Use with the Current CPU Types Limits and Conditions...
Page 9
As of V4. 64 / 64 As of V4.1 64 / 64 CPU 416F -2 ..416-2FK04 -0AB0 As of V4. 64 / 64 As of V4.1 64 / 64 CP 443-5 Extended for PROFIBUS / Manual Part B4 B4-9 Release 6/2005 C79000-G8976-C162-06...
Page 10
+ => The characteristic is supported / the listed mode is possible => The characteristic is not supported / the listed mode is not possible 1) All CPUs are CiR capable (the H -CPUs HCiR). CP 443-5 Extended for PROFIBUS / Manual Part B4 B4-10 Release 6/2005...
32 / 32 Legend: + => The characteristic is supported / the listed mode is possible => The characteristic is not supported / the listed mode is not possible CP 443-5 Extended for PROFIBUS / Manual Part B4 B4-11 Release 6/2005 C79000-G8976-C162-06...
Page 12
+ => The characteristic is supported / the listed mode is possible => The characteristic is not supported / the listed mode is not possible 1) All CPUs are CiR capable (the H -CPUs HCiR). CP 443-5 Extended for PROFIBUS / Manual Part B4 B4-12 Release 6/2005...
With the exception of the slots reserved for the power supply and IM-R, the CP 443-5 Extended can be inserted in all slots with a P and K bus interface (in the central or in an expansion rack no. 1 -6).
Page 14
You can connect the PG when configuring the CP as follows: for Configuration via MPI via LAN / PROFIBUS The CP 443-5 Extended must already have a PROFIBUS address. For details, see /2/, General Part. CP 443-5 Extended for PROFIBUS / Manual Part B4 B4-14...
(DP slave not in data transfer or not accessible) RUN; however problems on DP chain (faulty module in DP slave). Module fault / system error Legend: flashing Field gray: undefined / any CP 443-5 Extended for PROFIBUS / Manual Part B4 B4-15 Release 6/2005 C79000-G8976-C162-06...
Page 16
- DP slaves are taken out of data transfer - Data record routing is deactivated In the STOP mode - Configuration and diagnostics are possible - The time of day is distributed CP 443-5 Extended for PROFIBUS / Manual Part B4 B4-16 Release 6/2005 C79000-G8976-C162-06...
When there is a large number of modules (DP slaves) configured that can be assigned parameters; When a high value is configured for the constant bus cycle time in the network properties of the PROFIBUS DP chain. CP 443-5 Extended for PROFIBUS / Manual Part B4 B4-17 Release 6/2005 C79000-G8976-C162-06...
Page 18
DP slave expansion (CiR functionality) to the entire DP master system. If you specify the properties of a CiR object in the DP master system of the CP 443-5 Extended in STEP 7, these values are included in checks performed by STEP 7.
Job Active Component / FC min. max. min. max. AG-SEND 0.10 ms 0.11 ms 0.14 ms 0.16 ms AG-RECV 0.13 ms 0.14 ms 0.12 ms 0.13 ms CP 443-5 Extended for PROFIBUS / Manual Part B4 B4-19 Release 6/2005 C79000-G8976-C162-06...
1) one additional 1 S7 connection can be set up online (for example for routing) Note If PG or HMI functions or data record routing are used, a suitable number of S7 connections must be reserved during configuration! CP 443-5 Extended for PROFIBUS / Manual Part B4 B4-20 Release 6/2005 C79000-G8976-C162-06...
Page 21
SFB52 RDREC ”Read data record from a DP slave” corresponds to SFC59 SFB53 WRREC ”Write data record to a DP slave” corresponds to SFC58 SFB54 ALARM ”Read alarm information from a DP slave” 1) PNO: PROFIBUS Users Organization CP 443-5 Extended for PROFIBUS / Manual Part B4 B4-21 Release 6/2005 C79000-G8976-C162-06...
- a remote PC with CP 5412 / 5613 / 5614 Note With transmission rates of < 1.5 Mbps, we recommend that you configure a synchronization interval of at least 10 s. CP 443-5 Extended for PROFIBUS / Manual Part B4 B4-22 Release 6/2005 C79000-G8976-C162-06...
PDM can, however, use several connections to one PA field device (for more information, refer to the manual “PDM - The Process Device Manager”). Use in Fault-tolerant Systems With a CP 443-5 Extended, you have the following options in a fault-tolerant (H) system: S Operating fault-tolerant S7 connections with communication services configured...
The diagnostic/alarm frames are forwarded even when the CPU is in STOP mode, however, they must be evaluated by a suitable user program when the module starts up. CP 443-5 Extended for PROFIBUS / Manual Part B4 B4-24 Release 6/2005...
6 Compatibility with the Previous Product Extended Functionality Compared with Previous Product: Compared with previous products, the CP 443-5 Extended (6GK7 443-5DX04-0XE0) with firmware version V6.0 or higher has significantly improved performance in all services, in particular when they are operated parallel to each other.
Page 26
The information “for new modules” contained in both the STEP 7 / NCM S7 online help and the S7 CPs for PROFIBUS manual is also relevant for the CP described here. Look out for this symbol. CP 443-5 Extended for PROFIBUS / Manual Part B4 B4-26 Release 6/2005...
Page 27
Weight approx. 800 g All the information in /1/ in the Section “General Technical Data” regarding the following topics also applies to the CP 443-5 Extended S Electromagnetic compatibility S Transportation and storage conditions S Mechanical and climatic ambient conditions...