Page 1
The RXZ90.1 is used for wireless reception of the room temperature (from the QAX90.1) and the room temperature setpoint (from the QAX91.1), and for transmission of this information to a room controller. Wireless range indoors: approx. 30m. Types RXZ91.1 Receiver with PPS2 interface Siemens Building Technologies CA2N1644en Building Automation 07.2001...
Page 2
Basically the unit comprises the housing and the mounting plate. These can be snapped together and apart. The housing accommodates a printed circuit board and a tool socket (RJ45). The housing and mounting plate are plastic. 2/11 Siemens Building Technologies RXZ90.1 – Receiver with PPS2 interface CA2N1644en Building Automation 07.2001...
Page 3
• Do not install behind a cover or a metal grid which impedes wireless communication • The unit must be mounted at least 1 metre from the transmitter 3/11 Siemens Building Technologies RXZ90.1 – Receiver with PPS2 interface CA2N1644en Building Automation...
Page 4
Insert batteries in the replacement unit(s); these will switch to installation mode. The receiver recognises all newly connected room units and adds these to its device list. Caution: Wait 4 minutes before changing any further links. 4/11 Siemens Building Technologies RXZ90.1 – Receiver with PPS2 interface CA2N1644en Building Automation 07.2001...
Page 5
• Sustained pressure (>5s) on the button of an existing room unit. The receiver will delete this room unit from its device list and then switch to installation mode 5/11 Siemens Building Technologies RXZ90.1 – Receiver with PPS2 interface CA2N1644en Building Automation 07.2001...
Page 6
PPS2 power supply ON ON continuously PPS2 short circuit Pushbutton Action Brief pressure <1s Sets receiver to installation mode if fewer than 5 room units in device list 6/11 Siemens Building Technologies RXZ90.1 – Receiver with PPS2 interface CA2N1644en Building Automation 07.2001...
Page 7
Sustained pressure >5s Deletes the device list from the receiver and then brings it to the "Normal mode" with an empty device list. 7/11 Siemens Building Technologies RXZ90.1 – Receiver with PPS2 interface CA2N1644en Building Automation 07.2001...
Page 8
See “Dimensions” Colour Front plate NCS S 0502-G ≈ RAL 9003 signal white Housing base and mounting plate RAL 7035 light grey Weight Excluding packaging 0.13 kg 8/11 Siemens Building Technologies RXZ90.1 – Receiver with PPS2 interface CA2N1644en Building Automation 07.2001...
Page 9
N1 RXC… room controller A Connection for RXT10.1 commissioning and service tool B Connection for RXT20.1 service terminal with PPS2 interface C Connection for diagnostic plug 9/11 Siemens Building Technologies RXZ90.1 – Receiver with PPS2 interface CA2N1644en Building Automation 07.2001...
Page 10
Dimensions 00496 10/11 Siemens Building Technologies RXZ90.1 – Receiver with PPS2 interface CA2N1644en Building Automation 07.2001...